Skip to content
Three phase calculator icon

3 Phase Delta/Wye Calculator

Convert three-phase voltages, currents and impedances between delta (Δ) and wye (Y) connections. Enter line or phase values to see the equivalent in the other configuration.This calculator is part of Xindustra’s Industrial Electrical Calculation Tools, a collection of practical calculators designed for electrical and automation applications.

CHOOSE POWER SOURCE
V
A
V
A
kVA
kW
kVAR
Delta configuration symbol
Delta configuration formulas

Vline = Vph

Iline = √3 × Iph

Iph = Iline / √3

S = 3 × Vph × Iph

P = S × PF

PF = P / S

Q = √3 × Vline × Iline × sin φ

Three phase power triangle
Apparent Power S: -- kVA
Real Power P: -- kW
Reactive Power Q: -- kVAR
Power Factor PF: --
Phase Angle φ: -- deg

What is a 3-phase Delta/Wye calculator?

Three-phase power systems can connect loads and sources in two common ways: delta (Δ) and wye (Y or star). The relationship between line and phase voltages, currents and impedances is different in each configuration.

This calculator helps you:

  • Convert between line and phase voltages and currents
  • Compare Δ and Y connected loads at the same line voltage
  • Determine equivalent impedances between delta and wye networks
  • Size motors, heaters and distribution equipment correctly

Basics of delta and wye connections

In a delta (Δ) connection, the three phase windings or loads form a closed loop. Line conductors connect to each corner of the triangle.

In a wye (Y) connection, one end of each phase is tied to a common neutral point, and the line conductors connect to the remaining ends.

Quantity Wye (Y) connection Delta (Δ) connection
Line voltage vs phase voltage VL = √3 × VPH VL = VPH
Line current vs phase current IL = IPH IL = √3 × IPH
Apparent power S = √3 × VL × IL

Voltage and current relationships

Wye (Y) connected loads

  • Phase voltage: VPH = VL / √3
  • Line current: IL = IPH

Delta (Δ) connected loads

  • Phase voltage: VPH = VL
  • Line current: IL = √3 × IPH

The calculator applies these relations automatically to show how a given line voltage and load connection translate into per-phase quantities.

Delta–wye impedance conversion

When converting a three-branch network from wye to delta or vice versa, the branch impedances must be adjusted to preserve the same line-to-line behavior.

From wye to delta

For wye impedances ZA, ZB, ZC, the equivalent delta impedances are:

  • ZAB,Δ = (ZAZB + ZBZC + ZCZA) / ZC
  • ZBC,Δ = (ZAZB + ZBZC + ZCZA) / ZA
  • ZCA,Δ = (ZAZB + ZBZC + ZCZA) / ZB

From delta to wye

For delta impedances ZAB, ZBC, ZCA, the equivalent wye impedances are:

  • ZA,Y = (ZAB × ZCA) / (ZAB + ZBC + ZCA)
  • ZB,Y = (ZAB × ZBC) / (ZAB + ZBC + ZCA)
  • ZC,Y = (ZBC × ZCA) / (ZAB + ZBC + ZCA)

The calculator uses these formulas behind the scenes so you can focus on entering nameplate data and seeing the equivalent values.

Worked examples

Example 1 – 400 V supply, wye-connected load

  • Line voltage: VL = 400 V
  • Connection: wye (Y)

Phase voltage: VPH = 400 / √3 ≈ 231 V

If each phase draws 10 A, then:

  • IL = IPH = 10 A
  • S = √3 × 400 × 10 ≈ 6.93 kVA

Example 2 – same load in delta

To draw the same power at 400 V in delta, the per-phase impedance must change. The calculator can show the required phase currents and new per-phase impedance so that S stays approximately equal.

Design tips for 3-phase Delta/Wye systems

  • Know your line voltage: A “400 V” system usually refers to line-to-line voltage. Phase voltage is lower in wye connections.
  • Check nameplate connection: Motors and heaters may support Y, Δ or both (e.g. 230/400 V). Connecting incorrectly can over- or under-voltage the windings.
  • Balance the phases: Uneven loading between phases causes neutral currents, voltage imbalance and overheating.
  • Consider starting methods: Star–delta motor starters temporarily use Y connection to limit starting current before switching to Δ for full power.

This calculator helps you visualize how three-phase quantities change between delta and wye connections so you can choose the right configuration, verify ratings, and design safer distribution and motor control systems.

FAQ about 3 Phase Delta/Wye Calculator

When should I use a wye connection vs a delta connection?

Wye (Y) is often used when you need a neutral point and lower phase voltage (for example 230/400 V systems feeding both single-phase and three-phase loads).

Delta (Δ) is common for motor windings and balanced three-phase loads without neutral.

The choice depends on required voltage, insulation rating, neutral availability and how the equipment is designed.

What is the difference between line and phase voltage/current?

In three-phase systems:


  • <strong>Line voltage</strong> is measured between two line conductors.

  • <strong>Phase voltage</strong> is measured across a single winding or phase of the load.

  • <strong>Line current</strong> flows in the line conductors; <strong>phase current</strong> flows in each winding or branch.

    The relationship between these quantities depends on whether the load is connected in wye or delta
Can I directly convert a delta-rated motor to wye on the same supply voltage?

Not always. Many motors are marked with dual ratings (for example 230 Δ / 400 Y).

These are designed so that the winding voltage stays within limits in either configuration at the specified supply.

If a motor is only rated for Δ at a certain voltage, using Y on the same line voltage may under-voltage the windings and reduce torque, while using Δ on a voltage intended for Y may over-stress the insulation.

Always follow the motor nameplate and manufacturer guidelines.

Compare products

{"one"=>"Select 2 or 3 items to compare", "other"=>"{{ count }} of 3 items selected"}

Select first item to compare

Select second item to compare

Select third item to compare

Compare