Exact product identification
Your quotation references the complete manufacturer part number to keep the requested product clear.

1088478
STEP3-PS/1AC/24DC/5/PT: 120 W STEP POWER supply with 24 V DC, 5 A output in a 72 mm-wide housing. Single-phase AC or high-voltage DC input, Push-in terminals and DIN-rail or direct mounting. Output adjustable from 22 to 27 V.
Warranty coverage and terms are confirmed with your order.
We coordinate the fastest available shipping option for your destination.
Available payment methods are handled through secure payment channels.
Carrier and delivery options are confirmed for your destination before dispatch.
Independent supplier: Xindustra is not an authorized distributor, reseller, or representative of Phoenix Contact. Brand names are used for identification and compatibility purposes only. Read disclaimer
Electrical capacity, operating conditions and installation for STEP3-PS/1AC/24DC/5/PT (1088478).
1088478
STEP3-PS/1AC/24DC/5/PT
24 V DC; 5 A
120 W
Manufacturer catalog rating.
22–27 V DC
Above 24 V, constant-power operation limits available output current.
100–240 V AC, −15% / +10%
Single phase; operating limits 85–264 V AC.
50–60 Hz, ±10%
110–250 V DC, −10% / +40%
Operating limits 99–350 V DC.
> 94.5%
37 A
20 / 20 ms
1088478 converts the incoming AC or high-voltage DC supply into a 5 A, 24 V DC output for control and building-automation loads. Its 72 mm width occupies 4 modular pitches in a distribution board. Choose capacity from the connected loads and the permitted current under the actual input and temperature conditions.
The front adjuster sets the output between 22 and 27 V DC. Raising the setting above 24 V does not increase the 120 W power rating; reduce load current accordingly and stay within the connected equipment’s voltage range.
−10 to +70 °C
Reduce output above 50 °C.
2% per K above 50 °C, up to 70 °C
1% per V below 115 V AC down to 85 V AC
1% per V below 115 V DC down to 99 V DC
Up to 4000 m
Above 2000 m: 10% derating per 1000 m.
Short-circuit proof; electronic secondary protection
Supported
Supported for increased power; diode required for redundancy
Supported for increased output voltage
Green LED above 0.9 × nominal output voltage
LED off below that threshold; an indicator is not a separate remote signal contact.
Full nominal output is specified up to 50 °C before thermal derating. Above that temperature, reduce the permitted load by 2% for each additional degree up to 70 °C. Altitude above 2000 m and low input voltage also affect capacity; keep the specified ventilation space around the supply.
The 5 A version starts AC-input derating below 115 V, rather than 100 V on the 2.5 A and 4 A versions. Its DC-input range also differs:99–350 V, with derating below 115 V DC down to 99 V. Include these limits when using a nominal 110 V DC source or a low AC line.
The manufacturer supports parallel connection for increased power and series connection for increased voltage. A redundant output arrangement requires diode decoupling. These are engineered output arrangements; the duplicated output terminals on one supply are simply common connection points for its single DC output.
45° Push-in, double connection points
1.1 and 1.2
1.3 and 1.4
2.1, 2.2, 2.3 and 2.4
2.5, 2.6, 2.7 and 2.8
0.2–2.5 mm²
0.25–2.5 mm²
0.25–1 mm²
10 mm
Rigid/flexible conductors and ferrules.
Manufacturer article 1088478, datasheet pages 10–11; dimensions in mm. The drawings distinguish the 61 mm overall depth from the 55 mm DIN-rail-mounted device depth.
72 / 90 mm
61 mm
55 mm
Horizontal NS35 DIN rail, EN 60715
Direct screw mounting on a level surface
30 / 30 mm
0 / 0 mm
IP20
None
−40 to +85 °C
This 4/5 A housing has four positive and four negative output connection points. All positives belong to the same output potential, as do all negatives; they do not provide four independently regulated supplies. L/N input terminals are on the upper left of the front outline.
Snap the supply onto a horizontal NS35 rail or use the direct-mounting arrangement. The housing can sit against neighboring devices horizontally, but it needs 30 mm above and below for the specified installation. Include terminal access and cable routing when laying out a shallow distribution enclosure.
Order the exact product and condition your project requires, with assistance from quotation through delivery.
Your quotation references the complete manufacturer part number to keep the requested product clear.
Tell us whether you need new original, new surplus, used, refurbished or repaired equipment.
Shipping options are prepared around your destination, quantity and requested delivery date.
Access available manufacturer product data, manuals and certificates associated with the order number.