Exact product identification
Your quotation references the complete manufacturer part number to keep the requested product clear.

2910105
UNO POWER second-generation 480 W-class DIN rail supply with 24 V DC output, single-phase input and screw connection. 59 mm wide; output voltage adjusts up to 28 V DC within the power limit.
Warranty coverage and terms are confirmed with your order.
We coordinate the fastest available shipping option for your destination.
Available payment methods are handled through secure payment channels.
Carrier and delivery options are confirmed for your destination before dispatch.
Independent supplier: Xindustra is not an authorized distributor, reseller, or representative of Phoenix Contact. Brand names are used for identification and compatibility purposes only. Read disclaimer
Electrical selection and installation data for 2910105 (UNO2-PS/1AC/24DC/480W).
2910105
UNO2-PS/1AC/24DC/480W
480 W
24 V DC
20 A
24–28 V DC; constant power limit above24 V
Single-phase100–240 V AC
85–264 V AC
Screw
This 480 W-class unit converts the incoming supply to a regulated 24 V DC rail for control equipment. Size it for the sum of steady loads and their startup demand. A shared 24 V label does not mean supplies with different wattage or terminal arrangements can be exchanged without redesigning the installation.
Raising the output above 24 V reduces the current available within the 480 W power class. Account for load voltage tolerance and cable drop together. Voltage adjustment is not an additional power or boost rating.
59 × 130 × 129 mm
Horizontal35 mm DIN rail to EN60715
30 mm /30 mm
IP20
−25 to+70 °C; derate above+55 °C
−40 to+85 °C
Up to95%, non-condensing
Output power derates by2.5% per kelvin above+55 °C. At+70 °C the temperature factor is62.5% of rated power before any additional applicable input or installation limits. Use the temperature inside the enclosure when budgeting the load.
Use the conductor size and tightening torque for the exact input and output terminals in the manufacturer documentation. The output conductors carry substantially more current than the mains input on higher-power models; select each circuit independently. Connect protective earth wherever the exact unit provides a PE terminal.
This product belongs to the UNO2-designated generation of UNO POWER. Legacy UNO-PS models, other output voltages and UPS or redundancy modules are separate ordering references. Match the complete article number and designation when ordering.
A floating DC OK signal forwards the output operating state to a monitoring circuit. It is a status interface rather than a load-power output; route it separately from the DC load conductors.
Include the upstream disconnect and protection, downstream distribution and the actual load wiring in the cabinet design. Independent supplies connected for redundancy require the appropriate isolation arrangement; two outputs in parallel do not by themselves form a complete redundant supply system.
Order the exact product and condition your project requires, with assistance from quotation through delivery.
Your quotation references the complete manufacturer part number to keep the requested product clear.
Tell us whether you need new original, new surplus, used, refurbished or repaired equipment.
Shipping options are prepared around your destination, quantity and requested delivery date.
Access available manufacturer product data, manuals and certificates associated with the order number.