Skip to content

ABB MS116 Motor Protection Circuit Breaker (Manual Motor Starter), 3-Pole

by ABB
Original price $28.00 - Original price $28.00
Original price
$28.00
$28.00 - $28.00
Current price $28.00
Availability:
in stock, ready to be shipped

Compact 3-pole manual motor starter with thermal-magnetic protection and trip class 10A. Adjustable setting ranges (typ. 0.10…32 A), up to 690 V AC, high short-circuit capability (e.g., Ics 50 kA @ 400 V, Icu up to 75 kA, variant-dependent). 45 mm width; wide accessory ecosystem

Refurbished
Most sustainable option 🌿
New factory sealed
Request a quote
12 Month Warranty

12-month warranty

Secure Payment

secure payment

Fast shipping

fast shipping

We Deliver Worldwide

deliver worldwide

Product Description

The ABB MS116 (often called a motor protection circuit breaker / manual motor protector) combines overload (thermal) and short-circuit (magnetic) protection with a front rotary isolator—ideal for direct-on-line (DOL) starters and local motor isolation. The range covers adjustable FLA settings up to 32 A (variant-dependent) and is designed for fuse-less protection with fast magnetic tripping on faults. Typical performance includes Ics 50 kA @ 400 V and Icu up to 75 kA, with trip class 10A, temperature compensation, trip-free mechanism, and clear ON/OFF/TRIP indication. The 45 mm module width saves panel space; accessories (aux/signal contacts, shunt/undervoltage releases, lockable handles, feed-in blocks) are shared with MS132 to simplify stocking. Use with ABB contactors to build compact DOL/RV starters

Technical Specifications

Device type Manual motor starter / Motor protection circuit breaker
Poles 3-pole
Adjustable current ranges e.g., 0.10–0.16 A ... up to 20–25 A / 25–32 A (variant-dependent)
Trip class Class 10A (thermal)
Rated operational voltage Up to 690 V AC
Rated service short-circuit breaking capacity (Ics) Typically 50 kA @ 400 V AC (variant-dependent)
Rated ultimate short-circuit breaking capacity (Icu) Up to 75 kA @ 400 V AC (variant-dependent)
Instantaneous magnetic trip (Ii) Range depends on variant (e.g., ~28–31 A for 1.6–2.5 A unit)
Width 45 mm
Functions Overload, short-circuit, manual isolator, phase-loss sensitivity
Accessories Aux/OF/SD, shunt trip, undervoltage release, lockable handle, power feed-in blocks; shares many with MS132
Standards IEC/EN 60947-2, IEC/EN 60947-4-1 (application dependent)