Skip to content
Pilz PNOZ m B1 configurable safety base unit

Pilz 772101 PNOZ m B1 Safety Controller

772101

Expandable PNOZmulti 2 safety base unit with two switched Ethernet ports, supplied Pilz USB project memory and four test-pulse outputs. Safe inputs and actuator outputs are provided by separately selected expansion modules.

Availability
In Stock
Condition
New Original
SKU
772101
Lifecycle
Active
$1,001.82
Request a quote
Ask a product question

12 months warranty

Warranty coverage and terms are confirmed with your order.

Fast shipping

We coordinate the fastest available shipping option for your destination.

Secure payment

Available payment methods are handled through secure payment channels.

Worldwide delivery

Carrier and delivery options are confirmed for your destination before dispatch.

Independent supplier: Xindustra is not an authorized distributor, reseller, or representative of Pilz. Brand names are used for identification and compatibility purposes only. Read disclaimer

Technical specifications

Safety I/O, engineering dependencies and installation for PNOZ m B1 (772101).

A modular safety CPU with integrated Ethernet

772101 provides the processing, project storage interface and diagnostics for a modular PNOZmulti 2 safety system. Its base has four test-pulse outputs but no onboard safe sensor inputs or safe actuator outputs. Choose the required expansion I/O with the safety project rather than treating this unit as a 20-input B0.

Base-unit capacity

Manufacturer article

772101

Product designation

PNOZ m B1

Platform

PNOZmulti 2

Role

Modular base using separately selected safety input/output and function modules

Fixed safe digital inputs

0

Configurable input / auxiliary-output channels

0

Safety input capacity comes from expansion modules.

Maximum onboard safe inputs

0

Safe semiconductor outputs

0

Actuator outputs require a selected expansion module.

Test-pulse outputs

4

24 V DC, 0.32 A; test outputs are not safe actuator outputs.

Engineering software

PNOZmulti Configurator

Build the I/O around the project

The B1 CPU does not provide the eight or twenty safe inputs found on other PNOZmulti 2 base units. Select input and output modules for the actual sensors and actuators, and place them in the sequence defined in the Configurator project. The four base-unit test outputs support input fault detection.

Safety capability follows the circuit design

The platform supports safety functions up to PL e / Category 4 and SIL 3 in suitable architectures. The achieved level follows the input circuit, logic, output arrangement and reaction-time calculation for the complete safety function. Configure the sensor evaluation and output diagnostics for that design.

Supply and connection data

Nominal supply

24 V DC

Voltage tolerance

−20% / +25%

Supply arrangement

System supply; I/O module supplies selected separately

Supply/output isolation

See selected I/O module for its output-supply isolation

Connection terminals

Plug-in screw or spring-loaded type

Terminal sets are separately selected accessories.

Screw / spring terminal set

750016 / 751016

X1 / X2

Ethernet, RJ45

X3

Test-pulse outputs T0–T3

Supply

24 V DC and 0 V

Use the marked supply connections on the base.

Manufacturer front view and terminal legend

1003790-EN-12, page 9. Original front view with connection legend and device/version markings.

PNOZ m B1 manufacturer terminal map and front-view legend

PNOZ m B1 manufacturer terminal map and front-view legend

1003790-EN-12, page 9. Original front view with connection legend and device/version markings.

Supply the CPU and selected I/O separately

The B1 system supply is 24 V DC. Its test-pulse outputs belong to input monitoring; safe actuator power is provided through the selected output modules and their supply arrangements. The 18.5 W external-supply requirement is distinct from the module’s 4.5 W maximum power dissipation.

Project storage and diagnostics

The Pilz USB memory supplied with the device stores and transfers the safety project. The base also has two RJ45 Ethernet connections with an integrated switch for engineering and diagnostics. Select fieldbus or specialised safety-network functions through the applicable PNOZmulti system configuration; the presence of an RJ45 socket alone does not provide every industrial protocol.

Device version in the engineering project

The firmware version is marked on the front labelling clip and is selected as the device version in PNOZmulti Configurator. Hardware and firmware determine available module programs and functions. The linked current operating manual covers HW01 / FW01.12 and later.

Mechanical and operating envelope

Height × width × depth

101.4 × 45 × 120.2 mm

Manufacturer technical-data dimensions.

Net weight

209 g

Mounting

Horizontal on DIN rail

Housing / terminals

IP20

Installation area

IP54 control cabinet

Operating ambient

0 to +60 °C

Forced cabinet convection from 55 °C.

Storage ambient

−25 to +70 °C

Maximum operating altitude

2000 m

Condensation

Not permitted

Project storage

Supplied Pilz USB memory for project storage and transfer

Mounting outline

1003790-EN-12, page 24. Original dimensional drawing; retain the indicated orientation and terminal-dependent dimensions.

PNOZ m B1 manufacturer dimensional drawing with all original dimensions

PNOZ m B1 manufacturer dimensional drawing with all original dimensions

1003790-EN-12, page 24. Original dimensional drawing; retain the indicated orientation and terminal-dependent dimensions.

Complete the configured device order

The B1 base is supplied with a terminator and Pilz USB memory; screw terminal set 750016 or spring terminal set 751016 is selected separately. Add the project’s input/output and function modules, their terminals and required connections. A bare CPU is not a complete field-I/O system.

Sourcing and order support

Order the exact product and condition your project requires, with assistance from quotation through delivery.

Exact product identification

Your quotation references the complete manufacturer part number to keep the requested product clear.

Condition options

Tell us whether you need new original, new surplus, used, refurbished or repaired equipment.

International delivery

Shipping options are prepared around your destination, quantity and requested delivery date.

Documentation support

Access available manufacturer product data, manuals and certificates associated with the order number.