ABB PSR6-600-70 Compact Softstarter, 6.8 A IEC

PSR6-600-70

PSR6-600-70 (1SFA896104R7000) is a compact, two-phase-controlled softstarter for three-phase motors: 6.8 A IEC, 3 kW at 400 V. It accepts 208–600 V AC main power and 100–240 V AC control power, with built-in bypass and adjustable voltage ramps. Motor protection is external.

Availability
In Stock
Condition
New Original
SKU
PSR6-600-70
Lifecycle
Active
$372.66
Request a quote
Ask a product question

12 months warranty

Warranty coverage and terms are confirmed with your order.

Fast shipping

We coordinate the fastest available shipping option for your destination.

Secure payment

Available payment methods are handled through secure payment channels.

Worldwide delivery

Carrier and delivery options are confirmed for your destination before dispatch.

Independent supplier: Xindustra is not an authorized distributor, reseller, or representative of ABB. Brand names are used for identification and compatibility purposes only. Read disclaimer

Technical specifications

Motor ratings, starting duty and installation for PSR6-600-70.

Electrical configuration

Catalog type

PSR6-600-70

ABB order code

1SFA896104R7000

IEC operational current

6.8 A

UL/CSA full-load current

6.1 A

Use the matching UL/CSA motor-power table.

Main operational voltage

208–600 V AC, +10% / −15%

Main frequency

50/60 Hz, ±5%

Control supply, Us

100–240 V AC, 50/60 Hz

This is the -70 AC-control version.

Motor connection

In-line, three phase

Controlled phases

Two

Bypass

Built in

IEC normal-start motor ratings

IEC normal-start motor ratings
Parameter / condition 230 V AC400 V AC500 V AC
Rated motor power1.5 kW3 kW4 kW

UL/CSA normal-start motor ratings

UL/CSA normal-start motor ratings
Parameter / condition 200/208 V AC220/240 V AC440/480 V AC550/600 V AC
Rated motor power1 hp1.5 hp3 hp5 hp

Choose using motor current and starting duty

PSR6-600-70 is rated 6.8 A under IEC conditions and 6.1 A in the UL/CSA ordering table. Its 3 kW figure applies at 400 V, rather than across the entire voltage range. Select the motor from the table for its supply voltage, then account for starting duty, ambient temperature and altitude.

A voltage ramp for starting and stopping

PSR progressively changes motor voltage during starting and stopping, then closes its internal bypass at full voltage. It does not provide variable-frequency speed control during normal running. The two controlled phases are part of a three-phase motor circuit; this is not a single-phase motor starter.

Ramp and control functions

Start ramp

1–20 s

Stop ramp

0–20 s

Initial voltage

40–70%

Adjustment

Three front potentiometers

RUN relay output

Available

Top-of-ramp relay output

Not fitted

A TOR LED indication is distinct from a separate relay output.

Control power consumption

12 VA

Control-supply fuse

6 A, slow acting

100–240 V control-supply version.

Maximum power loss at rated Ie

3.5 W

Current rev K catalog value, including the model-specific bypass behavior.

Duty and environment

Starting capacity

4 × Ie for 6 s

Standard starts per hour

10

50% on / 50% off time.

Starts with auxiliary fan

20

Fan is optional; 50% on / 50% off time.

Operating ambient

−25 to +60 °C

Temperature derating

Above 40 °C: reduce current 0.8% per °C up to 60 °C

Altitude

Up to 4000 m

Above 1000 m, apply the manufacturer altitude factor.

Altitude current factor

100 − (altitude in m − 1000) / 150, in percent

For altitudes above 1000 m up to 4000 m.

Storage ambient

−40 to +70 °C

Starting frequency depends on the load

The 4 × Ie / 6 s starting duty and 50% on/off cycle underpin the standard duty figures. ABB also publishes a motor-current-versus-starts selection table at 40 °C; a smaller motor can allow more starts on a larger starter. A 100-start-per-hour family capability is not a blanket rating for every motor at this starter’s full current.

Provide motor and circuit protection externally

Built-in bypass reduces running losses but does not provide motor-overload or short-circuit protection. Use a coordinated manual motor starter, or the specified fuse/overload arrangement. A line contactor can provide upstream switching and open when an overload trips; it is separate from the internal bypass.

Wire status outputs for their actual function

This size provides a RUN relay output. Its Run/TOR front LED also indicates ramping and full voltage, but it does not add the separate TOR relay terminal found on PSR25 and larger models.

Manufacturer control and protection circuits

ABB catalog rev K p.25, PSR3–PSR16 circuit group. Examples show MMS, MMS with an auxiliary contact, and fuses with contactor/overload protection. These show circuit functions; protective-device ratings and fault duty come from the coordination selection.

Manufacturer control and protection circuits

Manufacturer control and protection circuits

ABB catalog rev K p.25, PSR3–PSR16 circuit group. Examples show MMS, MMS with an auxiliary contact, and fuses with contactor/overload protection. These show circuit functions; protective-device ratings and fault duty come from the coordination selection.

Separate the power circuit from the control supply

Connect the incoming three phases to 1L1, 3L2 and 5L3, with motor leads at 2T1, 4T2 and 6T3. A1/A2 receive the control supply and ST receives the start/stop command as shown in the applicable circuit. The main 208–600 V rating and the 100–240 V control-supply rating serve different terminals.

Mounting envelope

Width / overall height

45 / 140 mm

Depth marked in current outline

114 mm

Use the complete dimension drawing for fixing centers and projections.

Mounting

Screw or DIN-rail mounting

Main-circuit degree of protection

IP20

Enclosure provision

Install in a suitable equipment enclosure

Terminal protection is not a complete enclosed starter assembly.

Original frame dimensions

ABB catalog rev K p.24, PSR3–PSR16 outline. Dimensions include mm and inch annotations, fixing centers and projections.

Original frame dimensions

Original frame dimensions

ABB catalog rev K p.24, PSR3–PSR16 outline. Dimensions include mm and inch annotations, fixing centers and projections.

Optional connection and communication hardware

Mechanical connection kits join compatible ABB manual motor starters to the PSR. Fieldbus communication requires an external adapter and FieldbusPlug. These accessories are separate from the base softstarter and are selected for the actual frame and control system.

Sourcing and order support

Order the exact product and condition your project requires, with assistance from quotation through delivery.

Exact product identification

Your quotation references the complete manufacturer part number to keep the requested product clear.

Condition options

Tell us whether you need new original, new surplus, used, refurbished or repaired equipment.

International delivery

Shipping options are prepared around your destination, quantity and requested delivery date.

Documentation support

Access available manufacturer product data, manuals and certificates associated with the order number.