Skip to content

Beckhoff EL4xxx Analog Output EtherCAT Terminals

Beckhoff EL4xxx EtherCAT analog output terminals. The first selection covers ten standard 12-bit models for 0–10 V, 0–20 mA and 4–20 mA commands, with one to eight channels depending on the signal range.

View products

Plan the output circuit and terminal row

Channel density changes conversion time and, for current outputs, thermal operating limits.

  1. 01

    Current channels above +55 °C

    Two-channel current terminals are limited to one simultaneously controlled channel above +55 °C; four-channel models are limited to two, up to the +60 °C operating maximum.

  2. 02

    E-bus plus field supply

    The electronics use E-bus power; output stages use 24 V DC power contacts. Channels share ground. E-bus/field isolation does not provide independent channel isolation.

  3. 03

    Conversion time by channel count

    Approximately 100/150/250/400 µs for one/two/four/eight channels. Distributed Clocks is supported; application response also depends on the master and receiving equipment.