ABB MS116 Manual Motor Starters

ABB MS116 thermal-magnetic manual motor starters combine local ON/OFF switching with class 10A overload protection and magnetic short-circuit tripping. The first selection covers ten standard screw-terminal models with adjustment ranges from 0.10 to 10 A.

View products

Build the complete motor starter circuit

A manual motor starter, contactor and branch-circuit arrangement perform different jobs.

  1. 01

    Use the motor rated current

    The front dial sets thermal overload protection directly in amperes. The motor rated current must fall inside the selected model’s range; class10A does not mean a fixed10A device.

  2. 02

    Match voltage and fault rating

    Use the exact voltage row for Ics, Icu and conditional back-up fuses. A complete UL/CSA circuit’s rating is separate from IEC device breaking capacity and requires the stated branch-circuit protection.

  3. 03

    Add remote switching with a contactor

    MS116 supplies local manual switching. A separately controlled AF contactor adds remote switching; its coil voltage and tested coordination size must suit the circuit. Auxiliary contacts and connecting links are separate items.

  4. 04

    Respect connection and ambient conditions

    Selected models share a45mm-wide housing. Single-phase wiring uses all three protection poles. Open temperature-compensated, open operating and enclosed ambient limits are distinct.