A contactor switches the motor circuit on command. A magnetic motor starter combines that switching function with motor overload protection, usually using a separate relay or an integrated motor-protection device. A manual motor starter such as ABB's MS116 adds a local handle and protective trip functions, but has no contactor coil for a normal PLC run command. To choose a replacement, identify which of those functions the original part provides and which devices complete the circuit around it. 123
Identify the switching and protection functions
In a direct-on-line (DOL) starter, the coil of the contactor moves the three power contacts together. That allows a pushbutton, control relay or other compatible control circuit to switch the motor without routing motor current through the control device. The contactor's motor-duty current rating tells you about its ability to make and break the load under defined conditions. It does not tell you when the motor should trip on sustained overload. 23
A thermal overload relay senses motor current. A sustained overload heats its bimetal elements and operates an auxiliary trip contact. In a conventional starter, that normally closed contact opens the coil circuit, so the contactor disconnects the motor. The relay also has a distinct signaling contact on many models. Branch short-circuit protection is another function and must be provided by the protection arrangement specified for the circuit. 35
| Device in the circuit | What it does | What to look for when identifying it |
|---|---|---|
| Contactor | Opens and closes the main contacts in response to the coil. | A1/A2, main poles, coil range, utilization category and exact auxiliary contact configuration. |
| Thermal overload relay | Senses overload and operates a trip contact. | Current-setting dial, trip class, reset selector, trip contacts and compatible mounting. |
| Manual motor starter | Switches locally and can integrate thermal overload and magnetic short-circuit tripping. | Handle, adjustable current range, instantaneous trip characteristics and accessory contact arrangement. |
| Magnetic DOL motor starter | Combines remotely commanded switching and motor overload protection. | Contactor, overload device and control circuit. Confirm the upstream short-circuit protection and any enclosure or disconnect separately. |
See how an enclosed starter combines the parts

ABB's DRAF enclosed DOL example includes a contactor with a holding contact, an enclosure with ON and OFF/RESET controls, and an arrangement for a TF42 thermal overload relay. The leaflet lists the relay separately so its setting range can be matched to the motor. That is a useful distinction when ordering a replacement. The enclosure and contactor reference alone do not identify the correct overload relay. Read the complete starter drawing and the installed relay label. 3
A second DOL arrangement uses a manual motor starter as the upstream protective device with a separate contactor for routine switching. ABB's published 400 V, 50 kA, normal-start coordination table includes a 3 kW / 6.5 A row with the MS116-10 and an AF26. The protection in that combination comes from the MS116. The AF26 provides commanded switching. Compare the scheme with the three-phase starter wiring guide, which shows a different layout using a contactor and a separate overload relay. 4
Compare two actual ABB devices before ordering

The AF26-30-00-13, order code 1SBL237001R1300, is a three-pole contactor. ABB lists 26 A in AC-3 at 380/400 V under the stated conditions and a 100–250 V AC/DC coil range. This exact variant has zero built-in normally open and zero built-in normally closed auxiliary contacts. It cannot reproduce a wired auxiliary holding or PLC feedback contact by itself. Check whether the original build uses a compatible auxiliary block, and match the required contact form and its state in the drawing. 2
The MS116-10, order code 1SAM250000R1010, is a manual motor starter with a 6.30–10.00 A adjustable overload range. ABB's coordination table also shows a 150 A instantaneous trip current for that device in the stated row. These are different numbers with different jobs. The adjustable range is used to match the motor's normal current. The instantaneous value concerns short-circuit tripping. Neither number gives a contactor coil voltage or a contactor switching rating. 14
Three common replacement choices follow from those labels. If the job calls for local manual switching and protection, check the manual starter and its rating as applied. If the motor must start on command from a control circuit, identify the contactor and the coil interface as well. If the original assembly has a separately fitted overload relay, choose its replacement by setting range, trip class and compatibility with the actual contactor. The thermal overload relay selection guide shows how to make that third decision. 1235
Check two common parts-counter substitutions
A contactor with the right power rating can still be wrong for the control circuit. For example, a cabinet with a 24 V DC coil supply cannot use the AF26-30-00-13's 100–250 V coil as a direct replacement. In a cabinet with a compatible coil supply, the same model can still be missing the auxiliary contact needed for the holding branch or the PLC run feedback. Verify the voltage at the source and count the contacts the drawing actually uses before choosing a suffix. 2
A wider overload setting range does not establish that a replacement protects the motor in the same way. If the old assembly uses an MS116 with a magnetic release, a thermal relay on its own changes the protection arrangement. If it uses a separate thermal relay, confirm the contactor interface and the relay's reset and indication features. Keep the fault-current rating with the tested combination from the manufacturer, including the permitted upstream device and connecting accessories. 1345
Match the replacement to the fault and the drawings
A motor that stops with the overload's trip indication showing needs a load and protection diagnosis. A coil that never picks up needs the control path checked. A contactor that closes normally while one motor phase is missing needs the power path checked. These results lead to different parts of the circuit. The machine drawing should tell you whether the contactor is supposed to release on an overload, which contact interrupts it and what state the controller expects afterward. 35
| What you are replacing | Checks that can change the part number |
|---|---|
| Contactor only | AC-3 or other applicable duty, rated voltage and current for that duty, coil type and voltage, required auxiliary contacts and overload mounting. |
| Overload relay only | Motor current where the relay measures it, trip class, reset behavior, trip and alarm contacts, mechanical fit and tested coordination. |
| Complete starter | Starting method, load and start duty, coil supply, enclosure and control arrangement, available fault current and verified short-circuit protection. |
- Record the original order codes, coil marking and actual motor nameplate current. Trace the power and control drawings to see where the parts sit.
- Match the function that needs replacement. Verify contact arrangement, mounting and the manufacturer-approved combination at the installation's voltage and fault current.
- Check the machine's normal stop, overload trip and restart behavior under its commissioning procedure. Confirm both a safe stopped state and how the controller recognizes a trip.
If the original DOL arrangement struggles because the supply dips or the driven machine cannot take the start, the three-phase motor starter selection guide compares the operating conditions for direct starting, star-delta and soft starting. A mechanically compatible replacement can reproduce the same unwanted starting behavior.
For a panel that already uses star-delta, the star-delta starter guide maps each contactor to its line, star or delta role before you compare replacement coil and auxiliary specifications.
References
- MS116 manual motor starters technical datasheet
ABB · 2CDC131025D0201 Rev B
- AF26-30-00-13 contactor, 1SBL237001R1300
ABB
- DRAF enclosed direct-on-line starters
ABB · 1SBC100198L0201
- 400 V DOL normal-start coordination table, MS116 and AF contactors
ABB
- Thermal overload relay TF42 data sheet
ABB · 2CDC106023D0202, 08.2025 PDF
