For a first run, confirm three things in order. The drive must have the connected motor’s rated data, it must take its run command and reference from the intended sources, and its limits and ramps must suit the machine. This guide continues with the ABB ACS580-01-07A3-4 and the ABB Standard macro in scalar mode. The parameter numbers below apply to the ACS580 standard control program. 123
Confirm the installation and record the starting configuration
Have qualified personnel complete the electrical and mechanical checks before commissioning. Verify the supply and motor connections, the machine’s safe operating state and the applicable safeguards. Keep external start commands inactive during setup. The drive can act on an enabled external command when its control location changes. Check the ACS580 power and control drawings if the terminal map or input common is unclear. 12
Record the drive model, firmware, active macro and motor connection. In a retrofit, save the existing parameter set before changing a macro or starting from defaults. The ACS580-01-07A3-4 product code identifies the drive hardware. It does not tell you the installed firmware or the machine’s command configuration. 123
Transfer the motor’s rated values
The First start assistant and the Motor menu let you review the nominal values. Use one consistent nameplate row for the actual winding connection and voltage. For a complete example, ABB’s type test report for the M3AA 112M 8 motor lists 400 V delta, 50 Hz, 4.10 A, 690 rpm and 1.50 kW in its rating section. The same report lists 2.30 A for 690 V star. Copy the applicable rating row from the actual motor when commissioning. The earlier 3 kW selection example gives fewer motor data fields, so this section uses a complete rating row from the type test report. 14

| ACS580 parameter | Read from the motor’s rated data | ABB M3AA example at 400 V Δ |
|---|---|---|
| 99.03 Motor type | Motor technology | Asynchronous motor |
| 99.06 Motor nominal current | Rated line current at the actual voltage and connection | 4.10 A |
| 99.07 Motor nominal voltage | Rated motor voltage for that connection | 400 V |
| 99.08 Motor nominal frequency | Rated electrical frequency | 50 Hz |
| 99.09 Motor nominal speed | Rated shaft speed | 690 rpm |
| 99.10 Motor nominal power | Rated shaft output | 1.50 kW |
The report also shows 750 rpm in its no-load test. For nominal speed, use the 690 rpm from the rating row. Likewise the 7.2 A drive rating belongs in the sizing check. The motor nominal current entry takes the motor’s 4.10 A in this example. If the drive requests a direction test or identification run, check the applicable sequence and whether rotation is safe for the coupled machine before accepting it. 134
Verify the run command and the frequency reference separately
With ABB Standard scalar control and external control location EXT1 active, the default start path uses DI1. Parameter 20.01 defines how the external command inputs are interpreted and 20.03 selects the first input source. The frequency reference comes through 28.11, with AI1 scaled as the default source in this example. Changing either source can leave the other path working normally. 12

| Check on this configuration | Where to look | What you should be able to confirm |
|---|---|---|
| Command reaches the input | I/O screen or DI status in group 10 | DI1 changes with the intended run command |
| Command is used by the drive | Active Local or Remote location, EXT1 and group 20 | The selected location listens to DI1 for start and has the required enables |
| Analog reference reaches the drive | 12.11 AI1 actual value and 12.12 AI1 scaled value | The input and its scaled value change in the expected direction |
| Reference is selected | 28.11 EXT1 frequency source, constant-frequency selection and frequency limits | The active reference follows the intended source within allowed limits |

If the machine is configured so 0–10 V represents 0–50 Hz, then 5 V should produce a 25 Hz scaled reference. At a second authorized test point, 8 V should give a 40 Hz scaled reference under the same mapping. Comparing two points helps distinguish a wrong scale from a wrong reference source. The displayed output may lag during a ramp or be limited by an active override. The 25 Hz is an electrical frequency, and actual shaft speed also depends on the motor and load. If the drive is configured for vector speed control, verify the speed reference and speed limits applicable to that mode. 1
Match limits and ramps to the machine
The ACS580 scalar settings include 30.13 and 30.14 for minimum and maximum frequency. Set those from the machine’s allowed operating range. A pump’s minimum useful operating point or a conveyor’s maximum safe speed may set the boundary. Keep the permitted direction and stop mode with that decision. 1

For scalar frequency ramp set 1, the manual identifies 28.72 and 28.73 as the acceleration and deceleration settings. Verify which ramp set is active. The Standard macro can select the second set through DI5. Acceleration needs to suit load inertia and available torque. If the job requires ramp stop rather than coast, check the chosen stop mode and whether the machine can decelerate in the requested time. A high-inertia load can regenerate into the DC link during deceleration, so shortening the stop time can change the braking requirement. 1
If a trip interrupts acceleration or a ramp stop, use the VFD fault troubleshooting guide to check the event snapshot against the ramp and load before changing another setting.
Log what changes on the first run
- Under the site’s commissioning procedure, check direction and stopping at an approved initial reference. Record the selected control location, commanded reference, drive output frequency and motor current. Use the VFD sizing guide if the motor current and duty suggest the drive needs to be reassessed. 12
- Verify the remote command path with the machine ready for a controlled run. If the keypad works and DI1 stays off when the controller requests start, the next check is the physical command path. If DI1 changes, check the active control location, start source and enables. If the motor runs at the wrong frequency, compare the AI1 value, the scaled value and the active reference in that order. 12
- Save the released parameter set with the drive model, firmware, motor rating row, active command sources, ramps and limits. A written record of the actual I/O and output seen during commissioning gives the next technician a repeatable baseline. 1
References
- ACS580 Standard Control Program Firmware Manual
ABB · 3AXD50000016097 Rev G
- ACS580-01 Quick Installation and Start-up Guide for Global IEC Product Types
ABB · 3AXD50001317799 Rev B
- ACS580-01-07A3-4, 3AXD50000038951
ABB
- M3AA 112M 8 Type Test Report, 3GAA114101-_DE
ABB · 2011-12-28