ABB MS116 three-pole manual motor starter with rotary handle and screw terminals

ABB MS116-0.63 0.40–0.63 A Manual Motor Starter

MS116-0.63

Three-pole thermal-magnetic manual motor starter with 0.40–0.63 A adjustable overload protection, trip class 10A and 7.88 A instantaneous short-circuit setting. Screw terminals, rotary ON/OFF handle and 45 mm width. ABB order code 1SAM250000R1004.

Availability
In Stock
Condition
New Original
SKU
MS116-0.63
Lifecycle
Active
$45.50
Request a quote
Ask a product question

12 months warranty

Warranty coverage and terms are confirmed with your order.

Fast shipping

We coordinate the fastest available shipping option for your destination.

Secure payment

Available payment methods are handled through secure payment channels.

Worldwide delivery

Carrier and delivery options are confirmed for your destination before dispatch.

Independent supplier: Xindustra is not an authorized distributor, reseller, or representative of ABB. Brand names are used for identification and compatibility purposes only. Read disclaimer

Technical specifications

Overload adjustment, fault protection and installation data for MS116-0.63 / 1SAM250000R1004.

Manual switching with thermal and magnetic protection

MS116-0.63 switches a motor circuit manually and provides adjustable thermal overload protection, electromagnetic short-circuit tripping and phase-loss sensitivity. Select it when the motor’s rated current lies within 0.40–0.63 A. The rotary handle provides local ON/OFF operation; remote switching requires a separate contactor.

Ordered configuration

Product type

MS116-0.63

ABB order code

1SAM250000R1004

Thermal adjustment range

0.40–0.63 A

Rated operational current Ie

0.63 A

Instantaneous short-circuit setting Ii

7.88 A

Separate magnetic setting; not the adjustable overload range.

Trip class

10A

Main poles

3

Rated operational voltage Ue

690 V AC

Rated frequency

50/60 Hz

Rated insulation voltage Ui

690 V

Rated impulse withstand voltage Uimp

6 kV

Power loss per pole at upper thermal setting

1.7 W

Set the dial to motor rated current

The front scale is calibrated in amperes: set it to the motor’s rated current within 0.40–0.63 A. Do not multiply the nameplate current by the short-circuit trip factor or set the dial to 7.88 A. The thermal and magnetic mechanisms serve different faults. Trip class 10A describes the overload characteristic, not a fixed 10 A current rating.

Standard starter without a preassembled auxiliary contact

Order 1SAM250000R1004 for this standard screw-terminal MS116-0.63. An MS116 supplied with preassembled HKF1-11 auxiliary contacts uses the different 1SAM250005R10xx order family. Auxiliary/signaling contacts, shunt trips and undervoltage releases are optional accessories.

IEC service, ultimate and back-up ratings by voltage

IEC service, ultimate and back-up ratings by voltage
Parameter / condition Ics (kA)Icu (kA)Maximum gG/aM back-up fuse
230 V AC50100—
400 V AC50100—
440 V AC50100—
500 V AC30100—
690 V AC30100—

ABB datasheet Rev B, p.7. A dash means no back-up fuse is required up to the listed Icu. Fuse entries are maximum gG/aM ratings for short-circuit current up to 50 kA where Icc exceeds Ics; they are conditional ratings, not an unconditional 50 kA device rating.

Keep IEC breaking capacity separate from UL/CSA circuit ratings

At 400 V AC, this model has Ics = 50 kA and Icu = 100 kA in ABB’s IEC table. Ics is rated service short-circuit breaking capacity; Icu is rated ultimate capacity. These values are distinct from a complete UL/CSA starter combination’s short-circuit rating and from the 7.88 A magnetic trip setting.

UL/CSA 480 V contactor combination

ABB-listed contactor size range

AF09–AF16

480 V combination short-circuit rating

30 kA

Circuit arrangement

Motor disconnect / group installation; coordination Type 2

Branch-circuit protection

Separate listed fuse or UL489 / CSA C22.2 No.5 circuit breaker, sized to NEC/CEC

Padlocking for motor-disconnect use

SA1 or SA3 adaptor

Coordinate the whole starter circuit

For the 480 V UL/CSA combination above, ABB lists AF09–AF16 contactors with MS116-0.63. Provide the listed branch-circuit protection and select the contactor coil supply independently of the motor voltage. Mechanical connecting links and additional auxiliary contacts are separate components. ABB’s coordination tool provides further tested combinations for other circuit arrangements.

Single-phase, three-phase and terminal wiring

Original ABB MS116 datasheet Rev B, p.2. The two single-phase arrangements route the load through all three protection poles; the three-phase diagram uses one pole per phase. Terminal numbers are shown in the lower diagram.

Single-phase, three-phase and terminal wiring

Single-phase, three-phase and terminal wiring

Original ABB MS116 datasheet Rev B, p.2. The two single-phase arrangements route the load through all three protection poles; the three-phase diagram uses one pole per phase. Terminal numbers are shown in the lower diagram.

Screw-terminal installation, MS116 ≤16 A

Supply terminals

1L1, 3L2, 5L3

Load terminals

2T1, 4T2, 6T3

Rigid conductors

1 or 2 × 1–4 mm²

Flexible conductors, with or without ferrule

1 or 2 × 0.75–2.5 mm²

Stripping length

9 mm

IEC tightening torque

0.8–1.2 N·m

Screwdriver

Pozidriv 2

Use all three poles in a single-phase circuit

Follow one of the manufacturer’s illustrated single-phase loop arrangements so all three thermal elements carry the load current. Simply leaving a pole unused is not the shown single-phase arrangement and does not provide the intended phase-loss-sensitive operation.

Use the local handle and test function

The trip-free mechanism allows protective opening even if the handle is held in the ON position. The front test function supports checking the trip mechanism. A remote ON/OFF command is handled by a separately controlled contactor, not by the MS116 rotary handle.

MS116 ≤16 A housing dimensions

Original ABB MS116 datasheet Rev B, p.4, dimensions in mm and inches. Applies to all ten selected models. FS116 screw fixing and the larger ≥20 A housing are separate drawings and are not shown here.

MS116 ≤16 A housing dimensions

MS116 ≤16 A housing dimensions

Original ABB MS116 datasheet Rev B, p.4, dimensions in mm and inches. Applies to all ten selected models. FS116 screw fixing and the larger ≥20 A housing are separate drawings and are not shown here.

Mounting and environment

Housing width / height

45 / 90 mm

DIN-rail mounting

TH35-7.5 or TH35-15 to IEC 60715

Screw fixing

FS116 accessory kit

Open ambient, temperature-compensated

−25 to +55 °C

Open operating ambient

−25 to +70 °C

Distinct from the compensated range.

Ambient in IB132 enclosure

0 to +40 °C

Storage ambient

−50 to +80 °C

Maximum operating altitude

2,000 m

Protection: housing / main terminals

IP20 / IP10

Mechanical durability

100,000 operations

Electrical durability, selected ≤16 A models

100,000 operations

Spacing to another unit of same type

Horizontal 0 mm; vertical 150 mm

ABB lists group mounting separately as on request.

Spacing to conductive board

Horizontal 0 mm up to 400 V; >1.5 mm up to 690 V; vertical 75 mm

Separate ambient compensation from the operating limit

The −25 to +55 °C range is the documented temperature-compensated range. The open-device operating maximum is +70 °C, while an IB132 enclosure has a 0 to +40 °C rating. Plan the enclosure and current setting using the applicable condition rather than treating all three temperatures as one rating.

Match starting frequency to the duty

ABB specifies up to 15 operations per hour without early tripping, or 60 per hour at 40% duty ratio, when motor breaking current is 6 × In and starting time does not exceed 1 second. The separate 170 cycles/h maximum operating-frequency figure does not remove these motor-starting conditions.

Sourcing and order support

Order the exact product and condition your project requires, with assistance from quotation through delivery.

Exact product identification

Your quotation references the complete manufacturer part number to keep the requested product clear.

Condition options

Tell us whether you need new original, new surplus, used, refurbished or repaired equipment.

International delivery

Shipping options are prepared around your destination, quantity and requested delivery date.

Documentation support

Access available manufacturer product data, manuals and certificates associated with the order number.