Start with the drive’s state and the point in the machine cycle when it changed. A motor that never received a run command, one that tripped while accelerating and one that tripped while slowing down send you to different checks. On the ABB ACS580-01-07A3-4, the panel shows whether a fault is active, whether a start is inhibited and, for stored faults, what the drive recorded when it tripped. The codes below apply to the ACS580 standard control program. Check the manual revision for the installed firmware. 123
Capture the event before resetting the drive
Open Diagnostics and distinguish Active faults from the Fault & event log. The active list describes the present trip. The event log preserves previous faults, warnings and timestamps. Save the code, text, time and auxiliary code if the drive supplies one. Compare the time with the controller’s run command, a speed change or a production event. For example, a fault that coincides with a stop command is more informative than the same code copied from the panel after the machine is already stopped. 1
In the stored fault details, record the output frequency, DC link voltage and motor current captured at the trip. On the ACS580, the latest snapshot includes 05.81, 05.82 and 05.83 for those three values. They describe one point in time. A trace or machine event log can show whether a value rose gradually, spiked at the event or dropped only after the outputs turned off. 1
| When the problem occurs | First evidence to capture | Where it directs the next check |
|---|---|---|
| Start is requested and the motor never turns | Active fault or inhibit, actual start input, active control location and reference | Command, permission to start or reference path |
| Motor starts to accelerate and trips | Fault code, output frequency and current at the trip, load condition | Acceleration demand, motor data, mechanical load or power path |
| Motor trips as speed falls | DC voltage at the trip, stop request and selected ramp | Regenerated energy, braking arrangement or input overvoltage |
| Motor trips after running for a while | Fault code, time under load, cabinet conditions and other machines affected | Thermal duty, cooling, supply quality or a motor connection |
Keep observation on the panel separate from work at the terminals. Before opening or handling the circuit, qualified personnel should isolate the applicable supplies, observe the specified discharge time and verify absence of voltage under the ABB procedure. Safe Torque Off prevents torque generation under its defined conditions. Electrical isolation is a separate step. 34
No start with no active fault
For the Standard macro example, check the DI1 indication during a permitted start request and confirm which control location is active. If DI1 stays off when the PLC requests start, trace the command and its input common using the VFD control wiring diagram. If DI1 changes, check whether the selected remote control location uses that input. The Start, stop, reference summary is useful here because it shows where the drive is actually taking each signal. 13
If the drive shows a start inhibit, read Active inhibits or parameter 06.18 and trace the stated condition to the machine’s enable or safety logic. If the drive accepts the run command but the reference stays at zero, follow the actual input, scaled reference and selected reference source in the first commissioning guide. An enabled input and a usable speed or frequency reference are separate observations. 1
Overcurrent during acceleration · ACS580 2310
On the ACS580, 2310 means that output current crossed an internal fault limit. ABB also lists earth faults and supply phase loss as possible contributors. In Rev J, auxiliary code 0x83 is an example of software overcurrent detection in phases U and V. That detail narrows the event record. It takes further checks to tell whether the load, motor cable or another component caused it. 2

If the drive accelerates an empty conveyor but trips when it starts loaded, compare the actual loaded start against the last working condition. Look for mechanical drag, a jam or a cycle change. Verify the ramp actually in use and the motor’s voltage, winding connection and rated current. If the trip starts immediately even with the load removed under an approved test, give the motor circuit and supply path priority. An insulation test, where justified, follows the hardware manual with the motor and cable disconnected from the drive as specified. 124
Current rise during acceleration can reflect the time demanded by the application. Check which ramp set is actually selected and whether the event appeared after changing the load or the ramp. Use the VFD sizing guide to check the current and overload rating before proposing a different drive size or limit. 12
DC link overvoltage during deceleration · ACS580 3210
When a high-inertia load decelerates, the motor can feed energy back into the drive. If the drive cannot absorb or dissipate it fast enough, the DC link voltage rises. A 3210 event that recurs as speed falls after a short ramp makes regenerative braking a useful first lead. Confirm that the selected stop is ramp stop, which deceleration ramp is active and what stopping time the machine requires. 124
If the machine can tolerate a longer stop, an approved longer ramp can help distinguish a braking-demand problem. If the stop time is fixed, check the braking duty and the approved resistor and protection for the exact drive. The R1 example has an internal brake chopper and provision for a suitable external brake resistor. The chopper and resistor are separate components. If 3210 also appears during steady running, or several drives record it together, check the incoming supply for sustained or transient overvoltage as well. 234

Trips after the motor has been running
Use the actual code to choose a side of the drive. For 3130 input phase loss, look toward the incoming supply, protective devices and upstream connections. For 3381 output phase loss, look toward the motor cable, connections and any output switching equipment. Use the machine diagram and recent maintenance history to narrow which section needs inspection. An interruption in the supplied power and an open motor lead require different checks. 23
A 4210 IGBT overtemperature fault points to a different line of investigation. Compare the run time and load with normal operation, then check surrounding air temperature, airflow, fan operation and heatsink condition. If the fault occurs after a production or cabinet change, compare continuous motor demand with the drive’s derated duty rating. A drive that restarts after cooling has given you a clue about the conditions when the fault occurred. Record those conditions before changing parts or settings. 24
When a fault is repeatable, use the machine’s approved test plan and change one condition at a time. Record the trigger, the drive’s recorded values and the result. For a fault that starts after a retrofit, include what changed in the wiring, load, parameters or stop sequence. This gives the next person enough information to continue the diagnosis from the same evidence. 12
References
- ACS580 Standard Control Program Firmware Manual
ABB · 3AXD50000016097 Rev G
- ACS580 Standard Control Program Firmware Manual, Fault Tracing
ABB · 3AXD50000016097 Rev J
- ACS580-01 Quick Installation and Start-up Guide for Global IEC Product Types
ABB · 3AXD50001317799 Rev B
- ACS580-01 Drives Hardware Manual, Frames R1–R9
ABB · 3AXD50000044794 Rev G