Phoenix Contact STEP POWER Third Generation
Phoenix Contact STEP3 power supplies for compact control and building automation. The initial 24 V Push-in selection covers 0.63, 1.3, 2.5, 4 and 5 A, with DIN-rail or direct mounting. Fixed-output and adjustable-output models have distinct low-line and load limits.
View productsSelect 24 V capacity and installation width
The standard 24 V selection spans 15–120 W and 18–72 mm widths. Larger adjustable models have low-line derating; all five require thermal derating above 50 °C. Other STEP3 output and special-purpose variants remain separate selections.
Showing 1–5 of 5

Power supplies and circuit protection
Phoenix Contact 1088478 STEP3 5 A 24 V Power Supply
1088478
New Original
$80.21

Power supplies and circuit protection
Phoenix Contact 1088491 STEP3 2.5 A 24 V Power Supply
1088491
New Original
$70.13

Power supplies and circuit protection
Phoenix Contact 1088494 STEP3 1.3 A 24 V Power Supply
1088494
New Original
$46.51

Power supplies and circuit protection
Phoenix Contact 1088495 STEP3 0.63 A 24 V Power Supply
1088495
New Original
$39.75

Power supplies and circuit protection
Phoenix Contact 1140066 STEP3 4 A 24 V Power Supply
1140066
New Original
$72.22
Standard 24 V Push-in selections
Choose the output class before deciding the available rail width.
Fixed 24 V: 0.63 A and 1.3 A
Articles 1088495 and 1088494 provide 15 W and 30 W in 18 mm and 36 mm housings. Both use fixed 24 V output and two positive/two negative connection points.
Adjustable 24 V: 2.5 A, 4 A and 5 A
Articles 1088491, 1140066 and 1088478 provide 60, 96 and 120 W. Output adjusts 22–27 V, with constant-power restriction above 24 V. Widths are 54, 72 and 72 mm.
Match load, input source and enclosure
The same nominal 24 V output does not make every STEP3 order interchangeable.
- 01
AC and DC low-line limits
The 2.5/4 A models derate below 100 V AC or 110 V DC. The 5 A model derates below 115 V AC/DC and has a 99 V minimum DC input, rather than 88 V.
- 02
Space and terminal layout
All five are 90 mm high, 61 mm overall depth and 55 mm DIN-rail-mounted device depth. Allow 30 mm above/below. The 4/5 A housing has four positive/four negative output points; smaller units have two of each.
- 03
Keep special-purpose variants distinct
Select standard 24 V/PT orders here. LED-driver, coated/flat, USB and other output-voltage STEP3 variants have different duties and order suffixes; legacy STEP generations are outside this collection.