Skip to content

How to Size a VFD for a Three-Phase Motor

Size a VFD using motor current, load duty and installation derating. Compare two ABB ACS580 drives on a worked 400 V, 3 kW example.

  • Mason Alexander
  • Published Nov 27, 2026
  • 5 min read
ABB manufacturer image of ACS580-01 wall-mounted drives in several frame sizes and enclosures.

Start with the motor’s rated current at the voltage and winding connection you will actually use. Then find a variable frequency drive (VFD) whose output current in the required duty class still covers that value after any installation derating. Check the drive’s short-term overload against what the machine asks for during starting, acceleration and load changes. Two drives with the same kW rating can have different usable current in the same application. 12

Read the motor and supply as a pair

Write down the supply voltage and phase count. Read the motor voltage, current, frequency and winding connection from the corresponding line on its plate. A dual-voltage plate may show two currents. Use the current that goes with the connection you will use at the drive output. For example, a plate marked 230 V Δ / 400 V Y calls for the 400 V star connection on a 400 V drive output. The motor terminal diagram still decides the actual links. A VFD application does not use the timed star-to-delta changeover found in a star-delta starter. 24

Keep drive input and output ratings separate. The motor current belongs in the drive output comparison. The drive input rating and the manufacturer's protection table belong in the supply-side design. If the available supply is single-phase, look up a drive explicitly rated for that input and separately confirm its three-phase output voltage and current. The suffix and input phase count matter when two models look alike. 124

Choose the duty column from the load

A centrifugal fan normally asks for less torque as speed drops. A loaded conveyor can require substantial torque at low speed and during a loaded restart. Use these distinctions to work out how much current the drive must deliver, for how long, and how often the event can recur. Two machines with the same steady motor current can need different drive ratings because the next overload may come before the drive has recovered. 12

If the load will only run at line speed, the soft starter versus VFD comparison shows when controlling the start or stop is sufficient and when a drive offers something the machine needs.

In the ABB 400 V table, Iₙ is the nominal continuous current at 40 °C without overloadability. For the two R1 models below, the light-duty current Iᴸᵈ allows 110% of that column’s value for one minute every ten minutes at 40 °C. The heavy-duty column Iᴴᵈ allows 150% of its own value on that schedule. ABB lists Iₘₐₓ separately for two seconds at start. Read the time and repeat interval with the current. A two-second maximum cannot cover a sustained load. 14

ABB manufacturer image of ACS580-01 wall-mounted drives in several frame sizes and enclosures.
ABB’s wall-mounted ACS580-01 range spans multiple frame sizes. The two 400 V models compared below are both frame R1.

Work through a 400 V, 3 kW, 6.5 A example

ABB’s 400 V coordination table includes a 3 kW, 6.5 A motor example with the ACS580-01-07A3-4. Use that row as a set of motor inputs and read the separate 400 V drive ratings below to see how the answer changes with duty. The 6.5 A figure comes from the manufacturer’s table. This example assumes the machine can reach full motor load and starts the current comparison at the catalog rating conditions. 13

ABB catalog extract with the 400 V rating columns with the ACS580-01-07A3-4 and ACS580-01-09A5-4 rows outlined.
Read across the highlighted rows from nominal current to the light-duty and heavy-duty columns. The catalog gives separate ratings for 480 V.
ABB drive at 400 VNominal IₙLight-duty IᴸᵈHeavy-duty Iᴴᵈ
ACS580-01-07A3-47.2 A6.8 A5.6 A
ACS580-01-09A5-49.4 A8.9 A7.2 A

For a fan that fits ABB’s light-duty overload profile, the ACS580-01-07A3-4 passes the initial comparison: 6.8 A minus 6.5 A leaves 0.3 A. For a loaded conveyor that needs the heavy-duty profile, that drive is 0.9 A short at 5.6 A. The ACS580-01-09A5-4 is the next candidate at 7.2 A heavy-duty, with 0.7 A of margin before derating. In either case, finish the application check by comparing the actual overload pattern with ABB’s limits. 14

Recheck available current at the installation site

At 1,500 m elevation and 40 °C surrounding air temperature, ABB’s altitude rule gives 5% derating, based on 1% per 100 m above 1,000 m. With just that factor, the light-duty comparison becomes 6.8 A × 0.95 = 6.46 A, just below the motor’s 6.5 A. The larger drive’s 7.2 A heavy-duty rating becomes 6.84 A under the same assumption. If a higher minimum switching frequency or a different enclosure adds another restriction, run the calculation again. Keep the unrounded result for the comparison. 4

ABB graph of drive current derating factors by installation altitude and surrounding air temperature.
At 40 °C and 1,500 m, ABB’s dashed 0.95 line gives the factor used in the example.

Check the specific enclosure and frame and the actual air temperature around the drive. Also check whether the drive’s minimum switching frequency requires derating. ABB shows how to combine applicable factors and how a lower surrounding air temperature can alter the altitude correction. On the motor side, a shaft-mounted fan turns more slowly with the shaft. A conveyor running for long periods at low speed may need a motor thermal check or separate ventilation even where drive current is adequate. 24

If the installed drive is already tripping, use the VFD troubleshooting guide to identify the load, supply or cooling evidence that should inform the sizing check.

Record the selection before quoting or ordering

A simple worksheet makes it possible for someone else to repeat the decision. If an important box is blank, ask for a motor plate photo, the machine’s load cycle or the cabinet design temperature before finalizing the order.

Record thisWhat to compare
Supply voltage and phase countDrive input rating and complete suffix
Motor voltage, connection, frequency and full-load currentMotor configuration at the intended drive output
Starting and running load, acceleration time and frequency of overloadsDrive duty rating and the duration and repetition of its permitted overload
Cabinet air temperature, altitude and switching frequencyApplicable drive derating, with the remaining continuous current still above the required motor current
Stop behavior, cable run and control interfaceBraking requirements, cable or filter limits, and the terminals or communications needed by the controller
Supply protection and local disconnect arrangementManufacturer’s approved protection for the exact drive and the conditions of that combination

If the job only needs controlled starting and the motor then runs at line speed, revisit the three-phase motor starter selection guide before committing to a drive. If the duty and installation checks pass, carry the full model and frame into the three-phase VFD wiring diagram. That is where the incoming line, motor cable and control signals become three distinct things to verify. 34

References

  1. ABB General Purpose Drives, ACS580

    ABB · 3AUA0000145061 Rev R

  2. How do you size a VFD?

    Danfoss

  3. 400 V ACS580-01 Drive Starter Coordination Table

    ABB · Table 5722

  4. ACS580-01 Hardware Manual, Ratings and Derating

    ABB · 3AXD50000044794 Rev C