Skip to content
Mitsubishi Electric FX5UJ 40-point PLC CPU front housing

Mitsubishi Electric FX5UJ-40MR/ES 40-Point FX5UJ PLC CPU

FX5UJ-40MR/ES

FX5UJ CPU with 24 digital inputs and 16 relay outputs. 100–240 V AC supply, 48k-step flash program memory, built-in Ethernet and USB Mini-B, plus a 24 V DC service supply. 130 mm-wide removable-terminal housing.

Availability
In Stock
Condition
New Original
SKU
FX5UJ-40MR/ES
Lifecycle
Active
$1,067.00
Request a quote
Ask a product question

12 months warranty

Warranty coverage and terms are confirmed with your order.

Fast shipping

We coordinate the fastest available shipping option for your destination.

Secure payment

Available payment methods are handled through secure payment channels.

Worldwide delivery

Carrier and delivery options are confirmed for your destination before dispatch.

Independent supplier: Xindustra is not an authorized distributor, reseller, or representative of Mitsubishi Electric. Brand names are used for identification and compatibility purposes only. Read disclaimer

Technical specifications

Controller capacity, relay field wiring and AC installation data for FX5UJ-40MR/ES.

Compact CPU with built-in discrete I/O

FX5UJ-40MR/ES combines a PLC CPU, AC power supply, 24 24 V DC inputs and 16 relay outputs. It is suited to machine sequence control with switched AC or DC field loads. Select the complete suffix to match the output circuit; the input common can be wired for sink or source sensors on every model in this batch.

Controller configuration

Manufacturer part number

FX5UJ-40MR/ES

CPU family

MELSEC iQ-F FX5UJ

Physical built-in I/O

24 inputs + 16 outputs

Output type

Relay

Program memory

48k steps / 96 kbytes, flash

Device / label memory

120 kbytes

Data memory / standard ROM

5 Mbytes

Combined local and remote I/O limit

256 points total

Built-in Ethernet

10/100 Mbps, RJ45

Built-in USB

Mini-B, Full Speed up to 12 Mbps

SD / SDHC capacity

Up to 16 Gbytes

Engineering software

MELSOFT GX Works3

Count occupied points when expanding

This CPU has 40 physical terminals for I/O and occupies 40 points in the system allocation. Local I/O and remote I/O share the combined 256-point limit; the limits do not add to 512. Allocate module occupied points and check the extension power budget before increasing the station size.

Use Ethernet and USB; add serial hardware separately

The built-in Ethernet port supports engineering connections and machine communication. USB Mini-B provides a direct engineering interface; the SD slot supports removable storage. Serial communication uses an appropriate FX5 expansion board or adapter. The CPU has no built-in analog input/output terminals; analog signals require suitable expansion hardware.

Firmware conditions for optional programming features

Ladder diagram, structured text and FBD/LD are supported. SFC requires FX5UJ firmware 1.050 or later and GX Works3 1.095Z or later. The listed 34 ns LD/MOV instruction-processing time is an instruction figure, not the scan time of a complete machine program.

40-point AC CPU terminal arrangement

Original Mitsubishi catalog L(NA)08428ENG-I, p.256. Use the upper MR/ES, MT/ES arrangement and COM commons. Input and output addresses are octal; spare/occupied addresses are not additional terminals.

40-point AC CPU terminal arrangement

40-point AC CPU terminal arrangement

Original Mitsubishi catalog L(NA)08428ENG-I, p.256. Use the upper MR/ES, MT/ES arrangement and COM commons. Input and output addresses are octal; spare/occupied addresses are not additional terminals.

Digital input characteristics

Input signal voltage

24 V DC, +20% / −15%

Input type

Sink / source

Input current, X0–X7

5.3 mA at 24 V DC

Input current, X10 onward

4.0 mA at 24 V DC

High-speed input group

X0, X1, X3, X4: up to 100 kHz

Other pulse input group

X2, X5, X6, X7: up to 10 kHz

Input isolation

Photocoupler

I/O connection

Removable terminal block, M3 screws

Set S/S for the sensor circuit

For NPN open-collector sensors, use the sink-input circuit with the input common connected to the positive side. For PNP sensors, use the source-input circuit with the input common connected to 0 V. Both are 24 V DC field circuits; the CPU’s AC supply voltage must not be applied to the input terminals.

Output load limits

Output load supply

Up to 30 V DC or 240 V AC

Maximum load per point

2 A

Common-group limit

8 A per 4-output common group

Minimum switching load

5 V DC, 2 mA, reference value

Operate / release response

Approximately 10 ms

Output isolation

Mechanical relay contacts

Use the contact ratings and common limits

The relay outputs can switch the specified external AC or DC load supply. The 2 A per-point maximum and 6/8 A common-group maximum both apply, along with temperature/simultaneous-ON limits. Relay contacts are not the CPU’s high-speed positioning outputs. Use external suppression and suitable protection for inductive loads.

Supply and service-power budget

CPU mains supply

100–240 V AC, 50/60 Hz

Supply fluctuation range

−15% / +10%

Specified maximum-configuration consumption

32 W

Maximum connected configuration and fully used service supply; not CPU-only wattage.

Service supply with CPU inputs powered internally

24 V DC, 400 mA

Service supply with CPU inputs powered externally

24 V DC, 500 mA

Inrush at 100 V AC

30 A maximum, ≤5 ms

Inrush at 200 V AC

50 A maximum, ≤5 ms

Reserve current for extension I/O

Connected I/O modules consume current from the 24 V service supply. Subtract their demand from the applicable 400 mA or external-input-supply budget before allocating current to field devices. Extension power-supply selection and module count are separate from the 256-point address limit.

Keep powered extensions on the AC system route

Up to eight I/O/intelligent-function extension modules can be connected within the documented configuration; extension power and connector-conversion modules are excluded from that count. Connector-type extensions require FX5-CNV-IF. For these AC CPUs, powered extensions use the AC FX5-32E…/E… route and an AC FX5-1PSU-5V if needed; AC and DC powered extension types cannot be mixed in one system.

FX5UJ CPU dimensions and width table

Original hardware manual SH-082452ENG-Q, printed p.119 (PDF p.121). Use the 130 mm width / 111 mm horizontal mounting-pitch row for FX5UJ-40MR/ES. Vertical mounting pitch is 82 mm; units are mm.

FX5UJ CPU dimensions and width table

FX5UJ CPU dimensions and width table

Original hardware manual SH-082452ENG-Q, printed p.119 (PDF p.121). Use the 130 mm width / 111 mm horizontal mounting-pitch row for FX5UJ-40MR/ES. Vertical mounting pitch is 82 mm; units are mm.

Panel installation

Dimensions W × H × D

130 × 90 × 83 mm

Approximate weight

0.65 kg

Mounting

35 mm DIN rail or direct M4 screw mounting

Operating ambient

0 to +55 °C, non-freezing; I/O derating applies

Storage ambient

−25 to +75 °C, non-freezing

Humidity

5–95% RH, non-condensing

Installation location

Inside a control panel

Cooling clearance

At least 50 mm around the installation

Maximum altitude

2,000 m

AC CPU simultaneous-I/O derating

Original hardware manual SH-082452ENG-Q, printed p.101 (PDF p.103), AC-powered charts only. Use the left MR/ES chart: solid 1 A load curve and dashed 2 A load curve differ.

AC CPU simultaneous-I/O derating

AC CPU simultaneous-I/O derating

Original hardware manual SH-082452ENG-Q, printed p.101 (PDF p.103), AC-powered charts only. Use the left MR/ES chart: solid 1 A load curve and dashed 2 A load curve differ.

Apply simultaneous-ON limits at the panel temperature

For 1 A output loading, the AC relay chart permits 100% simultaneous ON through 47 °C and reaches 55% at 55 °C. At 2 A loading, the curve starts derating above 35 °C, gives 80% at 40 °C and reaches 50% at 55 °C. Per-point and common-group current limits still apply.

Sourcing and order support

Order the exact product and condition your project requires, with assistance from quotation through delivery.

Exact product identification

Your quotation references the complete manufacturer part number to keep the requested product clear.

Condition options

Tell us whether you need new original, new surplus, used, refurbished or repaired equipment.

International delivery

Shipping options are prepared around your destination, quantity and requested delivery date.

Documentation support

Access available manufacturer product data, manuals and certificates associated with the order number.