Exact product identification
Your quotation references the complete manufacturer part number to keep the requested product clear.

772105
Standalone PNOZmulti 2 safety controller in a 22.5 mm housing. Six fixed inputs plus two configurable channels provide up to eight safe inputs; four safe semiconductor outputs support compact machine safety circuits. No physical expansion modules.
Warranty coverage and terms are confirmed with your order.
We coordinate the fastest available shipping option for your destination.
Available payment methods are handled through secure payment channels.
Carrier and delivery options are confirmed for your destination before dispatch.
Independent supplier: Xindustra is not an authorized distributor, reseller, or representative of Pilz. Brand names are used for identification and compatibility purposes only. Read disclaimer
Safety I/O, engineering dependencies and installation for PNOZ m C0 (772105).
772105 is the compact standalone choice for a safety circuit that fits within eight safe inputs and four safe semiconductor outputs. It brings configurable safety logic to a 22.5 mm rail width without side-mounted expansion modules. LED status indication replaces the larger display found on the B0 and B1 bases.
772105
PNOZ m C0
PNOZmulti 2
Standalone; no physical expansion modules
6
2
Counted within the maximum safe input capacity, not extra inputs.
8
4
Positive-switching, single-pole outputs; 24 V DC, 2 A per output.
133 mA per °C above 45 °C
8 A at 45 °C before derating; includes the load-current limit for the installed ambient.
2
Configurable as test-pulse or auxiliary outputs; 0.1 A.
PNOZmulti Configurator
The 6 fixed safe inputs and 2 configurable input/auxiliary channels provide up to 8 safe inputs when every configurable channel is used as an input. Assigning one of those channels as a non-safety auxiliary output reduces the available safe-input count. The 2 test-pulse channels are a separate group.
The platform supports safety functions up to PL e / Category 4 and SIL 3 in suitable architectures. The achieved level follows the input circuit, logic, output arrangement and reaction-time calculation for the complete safety function. Configure the sensor evaluation and output diagnostics for that design.
24 V DC
−20% / +25%
Common module and output supply
No galvanic separation between input/output and module supply
Plug-in screw or spring-loaded type
Terminal sets are separately selected accessories.
750004 / 751004
Inputs I4–I7
Safe semiconductor outputs O0–O3
Configurable IM0 / IM1 and inputs I2 / I3
Test-pulse/auxiliary T0M20 / T1M21; 24 V / 0 V supply
1006013-EN-05, page 8. Original front view with connection legend and device/version markings.
The C0 uses one 24 V module supply for the device and its semiconductor outputs. Include the connected output load when sizing the supply. The manual’s 8.5 A / 204 W maximum external-supply figure is a load-supply requirement; the module’s maximum heat dissipation is 4 W.
Test-pulse wiring allows the configured system to detect shorts across input circuits. When assigned as test outputs, these terminals serve the input test arrangement rather than external actuator loads. The wiring and selected input functions form one circuit in the Configurator project.
Configure and transfer the safety project using PNOZmulti Configurator and the Mini-B USB connection. A chip card is optional for project transfer. The software-generated circuit defines which inputs implement each safety function and how the outputs respond; the LED indications identify run, diagnostic and I/O fault states.
C0 does not accept physical expansion modules. Its input and output channels can support configured cascading signals, but cascading is a designed safety connection between systems rather than an extra local I/O bank. The two configurable input/auxiliary channels are included within the eight-input maximum.
101.4 × 22.5 × 120 mm
Manufacturer technical-data dimensions.
105 g
Horizontal on DIN rail
IP20
IP54 control cabinet
0 to +65 °C
Forced cabinet convection from 55 °C.
−25 to +70 °C
2000 m
Not permitted
USB project transfer; optional 8 kB / 32 kB chip card
1006013-EN-05, page 23. Original dimensional drawing; retain the indicated orientation and terminal-dependent dimensions.
Choose screw terminal set 750004 or spring-loaded set 751004 for the C0. A chip card is an optional project-transfer accessory. Leave access to the USB connection and field wiring; the 22.5 mm body does not include a physical expansion bus for extra I/O modules.
Order the exact product and condition your project requires, with assistance from quotation through delivery.
Your quotation references the complete manufacturer part number to keep the requested product clear.
Tell us whether you need new original, new surplus, used, refurbished or repaired equipment.
Shipping options are prepared around your destination, quantity and requested delivery date.
Access available manufacturer product data, manuals and certificates associated with the order number.