Exact product identification
Your quotation references the complete manufacturer part number to keep the requested product clear.

2903147
TRIO-PS-2G/1AC/24DC/3/C2LPS: single-phase DIN-rail power supply, 24 V DC / 3 A (72 W), with 4.5 A dynamic boost for 1 second. Push-in wiring, DC OK contact and a 30 mm-wide housing.
Warranty coverage and terms are confirmed with your order.
We coordinate the fastest available shipping option for your destination.
Available payment methods are handled through secure payment channels.
Carrier and delivery options are confirmed for your destination before dispatch.
Independent supplier: Xindustra is not an authorized distributor, reseller, or representative of Phoenix Contact. Brand names are used for identification and compatibility purposes only. Read disclaimer
Output capacity, input supply, connection details and cabinet installation for TRIO-PS-2G/1AC/24DC/3/C2LPS.
TRIO-PS-2G/1AC/24DC/3/C2LPS supplies 3 A continuously at 24 V DC (72 W). Its dynamic boost delivers 4.5 A for 1 second for short load peaks; this is not its continuous output rating. This C2LPS version is certified as an NEC Class 2 power source according to UL 1310.
| Parameter / condition | Continuous | Dynamic boost |
|---|---|---|
| Output voltage | 24 V DC | 24 V DC |
| Output current | 3 A | 4.5 A |
| Output power | 72 W | 108 W |
| Duration | Continuous within installation ratings | 1 s |
Ratings are at nominal output voltage. The 3 A C2LPS unit has a one-second boost, not the five-second boost of larger models.
24 V DC ... 28 V DC (> 24 V DC, constant capacity restricted)
> 89 % (for 230 V AC and nominal values)
< 50 mVPP (with nominal values)
yes, for redundancy and increased capacity
yes
The adjustment range does not increase the 72 W continuous rating. Above 24 V, the constant-power operating limit reduces the available current. Size the supply for the load at the actual set voltage, including cable voltage drop and startup demand.
This 1AC version accepts nominal 100–240 V AC or 110–250 V DC. It is not a 400 V three-phase input model. Keep the AC supply within the stated 85–264 V range.
100–240 V AC; 110–250 V DC
85–264 V AC
50 Hz ... 60 Hz ±10 %
6 A ... 16 A (Characteristics B, C, D, K)
II (in closed control cabinet)
The 1AC and 3AC versions are different ordering variants; a matching DC output does not make their mains inputs interchangeable. The input breaker recommendation is for supply protection, not a claim that each DC branch is individually protected.
| Parameter / condition | Rigid conductor | Flexible conductor | Stripping length |
|---|---|---|---|
| Input | 0.2 mm²–4 mm² | 0.2 mm²–2.5 mm² | 10 mm |
| Output | 0.2 mm²–4 mm² | 0.2 mm²–2.5 mm² | 10 mm |
| Signal | 0.2 mm²–1.5 mm² | 0.2 mm²–1.5 mm² | 8 mm |
Cross-sections and stripping lengths are terminal-group specific. Input, output and signaling terminals do not necessarily accept the same conductors.
Power path and signaling terminals
Original manufacturer block diagram for TRIO-PS-2G/1AC/24DC/3/C2LPS. Terminal markings are preserved.
Green DC OK LED
Floating DC OK contact, terminals 13 and 14
30 V AC/DC, 100 mA
The floating contact reports the supply output state to the control circuit. It is separate from the 24 V / 3 A load output and is limited to 100 mA switching current. Parallel connection capability does not make the unit a UPS or a redundancy module.
2903147
TRIO-PS-2G/1AC/24DC/3/C2LPS
TRIO POWER second generation, TRIO-PS-2G
30 × 130 × 115 mm
328.21 g
Horizontal on NS 35 DIN rail, EN 60715
IP20
Natural convection
−25 to +70 °C
Above +60 °C, derate by 2.5% per kelvin.
−40 to +85 °C
≤ 5000 m (> 2000 m, observe derating)
Allow 50 mm vertical clearance. Horizontal spacing is 0 mm up to 40 °C ambient and 10 mm up to 70 °C. These are installation conditions, not additions to the 30 mm housing width. Keep the unit in a closed control cabinet and leave the ventilation slots unobstructed.
Continuous ambient operation is rated from −25 to +70 °C, with output derating above +60 °C. The manufacturer's typical −40 °C startup test is not a −40 °C continuous operating rating. Altitude derating applies above 2,000 m as described in the data sheet.
Exact item-number data and manufacturer technical resources.
Order the exact product and condition your project requires, with assistance from quotation through delivery.
Your quotation references the complete manufacturer part number to keep the requested product clear.
Tell us whether you need new original, new surplus, used, refurbished or repaired equipment.
Shipping options are prepared around your destination, quantity and requested delivery date.
Access available manufacturer product data, manuals and certificates associated with the order number.