Phoenix Contact STEP3-PS/1AC/24DC/2.5/PT power supply

Phoenix Contact 1088491 STEP3 2.5 A 24 V Power Supply

1088491

STEP3-PS/1AC/24DC/2.5/PT: 60 W STEP POWER supply with 24 V DC, 2.5 A output in a 54 mm-wide housing. Single-phase AC or high-voltage DC input, Push-in terminals and DIN-rail or direct mounting. Output adjustable from 22 to 27 V.

Availability
In Stock
Condition
New Original
SKU
1088491
Lifecycle
Active
$70.13
Request a quote
Ask a product question

12 months warranty

Warranty coverage and terms are confirmed with your order.

Fast shipping

We coordinate the fastest available shipping option for your destination.

Secure payment

Available payment methods are handled through secure payment channels.

Worldwide delivery

Carrier and delivery options are confirmed for your destination before dispatch.

Independent supplier: Xindustra is not an authorized distributor, reseller, or representative of Phoenix Contact. Brand names are used for identification and compatibility purposes only. Read disclaimer

Technical specifications

Electrical capacity, operating conditions and installation for STEP3-PS/1AC/24DC/2.5/PT (1088491).

Supply configuration

Manufacturer article

1088491

Product designation

STEP3-PS/1AC/24DC/2.5/PT

Nominal output

24 V DC; 2.5 A

Nominal output power

60 W

Manufacturer catalog rating.

Output adjustment

22–27 V DC

Above 24 V, constant-power operation limits available output current.

AC input rating

100–240 V AC, −15% / +10%

Single phase; operating limits 85–264 V AC.

Input frequency

50–60 Hz, ±10%

DC input rating

110–250 V DC, −20% / +40%

Operating limits 88–350 V DC.

Efficiency at 230 V AC

> 90%

Typical inrush current

28 A

Typical mains buffering at 120 / 230 V AC

25 / 130 ms

Compact power for distributed control

1088491 converts the incoming AC or high-voltage DC supply into a 2.5 A, 24 V DC output for control and building-automation loads. Its 54 mm width occupies 3 modular pitches in a distribution board. Choose capacity from the connected loads and the permitted current under the actual input and temperature conditions.

Voltage adjustment keeps the power limit

The front adjuster sets the output between 22 and 27 V DC. Raising the setting above 24 V does not increase the 60 W power rating; reduce load current accordingly and stay within the connected equipment’s voltage range.

Operating limits

Operating ambient

−10 to +70 °C

Reduce output above 50 °C.

Thermal derating

2% per K above 50 °C, up to 70 °C

Low AC input

1% per V below 100 V AC down to 85 V AC

Low DC input

1% per V below 110 V DC down to 88 V DC

Altitude

Up to 4000 m

Above 2000 m: 10% derating per 1000 m.

Output protection

Short-circuit proof; electronic secondary protection

No-load operation

Supported

Parallel connection

Supported for increased power; diode required for redundancy

Series connection

Supported for increased output voltage

DC OK indication

Green LED above 0.9 × nominal output voltage

LED off below that threshold; an indicator is not a separate remote signal contact.

Size for the installed ambient temperature

Full nominal output is specified up to 50 °C before thermal derating. Above that temperature, reduce the permitted load by 2% for each additional degree up to 70 °C. Altitude above 2000 m and low input voltage also affect capacity; keep the specified ventilation space around the supply.

Low-line conditions reduce available load

Apply 1% per volt below 100 V AC down to 85 V AC, or below 110 V DC down to 88 V DC. The wide input operating range therefore does not mean full output current at every accepted input voltage.

Separate power increase from redundant operation

The manufacturer supports parallel connection for increased power and series connection for increased voltage. A redundant output arrangement requires diode decoupling. These are engineered output arrangements; the duplicated output terminals on one supply are simply common connection points for its single DC output.

Terminal assignment and conductor preparation

Connection technology

45° Push-in, double connection points

Input L

1.1 and 1.2

Input N

1.3 and 1.4

Positive DC output

2.1 and 2.2

Negative DC output

2.3 and 2.4

Rigid / flexible conductor

0.2–2.5 mm²

Ferrule without plastic sleeve

0.25–2.5 mm²

Ferrule with plastic sleeve

0.25–1 mm²

Stripping length

10 mm

Rigid/flexible conductors and ferrules.

Front terminal layout and side profile

Manufacturer article 1088491, datasheet pages 10–11; dimensions in mm. The drawings distinguish the 61 mm overall depth from the 55 mm DIN-rail-mounted device depth.

STEP3-PS/1AC/24DC/2.5/PT original terminal and dimension drawings

STEP3-PS/1AC/24DC/2.5/PT original terminal and dimension drawings

Manufacturer article 1088491, datasheet pages 10–11; dimensions in mm. The drawings distinguish the 61 mm overall depth from the 55 mm DIN-rail-mounted device depth.

Installation envelope

Width / height

54 / 90 mm

Overall depth

61 mm

Device depth, DIN-rail mounted

55 mm

Rail

Horizontal NS35 DIN rail, EN 60715

Alternative mounting

Direct screw mounting on a level surface

Required clearance, top / bottom

30 / 30 mm

Required clearance, left / right

0 / 0 mm

Protection

IP20

Protective coating

None

Storage / transport

−40 to +85 °C

Use the terminal map for this article

This housing has two L and two N input points plus two positive and two negative output points. Duplicated points share their respective potentials. Follow the article’s front outline for input/output placement; the larger 4/5 A housings use a different terminal arrangement.

Allow space around the mounted unit

Snap the supply onto a horizontal NS35 rail or use the direct-mounting arrangement. The housing can sit against neighboring devices horizontally, but it needs 30 mm above and below for the specified installation. Include terminal access and cable routing when laying out a shallow distribution enclosure.

Sourcing and order support

Order the exact product and condition your project requires, with assistance from quotation through delivery.

Exact product identification

Your quotation references the complete manufacturer part number to keep the requested product clear.

Condition options

Tell us whether you need new original, new surplus, used, refurbished or repaired equipment.

International delivery

Shipping options are prepared around your destination, quantity and requested delivery date.

Documentation support

Access available manufacturer product data, manuals and certificates associated with the order number.