Yaskawa A1000 AC Drives

Yaskawa A1000 vector AC drives. This selection covers ten US CIMR-AU4A FAA orders with 380–480 V three-phase input and NEMA Type 1 enclosures. Compare model-specific Normal Duty and Heavy Duty currents, installation dimensions and control options.

View products

Build the selection around the installed load

Duty, physical enclosure and optional interfaces are separate choices.

  1. 01

    Normal Duty versus Heavy Duty

    ND allows 120% of rated output current for 60 seconds; HD allows 150% for 60 seconds. Select against motor current and the load cycle, and apply carrier-frequency/thermal derating where needed.

  2. 02

    Use the complete FAA outline

    FAA is the selected NEMA Type 1 arrangement, with −10 to +40 °C ambient. UAA flange and AAA protected-chassis versions have different dimensions and installation conditions. These are not interchangeable enclosure suffixes.

  3. 03

    Separate built-in functions from expansion

    The first ten include a braking transistor, LCD operator and Modbus serial interface. External braking resistors, DC link chokes, feedback cards and industrial network options are selected separately.