ABB PSR Compact Softstarters

ABB PSR compact softstarters provide two-phase-controlled voltage ramps and built-in bypass for three-phase motors. The first batch covers ten PSR3–PSR60 orders with 208–600 V AC main power and 100–240 V AC control power. Motor and short-circuit protection are external.

View products

Build the complete motor-starting circuit

A base softstarter is one part of the motor-control assembly.

  1. 01

    Use the correct voltage and rating system

    Main power is 208–600 V AC. These -70 orders use 100–240 V AC control power. IEC current/kW and UL/CSA FLA/hp have distinct values, so size using the matching table.

  2. 02

    Account for start frequency and ambient

    Starting capacity is 4 × Ie for 6 seconds. Above 40 °C reduce current 0.8% per °C up to 60 °C; altitude above 1000 m also requires derating. Frequent or heavy starts affect starter selection.

  3. 03

    Provide coordinated protection

    Use an external manual motor starter or an appropriate fuse/overload arrangement. The internal bypass is not motor protection or a line-isolating device. Exact protective-device combinations depend on supply and fault duty.