VFD Wiring Diagram for a Three-Phase Motor

Trace a three-phase VFD from mains to motor, then read the start command and speed reference on original ABB ACS580 power and control drawings.

  • Mason Alexander
  • Published Nov 27, 2026
  • 5 min read
ABB drawing showing the ACS580 terminal layout, including frames R1 and R2, with separate input and motor cable groups and grounding clamps.

Read a three-phase VFD drawing in two passes. First trace the power from the supply, through the drive and out to the motor. Then trace the low-voltage signals that tell the drive when to run and what speed to request. The drawings below use the ABB ACS580-01-07A3-4, frame R1, and the ABB Standard macro. The terminal functions shown apply to this example and should be checked against the installed drive and its active settings. 123

Trace the incoming supply and the motor output

ABB labels the supply terminals L1, L2 and L3. The motor goes on T1/U, T2/V and T3/W. PE is the protective-earth connection on both sides. Follow those labels across the diagram before comparing cable tags or terminal positions. When replacing a drive, confirm the complete model and frame from the label. Models in the same family can have different terminal layouts. 12

ABB three-phase power connection diagram with blue outlines around L1, L2 and L3 and around T1/U, T2/V and T3/W.
The two outlines mark the incoming supply on the left and the motor output on the right. ABB’s numbered callouts identify PE and shielding requirements and an optional output filter.
On the drawingWhat it doesWhat to check
L1, L2, L3Incoming three-phase supply to the driveSupply voltage class, phase count and approved line-side protection
T1/U, T2/V, T3/WVariable-frequency output to the motorMotor cable destination and winding connection for the intended voltage
PE and the cable shieldsProtective-earth and EMC connectionsRequired PE conductors and the manufacturer’s shield terminations at the drive and motor
R− and UDC+/R+ on this R1 designOptional brake resistor connectionApplicable frame, braking requirement and manufacturer’s resistor and protection instructions

The cable drawing calls out PE continuity and shield termination separately. The motor cable screen is bonded around its circumference at the cabinet and motor ends as shown, and its suitability as a protective-earth conductor depends on the installation requirements. The power-terminal illustration below shows the physical separation of the input and output groups. An extra terminal beside them may belong to the brake circuit. Use the markings rather than tracing by proximity. 12

ABB drawing showing the ACS580 terminal layout, including frames R1 and R2, with separate input and motor cable groups and grounding clamps.
On the shared terminal drawing for R1–R4 and R5 v2, 3b marks the input cable side, 3a the motor cable side and 3c the grounding shelf clamps.

On this ACS580-01-07A3-4, the supply-side protection comes from the drive’s own installation or coordination data. A DOL panel drawing can help you recognize the old line-side devices, but the VFD’s output and switching requirements change the retrofit. If a safety switch, contactor or bypass is retained between the drive and motor, use the switching sequence permitted by the manufacturer. In ABB’s vector control example with ramp stop, the motor must come to zero speed before the output contactor opens. ABB’s bypass example also uses interlocking to keep the drive and line paths from closing together. See the DOL power and control drawing to identify which part of the original circuit you are looking at. 123

The VFD fault troubleshooting guide shows how an input or output phase-loss code points to a different side of this drawing.

Separate the run command from the speed request

ABB’s Standard macro drawing puts two different kinds of commands on adjacent terminal blocks. The digital start input asks the drive to run. The analog input asks for a speed or frequency reference through the selected control mode. A valid reference can exist while the motor is stopped. A valid run command can also be present while the drive is using a different reference source than the one shown in the cabinet drawing. 14

ABB Standard macro diagram for analog block X1 with AI1, AGND and the plus 10 volt reference highlighted.
Follow the potentiometer wiper to AI1, and the two ends to AGND and +10V. The blue outline locates those three rows in ABB’s drawing.
ABB Standard macro diagram of the digital control section with DI1 stop and start highlighted.
DI1 is the start input in the macro shown. Follow its switch back to the illustrated auxiliary supply, then locate the digital input common DCOM.
Signal in the ABB Standard macroExample connectionHow to read it
Analog speed or frequency referenceX1:2 AI1 and X1:3 AGNDThe default shown is 0–10 V. Read the signal relative to the analog common.
Potentiometer reference supplyX1:4 +10VIn the drawn potentiometer circuit this supplies the fixed end. The wiper feeds AI1 and the other fixed end returns to AGND.
Digital start requestX2/X3:13 DI1The default shown is stop at 0 and start at 1. Check the selected macro and command source if the cabinet differs.
Digital supply and commonX2/X3:10 +24V, :11 DGND and :12 DCOMThe source drawing identifies the auxiliary supply return and the common for the digital inputs. Verify how the installed supply and input circuit are referenced.

The +10 V terminal belongs to the potentiometer example. For a PLC voltage output, identify the output signal and its return on the PLC diagram and check that the drive input is set for the voltage range being sent. If the project specifies 4–20 mA, verify which input accepts current, its input mode, the loop supply and the scaling. The drawing’s default AI1 example is a voltage input. 14

Verify the two paths before a first run

  1. Identify the exact drive and the applicable diagram. Before working on terminals, have qualified personnel isolate every relevant power source, allow the specified discharge time and verify absence of voltage using the ABB electrical-safety procedure. A stop command or active STO indication does not electrically isolate the drive. 12
  2. Compare cable tags with terminal markings. Trace supply to L1/L2/L3, the motor cable to T1/U–T3/W, and the PE and shield connections to the points shown for the frame. Confirm the motor’s winding links for the intended output voltage. If the supply, motor rating or winding connection is unresolved, return to the VFD sizing guide. 12
  3. Check the control settings against the installed wires. Identify the active control location and the selected start and reference sources. With the machine secured for commissioning, read the drive’s input status and reference display to confirm that the intended command and speed signal each arrive. Verify motor direction and the response to a stop command under the site’s commissioning procedure. 14

If the keypad operates the drive but a PLC command does not, compare what the drive sees on DI1 with the start source selected in remote mode. If the drive accepts the run command but follows the wrong speed, compare the displayed reference with the intended AI1 signal and scaling. Keeping those checks separate narrows the cause without moving wires just to see whether the motor turns. 4

For the corresponding ABB settings, the VFD commissioning guide maps the DI1 command and AI1 reference to the parameters, then walks through the checks for the first local and remote run.