Select a thermal overload relay using the current that actually passes through it, the time the motor needs to accelerate, and the protection combination specified for the starter. The motor nameplate gives the starting point for the current setting. The power diagram tells you if the relay measures line current or winding current. The relay curve tells you how the device responds to an overload after a cold start or after the circuit has already warmed up. 134
Match the setting range to the current through the relay

Begin with rated motor current at the installed voltage, frequency and winding connection. Use that current as the basis when the relay measures the full motor line current, then follow the motor and relay instructions and the applicable installation rules for the final setting. Select a relay range that contains the required setting. The number at the top of the adjustment range is a device limit. It is not automatically the dial setting for the motor. 12
Take the 3 kW, 400 V, 6.5 A example in the three-phase motor starter selection guide. For a separate relay in the line, 6.5 A falls within both the ABB TF42-7.6 and the Schneider LRD12 adjustment ranges. That answers the first selection question only. The relay still has to fit the chosen contactor and control circuit, have the required trip characteristic, and form a tested combination with the upstream protective device. 125
| Reference | Adjustment range | Published trip class | What to check next |
|---|---|---|---|
| ABB TF42-7.6, 1SAZ721201R1040 | 5.70–7.60 A | 10 | Matching ABB contactor, trip and signaling contacts, mounting, and documented upstream protection. |
| Schneider TeSys LRD12 | 5.5–8 A | 10A | Compatible LC1D frame and connection style, reset mode, and the tested starter combination. |
A motor starter may already have integrated overload protection. The ABB MS116-10 has a 6.30–10.00 A adjustable range and magnetic short-circuit tripping. The earlier 6.5 A ABB coordination example uses that manual starter with an AF26. The separate-relay examples above illustrate a different architecture. Use the motor starter versus contactor comparison to identify which architecture is installed before looking for a relay. 5
Check whether the relay is in the line or inside delta
For a DOL circuit, the overload elements in the power path carry motor line current. In a star-delta starter the relay can be located in the line or in the delta branch, depending on the approved design. A line-mounted device sees full line current in normal running. A relay inside delta sees winding current, about line current divided by √3 for balanced delta operation. Read the three current paths on the actual drawing, then use the manufacturer's instructions for the position and setting. 4
For example, ABB's test report for the M3AA 112M 8 lists 4.10 A at 400 V delta. In an otherwise suitable line-sensing installation this is a 4.10 A current basis. A relay inside a balanced delta connection would see about 2.37 A at that running point (4.10 ÷ √3). The two values lead to different relay ranges. The calculation does not authorize moving a relay from one location to another within a tested assembly. 46
To locate the sensing elements before choosing a setting range, compare the line-side and inside-delta power drawings in the star-delta starter guide.
Read the trip curve with starting time and thermal history

Trip class describes a time range under a specified test condition. It is not the number of seconds every motor can run above its setting. Schneider's LRD catalog specifies a 2–10 s window for class 10A at 7.2 times the current setting from cold under the stated IEC test. 7 ABB identifies the TF42 as class 10 and gives a representative cold curve. Retain the exact class suffix and curve when comparing replacements. Dividing a measured or specified start current by the relay setting tells you where to read the horizontal axis. Consider the time and the relay's thermal state together. 123
For an illustrative line-mounted arrangement, use a 6.5 A setting and a 39 A current during part of acceleration. That point is 6.0 times the setting on the chart. Compare the actual current-versus-time trace with the manufacturer's cold and hot characteristics and the motor's thermal limits. The 39 A value is an illustrative calculation input. It is not a measured start value for the ABB coordination example. 135
A relay that accepts the first cold start may trip on a restart after a short stop. Schneider publishes distinct LRD characteristics for three-phase cold, three-phase hot and two-phase cold operation. If repeated starts are involved, check the entire cycle, including run time, restart interval and enclosure temperature. A slower class or higher dial setting can also leave the motor exposed longer to a stalled load. Review the motor's permitted stall or acceleration time before changing either. 13
Use the curve to compare two start histories
A useful check is to place the first cold start and the first restart on the same current-versus-time record. If the peak current is similar but the restart trips earlier, include the preceding run and cool-down time in your diagnosis. If the current remains high for longer on both starts, compare the acceleration with the driven load and supply voltage. A trip curve represents a response under defined initial conditions. For a varying start current, avoid treating one point on that curve as a prediction of the exact trip time. 13
Follow the trip contact back to the contactor

Motor current passes through the overload's three sensing elements. ABB's TF42 diagram shows the normally closed 95–96 trip contact and the normally open 97–98 signaling contact. In the reset state, 95–96 is closed and 97–98 is open. After a trip, the states reverse. A circuit designer can use 95–96 to interrupt the contactor coil and 97–98 for an alarm if the drawing calls for it. Follow the full DOL power and control diagrams to see how opening the trip contact drops the contactor and breaks the holding path. 1
Automatic reset can make the trip contact available again after the relay recovers. Whether that can restart the motor depends on the command circuit. Verify the installed reset mode, the state of any maintained command, and the machine's restart design before handing the equipment back. 13
Diagnose the trip before changing the setting
| When it trips | What to check first |
|---|---|
| During the first start | Compare the load and acceleration time with the specified start, and check line voltage, the winding connection and current in all three phases. |
| On a warm restart | Review start frequency, cool-down time, load and the hot characteristic of the exact relay. |
| After running normally for a while | Check for a rising mechanical load, loss or imbalance of a phase, supply problems, and an incorrect setting for the relay's circuit position. |
| At irregular times after a replacement | Verify the current range, trip class, mounting, ambient conditions, supply and reset behavior against the previous device and drawings. |
Before installing a replacement, record the motor's rated current, relay position, intended setting, trip class and reset mode. Then record the contactor and upstream short-circuit device used in the verified combination. Keep those details together. They explain why an overload relay with a similar housing and current range can behave differently after installation.
References
- Thermal overload relay TF42 data sheet
ABB · 2CDC106023D0202, 08.2025 PDF
- TeSys LRD12 thermal overload relay product data sheet
Schneider Electric · LRD12
- LRD cold and hot state trip characteristics
Schneider Electric · FA284601
- Overload relay position for a star-delta starter
Schneider Electric · FA86594
- 400 V DOL normal-start coordination table, MS116 and AF contactors
ABB
- M3AA 112M 8 type test report, 3GAA114101-_DE
ABB · 2011-12-28
- TeSys LRD overload relays catalog
Schneider Electric · B11