Star-Delta Starter: How to Read the Motor Nameplate, Wiring Diagram and Changeover Sequence

Read a real ABB motor rating, decide when star-delta starting fits the load, and follow the three contactors, interlocks and transfer timing on original manufacturer drawings.

  • Mason Alexander
  • Published Nov 26, 2026
  • 8 min read
Schneider Electric TeSys K LC3K prewired star-delta starter assembly with three contactors and timer.

A star-delta starter starts a three-phase induction motor in star to reduce starting current, then switches it to delta for normal running. It works when three conditions are met: the motor is rated to run in delta at the available line voltage, all six winding ends are accessible, and the load can accelerate on the reduced torque available in star. The transition also has to suit the starter and the machine. 12

Read the delta voltage and the terminal diagram first

In ABB's type-test report for the M3AA 112M 8, product code 3GAA114101-_DE, the 50 Hz ratings show 1.5 kW at 400 V delta and 690 V star. ABB lists 4.10 A for 400 V delta and 2.30 A for 690 V star. These are rated running conditions at two different supply voltages. The report uses D and Y for delta and star. 3

ABB M3AA 112M 8 test report excerpt listing 690 V Y at 2.30 A and 400 V D at 4.10 A, both at 50 Hz and 1.5 kW.
The ABB report gives two rated running conditions. Read the 400 V D row for delta running on a 400 V supply. The 690 V Y row is rated star running on a different supply voltage.

On a 400 V supply, the motor runs in delta and each winding receives 400 V. During a star start on the same supply, each winding receives 400 ÷ √3, or about 231 V. The 2.30 A figure from the 690 V row does not give the starting current in star on 400 V. Similarly, the 4.10 A figure is the motor's rated running current. Use the motor's starting characteristics and the installation conditions for a starting-current estimate. 13

Motor marking and supplyWhat to conclude
400 V delta / 690 V star motor on 400 VThe winding voltage permits a star start and delta run. Check the six leads, load and transition separately.
230 V delta / 400 V star motor on 400 VThe normal connection is star. A transition to delta would put 400 V across windings rated for 230 V.
400 V delta / 690 V star motor on 690 VThis supply matches the motor's star rating. The 400 V delta winding rating still controls whether a delta run is possible at a given line voltage.
The delta rating fits, but the motor exposes only three leadsA conventional external star-delta starter needs access to both ends of each winding. Check the motor maker's terminal drawing and the actual terminal box.

Look for U1/V1/W1 and U2/V2/W2 on the motor and the drawing, or their equivalents on the exact model. On a fixed-connection motor those winding ends may be joined by links or connected internally. With an external changeover starter the drawing determines how all six ends are brought to the starter. Confirm the winding ends and terminal links from the maker's instructions before any work on the connections. 12

Check whether the load can accelerate in star

At the same supply voltage, the voltage across each winding in star is about 58% of its value in delta. In a simplified standstill comparison with the same winding impedance, starting line current is about one-third of a DOL start in delta. Starting torque also falls, roughly to one-third in the ideal voltage-squared model. ABB's guide notes that practical torque reduction can be greater. The useful question is whether the motor in star develops more torque than the load requires through the acceleration interval. 1

A centrifugal fan may have modest shaft torque at low speed, yet its inertia can make acceleration slow. A loaded belt may need high breakaway torque from the moment it moves. For each application, check the actual load and acceleration, whether starting unloaded is possible, the supply's allowable voltage dip, and how often the machine starts. If the motor settles at a low speed in star, leaving it in star longer will not solve a torque deficit. If DOL is acceptable, it can be the simpler choice. If the process requires a smoother start, compare soft starting, and consider a drive where normal running needs variable speed. The three-phase motor starter selection guide compares those choices against supply and load requirements. 12

Trace the three contactors on the original power drawing

Schneider Electric TeSys K LC3K prewired star-delta starter assembly with three contactors and timer.
Schneider’s TeSys K LC3K assembly shows the contactors and timer as a prewired group. The motor rating still determines which tested combination applies.

Schneider's TeSys K guide shows a prewired LC3K assembly with three contactors, a timer and a built-in mechanical interlock. That group photo shows what the pieces look like together. Pick the actual assembly from the manufacturer's rating and coordination tables for the motor and installation. The photograph and the ABB motor test report are separate examples. 23

Schneider Electric original star-delta power diagrams showing the three contactors and six motor ends, with inside-delta and line-side overload examples.
Schneider’s power drawings use KM1 for star, KM2 for line and KM3 for delta. Compare the overload location on the left with the line-mounted relay on the right. These are the manufacturer’s illustrated coordination arrangements.

Schneider's TeSys guide uses KM1 for star, KM2 for line and KM3 for delta. In the Type 1 drawing, KM2 establishes the line feed to the first ends of the three windings. KM1 brings the other ends together for the star connection. When KM1 has opened, KM3 makes the cross-connections required for delta. Read the device tags and connections together. A different manufacturer's drawing may number the contactors differently. 2

The model number of a contactor is also a separate decision from its role on this drawing. For instance, the ABB AF26-30-00-13 illustrates why the coil code and built-in auxiliary contact count need to be checked independently of the main poles. Use the manufacturer's tested star-delta combination and the actual starter diagram for the line, star and delta contactors. The motor starter versus contactor guide explains what those parts do and which specifications a replacement must preserve. 26

The overload relay may be in the full line-current path or in the delta branch. The two Schneider power drawings show both placements in different coordinated designs. For the ABB motor example, 4.10 A line current corresponds to roughly 2.37 A winding current in balanced delta. Check the actual relay location and the tested assembly before using either current as the basis for its setting. The thermal overload relay selection guide works through placement, range and trip class. 237

Read the open-transition sequence before looking at timer values

StateLine contactorStar contactorDelta contactorWhat the motor sees
StoppedOpenOpenOpenNo commanded connection to run.
Starting in starClosedClosedOpenReduced voltage across each winding.
Changeover gapClosedOpenOpenThe winding circuit is temporarily open and the motor coasts. The line contactor can still leave terminals live.
Running in deltaClosedOpenClosedEach winding receives line voltage.
Stop or protective tripOpenOpenOpenThe control arrangement drops the commanded outputs. Isolation is a separate step.

Separate the acceleration time from the changeover gap

ABB CT-SDS.23 timing chart with 17–18 active for t₁, both outputs open through t₂, and 17–28 active after the gap.
Read the two output rows. Star opens at the end of t₁. Delta closes after t₂, the 50 ms transition time specified for this ABB timer.

ABB's CT-SDS.23 timer illustrates the two intervals. Its first normally open output, 17–18, commands star while the adjustable time t₁ runs. That output drops out, and the timer waits through a fixed t₂ of 50 ms before 17–28 commands delta. The 50 ms belongs to this timer model. It is not an adjustment target for another combination. The timer's outputs are commands. The complete control and protection drawing determines the line contactor, permissives, feedback and release behavior. 4

Set the star interval using the equipment maker's procedure and the actual acceleration under the intended load. An early transfer can close delta at low speed, with a high current step and a sharp torque change. A long changeover gap can allow speed to fall, and the motor's residual voltage may differ in phase from the supply at reconnection. Check the contactors' release behavior and the coordination instructions rather than copying a timer value from another motor. 125

The star and delta contactors must not close together. In the documented arrangement, the mechanical interlock prevents simultaneous closure at the mechanism. Electrical interlocking uses the opposing contactor's normally closed auxiliary in each coil path to prevent conflicting commands. The timer provides the break-before-make interval. Those three features address different parts of the transfer. On Schneider's TeSys K control drawing, trace the KM3 auxiliary in the KM1 coil branch and the KM1 auxiliary in the KM3 branch. The 21–22 normally closed contacts implement the cross-lockout in that example. The 95–96 overload contact is upstream on the control supply path. 2

Schneider TeSys K LC3K control circuit with 95–96 overload contact, KM1 and KM3 interlock auxiliaries, and three coil branches.
In this LC3K control circuit, the 95–96 contact interrupts the upstream control path. The 21–22 auxiliary contacts cross-lock the star and delta coil branches.

The DOL wiring guide is a useful reference for tracing a coil, an auxiliary contact and the protective stop path before reading the additional branches here.

Match the symptom to the stage of the start

What you observeWhat to check first
The motor hums or fails to accelerate in starConfirm the motor connection, supply and all three phases. Compare load torque with the available star torque and check whether the driven machine can start unloaded.
It accelerates in star, but trips as delta closesEstablish the speed at transfer and verify the intended winding connections, opening of star before delta and changeover timing. Check the protective device indication and the actual current trace before changing settings.
It drops out during the changeover and never runs in deltaTrace the delta command, opposite interlock, coil supply and protective permissives against the control drawing. Confirm whether it is a missing command or failure of a contactor to pick up.
It transfers correctly, then trips later in deltaCheck running load and phase current, relay placement and adjustment, and thermal history.

Before accepting a start, record the nameplate voltage and current, the six leads and their drawing references, the expected contactor states, the start and transfer observations, and where the overload measures current. Follow the machine's isolation and commissioning procedures. Treat a timed gap as a transition in the control sequence, never as proof that the motor terminals are isolated.

References

  1. Softstarter Handbook

    ABB · 1SFC132060M0201

  2. Control Panel Technical Guide: How to quickly design optimized contactor assemblies

    Schneider Electric · CPTG011_EN

  3. M3AA 112M 8 type test report, 3GAA114101-_DE

    ABB · 2011-12-28

  4. CT-SDS.23 electronic timer data sheet

    ABB · 2CDC111128D0201

  5. Timing function for larger TeSys star-delta contactors

    Schneider Electric · FA24956

  6. AF26-30-00-13 contactor, 1SBL237001R1300

    ABB

  7. Overload relay position for a star-delta starter

    Schneider Electric · FA86594