Exact product identification
Your quotation references the complete manufacturer part number to keep the requested product clear.

EL4002
2-channel EtherCAT analog output terminal for 0–10 V control signals. 12-bit resolution, approximately 150 µs conversion time and 24 V DC output-stage supply via power contacts.
Warranty coverage and terms are confirmed with your order.
We coordinate the fastest available shipping option for your destination.
Available payment methods are handled through secure payment channels.
Carrier and delivery options are confirmed for your destination before dispatch.
Independent supplier: Xindustra is not an authorized distributor, reseller, or representative of Beckhoff. Brand names are used for identification and compatibility purposes only. Read disclaimer
Output signal, load and terminal-station data for EL4002.
EL4002 generates 2 0–10 V voltage signals from EtherCAT output data. Use it to command equipment with a matching analog input, such as a drive reference or process actuator. It generates a control signal; it is not an analog measurement input or a power output for directly driving a motor.
2
0–10 V
12 bit
Single-ended; shared ground
Approximately 150 µs
Multiplex
>5 kΩ
<±0.1% of full-scale value
<±0.2% of full-scale value
Supported
2 × 16-bit analog output word
Connect a receiving input with resistance above 5 kΩ. This is a 0–10 V unipolar signal; an application requiring negative command voltage needs a bipolar output terminal. The 12-bit conversion specification and full-scale error are separate characteristics.
Original Beckhoff EL40xx manual v4.6, p.19. The diagram shows exact signal terminals, ground and power contacts.
The E-bus supplies the terminal electronics; 24 V DC through the power contacts supplies the output stages. An operating EtherCAT connection alone does not provide the field output-stage supply. Route signal and return to the marked output/GND terminals.
Output channels share a common reference. The documented 500 V isolation is between E-bus and field voltage; it does not isolate every output channel from the others. Current-output channel ground is common with the 0 V DC supply.
Follow the exact model drawing when changing channel density. Terminal points identified as without function are not spare connection points and must not be connected to conductors. Shield connections and signal returns have different roles.
E-bus
24 V DC via power contacts
140 mA
40 mA
500 V, E-bus/field voltage
Approximately 15 × 100 × 70 mm
12 mm
Approximately 60 g
−25 to +60 °C; current-output channel limits apply above +55 °C
−40 to +85 °C
95%, non-condensing
IP20
35 mm DIN rail to EN 60715
Install in an EtherCAT terminal row with a suitable coupler or controller, allocate E-bus and field power, and configure the exact output terminal in TwinCAT or the EtherCAT master. Its 16-bit output word is the process-data container for a 12-bit output, not a 16-bit analog-resolution claim.
The approximately 150 µs conversion rating is terminal-specific. PLC task timing, EtherCAT cycle and the receiving device also affect command response. Distributed Clocks support provides a synchronization facility; it does not replace output conversion or application cycle planning.
Order the exact product and condition your project requires, with assistance from quotation through delivery.
Your quotation references the complete manufacturer part number to keep the requested product clear.
Tell us whether you need new original, new surplus, used, refurbished or repaired equipment.
Shipping options are prepared around your destination, quantity and requested delivery date.
Access available manufacturer product data, manuals and certificates associated with the order number.