Honeywell Searchpoint Optima Plus Point Infrared Gas Detectors

Honeywell Searchpoint Optima Plus point-infrared flammable gas detectors. Select hydrocarbon or ethylene optics, gas calibration, approval and mounting thread, HART or analog output, and an optional factory-fitted remote gassing cell.

View products

Searchpoint Optima Plus detector configurations

This first batch covers complete weather-protected diffusion detectors: ATEX/IECEx M25 hydrocarbon and ethylene versions, plus UL/Inmetro ¾-inch NPT hydrocarbon versions. Compare HART capability and factory RGC separately from the target-gas calibration.

Match the installed configuration

The same cylindrical enclosure can carry different approvals, output hardware and gas-check provisions.

  1. 01

    Approval and mounting thread

    The selected ATEX/IECEx units have M25 spigots; the selected UL/Inmetro hydrocarbon units have ¾-inch NPT spigots.

    • Do not substitute one mounting thread because the body looks identical.
    • Use a corresponding certified enclosure and connection arrangement.
  2. 02

    H suffix or N suffix

    H versions add HART digital communication over 4–20 mA. N versions retain the non-HART analog output.

    • The analog circuit supports automatic source or sink operation.
    • HART requires a suitable host and at least 230 Ω loop resistance.
  3. 03

    Factory remote gassing cell

    RGC-equipped versions support a gas response check when the detector is hard to reach. They are not a complete sampling system.

    • RGC flow and local gassing-cover flow are different.
    • The test-gas response is not a universal span-calibration reading.
  4. 04

    Horizontal mounting and protected response

    Keep the optical cell horizontal, the weather openings down and the vent slot unobstructed.

    • Installed weather protection changes the response relative to bare optics.
    • Separate the detector body envelope from junction-box, shade and tubing clearance.