VFD Setup Parameters for First Commissioning

Set up an ABB ACS580 for a first run. Transfer motor ratings, verify local and remote control, then check the frequency reference, limits and ramps.

  • Mason Alexander
  • Published Nov 27, 2026
  • 6 min read
ABB ACS580 First start assistant Motor nominal values screen and its motor current edit screen.

For a first run, confirm three things in order. The drive must have the connected motor’s rated data, it must take its run command and reference from the intended sources, and its limits and ramps must suit the machine. This guide continues with the ABB ACS580-01-07A3-4 and the ABB Standard macro in scalar mode. The parameter numbers below apply to the ACS580 standard control program. 123

Confirm the installation and record the starting configuration

Have qualified personnel complete the electrical and mechanical checks before commissioning. Verify the supply and motor connections, the machine’s safe operating state and the applicable safeguards. Keep external start commands inactive during setup. The drive can act on an enabled external command when its control location changes. Check the ACS580 power and control drawings if the terminal map or input common is unclear. 12

Record the drive model, firmware, active macro and motor connection. In a retrofit, save the existing parameter set before changing a macro or starting from defaults. The ACS580-01-07A3-4 product code identifies the drive hardware. It does not tell you the installed firmware or the machine’s command configuration. 123

Transfer the motor’s rated values

The First start assistant and the Motor menu let you review the nominal values. Use one consistent nameplate row for the actual winding connection and voltage. For a complete example, ABB’s type test report for the M3AA 112M 8 motor lists 400 V delta, 50 Hz, 4.10 A, 690 rpm and 1.50 kW in its rating section. The same report lists 2.30 A for 690 V star. Copy the applicable rating row from the actual motor when commissioning. The earlier 3 kW selection example gives fewer motor data fields, so this section uses a complete rating row from the type test report. 14

ABB ACS580 First start assistant Motor nominal values screen and its motor current edit screen.
ABB’s First start assistant shows the motor data list and the current edit screen. The displayed 1.8 A belongs to the manual’s screen example.
ACS580 parameterRead from the motor’s rated dataABB M3AA example at 400 V Δ
99.03 Motor typeMotor technologyAsynchronous motor
99.06 Motor nominal currentRated line current at the actual voltage and connection4.10 A
99.07 Motor nominal voltageRated motor voltage for that connection400 V
99.08 Motor nominal frequencyRated electrical frequency50 Hz
99.09 Motor nominal speedRated shaft speed690 rpm
99.10 Motor nominal powerRated shaft output1.50 kW

The report also shows 750 rpm in its no-load test. For nominal speed, use the 690 rpm from the rating row. Likewise the 7.2 A drive rating belongs in the sizing check. The motor nominal current entry takes the motor’s 4.10 A in this example. If the drive requests a direction test or identification run, check the applicable sequence and whether rotation is safe for the coupled machine before accepting it. 134

Verify the run command and the frequency reference separately

With ABB Standard scalar control and external control location EXT1 active, the default start path uses DI1. Parameter 20.01 defines how the external command inputs are interpreted and 20.03 selects the first input source. The frequency reference comes through 28.11, with AI1 scaled as the default source in this example. Changing either source can leave the other path working normally. 12

ACS580 Start, stop, reference menu showing separate lines for AI1 reference, AI1 scaling and DI1 start/stop.
In Primary settings, the menu puts the AI1 reference and DI1 start input on separate lines. The top-left corner shows that the panel is currently in Local.
Check on this configurationWhere to lookWhat you should be able to confirm
Command reaches the inputI/O screen or DI status in group 10DI1 changes with the intended run command
Command is used by the driveActive Local or Remote location, EXT1 and group 20The selected location listens to DI1 for start and has the required enables
Analog reference reaches the drive12.11 AI1 actual value and 12.12 AI1 scaled valueThe input and its scaled value change in the expected direction
Reference is selected28.11 EXT1 frequency source, constant-frequency selection and frequency limitsThe active reference follows the intended source within allowed limits
ABB ACS580 I/O screen with DI1 state 0 and its assigned Start/stop function, plus other digital input states.
The I/O screen shows the input state beside its assigned function. Here DI1 is off and its assigned function is Start/stop.

If the machine is configured so 0–10 V represents 0–50 Hz, then 5 V should produce a 25 Hz scaled reference. At a second authorized test point, 8 V should give a 40 Hz scaled reference under the same mapping. Comparing two points helps distinguish a wrong scale from a wrong reference source. The displayed output may lag during a ramp or be limited by an active override. The 25 Hz is an electrical frequency, and actual shaft speed also depends on the motor and load. If the drive is configured for vector speed control, verify the speed reference and speed limits applicable to that mode. 1

Match limits and ramps to the machine

The ACS580 scalar settings include 30.13 and 30.14 for minimum and maximum frequency. Set those from the machine’s allowed operating range. A pump’s minimum useful operating point or a conveyor’s maximum safe speed may set the boundary. Keep the permitted direction and stop mode with that decision. 1

ABB ACS580 Ramps screen beside its Limits screen, showing acceleration time, deceleration time, stop mode and minimum and maximum frequency.
Ramps and Limits are distinct menus. Use the values approved for the machine when applying these settings.

For scalar frequency ramp set 1, the manual identifies 28.72 and 28.73 as the acceleration and deceleration settings. Verify which ramp set is active. The Standard macro can select the second set through DI5. Acceleration needs to suit load inertia and available torque. If the job requires ramp stop rather than coast, check the chosen stop mode and whether the machine can decelerate in the requested time. A high-inertia load can regenerate into the DC link during deceleration, so shortening the stop time can change the braking requirement. 1

If a trip interrupts acceleration or a ramp stop, use the VFD fault troubleshooting guide to check the event snapshot against the ramp and load before changing another setting.

Log what changes on the first run

  1. Under the site’s commissioning procedure, check direction and stopping at an approved initial reference. Record the selected control location, commanded reference, drive output frequency and motor current. Use the VFD sizing guide if the motor current and duty suggest the drive needs to be reassessed. 12
  2. Verify the remote command path with the machine ready for a controlled run. If the keypad works and DI1 stays off when the controller requests start, the next check is the physical command path. If DI1 changes, check the active control location, start source and enables. If the motor runs at the wrong frequency, compare the AI1 value, the scaled value and the active reference in that order. 12
  3. Save the released parameter set with the drive model, firmware, motor rating row, active command sources, ramps and limits. A written record of the actual I/O and output seen during commissioning gives the next technician a repeatable baseline. 1

References

  1. ACS580 Standard Control Program Firmware Manual

    ABB · 3AXD50000016097 Rev G

  2. ACS580-01 Quick Installation and Start-up Guide for Global IEC Product Types

    ABB · 3AXD50001317799 Rev B

  3. ACS580-01-07A3-4, 3AXD50000038951

    ABB

  4. M3AA 112M 8 Type Test Report, 3GAA114101-_DE

    ABB · 2011-12-28