Can't find what you looking for ?
Fill out the simple form and our team will be happy to assist you
Want to browse on your own? Click the button to see more products in this series
1-pole thermal-magnetic MCB from ABB S200 family. B/C/D trip curves, IEC 60898-1 / 60947-2 compliance, up to 6 kA breaking capacity at 230/400 V AC (model-dependent). DIN-rail, accessory-ready.
Brand / Series | ABB — System pro M compact S200 |
Model | S201 (1-pole) |
Trip Curves | B, C, D |
Rated Current (In) | typ. 6, 10, 13, 16, 20, 25, 32, 40, 50, 63 A |
Rated Voltage | 230/400 V AC (model-dependent); selected DC ratings available |
Breaking Capacity (IEC) | up to 6 kA @ 230/400 V AC (S200 family) |
Standards | IEC/EN 60898-1, IEC/EN 60947-2 (variant-dependent) |
Trip Technology | Thermal-magnetic |
Mounting | 35 mm DIN-rail |
Accessories | Bottom-fitting auxiliaries (OF/SD, shunt, UVT), comb busbars |
No documents available for this product.
Can't find what you looking for ?
Fill out the simple form and our team will be happy to assist you
Want to browse on your own? Click the button to see more products in this series
Request a Quote
resistive/low-inrush loads. C: mixed & small motors. D: high-inrush (transformers, large motors). Always coordinate with upstream devices.
Use ABB S200M/S200P high-breaking versions or ensure upstream current-limiting so the S201’s Icn is not exceeded.
S201 is the IEC family. For UL1077 supplementary protectors see ST201M (ST200M family). Do not mix families—match your market standard.
Compare products
{"one"=>"Select 2 or 3 items to compare", "other"=>"{{ count }} of 3 items selected"}