Exact product identification
Your quotation references the complete manufacturer part number to keep the requested product clear.

774311
PNOZ X3 standalone safety relay with 42 V AC or alternative 24 V DC supply. Three instantaneous N/O safety contacts, one N/C auxiliary contact and one semiconductor status output; 45 mm housing with integrated screw terminals.
Warranty coverage and terms are confirmed with your order.
We coordinate the fastest available shipping option for your destination.
Available payment methods are handled through secure payment channels.
Carrier and delivery options are confirmed for your destination before dispatch.
Independent supplier: Xindustra is not an authorized distributor, reseller, or representative of Pilz. Brand names are used for identification and compatibility purposes only. Read disclaimer
Supply selection, safety-contact functions and installation data for 774311.
774311
PNOZ X3
42 V AC, 50–60 Hz
24 V DC, alternative dedicated terminals
−15% / +10%
5 VA
2.5 W
1- or 2-channel wiring
Automatic or monitored
3 N/O: 13–14, 23–24, 33–34
1 N/C: 41–42
1: Y32, 24 V DC / 20 mA
The 42 V AC rating applies to the AC supply terminals A1/A2. Alternative 24 V DC power uses B1/B2 and a SELV/PELV supply. These are alternative supply arrangements on separate terminal groups. Do not apply the AC voltage to B1/B2; with AC operation, B2 is connected to functional earth as shown in the manufacturer wiring.
Pilz operating manual p.8. Identifies the relay paths and the common configuration used by this supply family.
Use 13–14, 23–24 and 33–34 as the safety contact paths. The normally closed 41–42 contact and Y32 semiconductor signal report state and are not safety outputs. When the input circuit opens, the N/O safety contacts open and the auxiliary contact changes state.
Pilz operating manual p.12. Select the AC or DC supply drawing and the intended single/dual-channel input arrangement.
Pilz operating manual p.13. Automatic and monitored start use different terminal links and reset arrangements.
With automatic start, closing the input circuit can activate the relay without a separate reset action. Prevent an unexpected machine restart through the external control circuit. With monitored start, use the documented reset sequence; do not copy the automatic-start bridge arrangement.
Use feedback contacts from the external contactors or relays in the documented start/feedback arrangement. Single-channel input wiring has no input-circuit redundancy; dual-channel wiring and short-circuit detection require their matching terminal configuration.
For automatic start, S33 and S34 must not be linked. For monitored start, S13 and S14 must not be linked. The factory link and input bridges must match the chosen circuit diagram rather than being carried over from another installation.
Up to 8 A at 240 V AC
Up to 8 A at 24 V DC; maximum 200 W
Up to 5 A at 230 V AC
Up to 6 A at 24 V DC, 6 cycles/min
6.5 A per contact under stated AC1/DC1 conditions
7 A per contact under stated AC1/DC1 conditions
The resistive current rating is not an unrestricted inductive-load rating. Apply the utilisation category, the number of loaded contacts, external contact fuse protection and switching-life curve together. Use suppression on inductive loads to limit contact wear.
The manual provides component data up to PL e / Category 4 and SIL CL 3. Input redundancy, feedback, switching demand and contact life remain part of the complete safety function. For the stated high-level use, the manual requires the contacts to be opened and the relay restarted at least monthly so diagnostics can check opening; lower-level SIL CL 2 / PL d use requires at least yearly operation.
45 × 87 × 121 mm
Integrated screw terminals
0.6 N·m
DIN rail; any mounting position
−20 to +55 °C
−40 to +85 °C
IP40
IP20
IP54
375 g
Pilz operating manual p.15. The outline drawing includes the overall depth and terminal profile.
Order 774311 for the 42 V AC / 24 V DC supply arrangement. Other PNOZ X3 order numbers use different AC voltages; PNOZ X3P, X3.10P and other PNOZ X types are separate devices, not interchangeable spellings.
Order the exact product and condition your project requires, with assistance from quotation through delivery.
Your quotation references the complete manufacturer part number to keep the requested product clear.
Tell us whether you need new original, new surplus, used, refurbished or repaired equipment.
Shipping options are prepared around your destination, quantity and requested delivery date.
Access available manufacturer product data, manuals and certificates associated with the order number.