Skip to content

Phoenix Contact TRIO POWER Second Generation Power Supplies

Phoenix Contact TRIO-PS-2G DIN-rail power supplies with push-in connections and dynamic boost. This selection covers 24 V DC single- and three-phase models and 48 V DC single-phase models, including the compact 3 A C2LPS unit.

View products

TRIO-PS-2G power supplies

Choose the mains input and DC output first, then check continuous load, short peaks, wiring and cabinet space.

Size the supply around its operating conditions

Generation, rated load and cabinet installation matter more than a shared TRIO POWER name.

  1. 01

    Keep the generation and item number exact

    TRIO-PS-2G is the second-generation platform. TRIO3 is a separate generation, and QUINT4 is a different product family. Use the numeric Phoenix Contact item number together with the complete type designation.

    • This initial selection excludes UPS, DC/DC, redundancy, IP67 field supplies and B+D marine variants.
    • The 3 A C2LPS variant is an NEC Class 2 supply according to UL 1310.
  2. 02

    Continuous current is not boost current

    Dynamic boost provides 150% of nominal current for brief load peaks: one second for 2903147 and five seconds for the other selected models. It does not increase the continuous power rating.

    • Raising the output voltage above nominal reduces available current at constant power.
    • Above +60 °C ambient, reduce output by 2.5% per kelvin.
  3. 03

    Check terminals, clearance and monitoring

    Push-in conductor ranges and stripping lengths vary by terminal group and current rating. The floating DC OK contact is a monitoring signal, not a load output.

    • Reserve 50 mm vertical clearance; horizontal spacing depends on ambient temperature.
    • Check exact housing width and altitude limits on the selected product.