Honeywell Searchpoint Optima Plus stainless-steel point infrared detector with black weather protection

Honeywell 2108N4011H Optima Plus Ethylene IR Detector HART with RGC

2108N4011H

Searchpoint Optima Plus ethylene-version diffusion detector, ATEX / IECEx, M25, HART over 4–20 mA. Factory RGC fitted. 316SS body with dust barrier, weather housing and shade. Target gas and scale are selected by compatible calibration.

Availability
In Stock
Available quantity
12 units
Condition
New Original
SKU
2108N4011H
Lifecycle
Active
$3,145.00
Request a quote
Ask a product question

12 months warranty

Warranty coverage and terms are confirmed with your order.

Fast shipping

We coordinate the fastest available shipping option for your destination.

Secure payment

Available payment methods are handled through secure payment channels.

Worldwide delivery

Carrier and delivery options are confirmed for your destination before dispatch.

Independent supplier: Xindustra is not an authorized distributor, reseller, or representative of Honeywell. Brand names are used for identification and compatibility purposes only. Read disclaimer

Technical specifications

Detector configuration, gas-calibration selection, electrical integration and installation for 2108N4011H.

Ethylene point-infrared detector

2108N4011H is a complete Searchpoint Optima Plus diffusion detector with ATEX / IECEx certification, a M25 mounting spigot and HART over 4–20 mA output. A remote gassing cell is factory fitted for functional response testing at an inaccessible detector. The stainless-steel detector measures gas at its optical cell; it is not an open-path transmitter/receiver pair.

Exact ordering configuration

Manufacturer part number

2108N4011H

Detector version

Ethylene calibration family

Gas entry

Diffusion, with weather protection and dust barrier

Approval variant

ATEX / IECEx

Mounting thread

M25

Electrical interface

HART over 4–20 mA

Remote gassing cell

Factory fitted

Body material

Electropolished 316 stainless steel

Supplied protection

Polyester mesh dust barrier, nylon weather housing and deluge/sunshade

Integral numerical display

Not fitted

Integral alarm relays

Not fitted

Select the gas calibration with the detector

The ethylene version identifies an optical/calibration family, not a unique target-gas setting. Choose a compatible ethylene-version calibration for the intended gas; this is not an interchangeable methane-calibrated detector. Honeywell specifies a compatible calibration with every complete detector order. The configured target gas, full scale and LEL convention on the unit label must match the receiving controller.

Keep concentration scale separate from package hardware

The 4–20 mA measurement represents 0–100% of the selected full scale. %LEL calibrations are gas-specific; %LEL is not the same as percent gas by volume. The special high-concentration methane/propane sampling packages are different order codes, not a feature added to these diffusion versions by fitting an RGC.

Choose this configuration

Choose the ethylene-version optics when the selected gas calibration requires that version. HART provides digital setup and diagnostics on the analog loop. The M25 ATEX/IECEx configuration mates to the corresponding certified junction-box entry. The factory RGC is useful when routine access for a gas response check is difficult.

Electrical integration

Nominal supply

24 V DC

Permitted supply at detector

18–32 V DC

Maximum power budget

5 W

Analog circuit

Three-wire, automatic current source or sink

Maximum signal-loop resistance

600 Ω

In current-source mode at 18–20 V DC, maximum 500 Ω.

Minimum HART loop resistance

230 Ω

Applies to digital communication on this HART version.

Red lead

Positive DC supply

Black lead

0 V DC

White lead

4–20 mA measurement signal

Orange / blue leads

RS485 A / B for proprietary SHC1 communication

Not a general-purpose Modbus RTU interface.

Green/yellow lead

Protective earth

Original current-source circuit

Honeywell MAN0905 Issue 7, p.28. Source-mode load is between the controller signal and common. Preserve the illustrated shield/earth arrangement and the stated load limit.

Honeywell Optima Plus current-source circuit showing red supply, white signal, black common and controller load

Honeywell Optima Plus current-source circuit showing red supply, white signal, black common and controller load

Honeywell MAN0905 Issue 7, p.28. Source-mode load is between the controller signal and common. Preserve the illustrated shield/earth arrangement and the stated load limit.

Original current-sink circuit

Honeywell MAN0905 Issue 7, p.29. Source and sink are alternative controller circuits; the detector selects the operating mode automatically.

Honeywell Optima Plus current-sink circuit showing controller load between positive supply and signal

Honeywell Optima Plus current-sink circuit showing controller load between positive supply and signal

Honeywell MAN0905 Issue 7, p.29. Source and sink are alternative controller circuits; the detector selects the operating mode automatically.

Budget voltage drop separately from signal load

Size the supply cable so the detector still receives at least 18 V DC at its maximum power demand. Supply cable loop resistance and the receiving controller’s analog load are separate calculations; a 600 Ω signal-load allowance is not permission to put 600 Ω in the power cable.

HART is fitted on this H-suffix detector

Use a HART-compatible host and the Optima Plus device description for digital setup, diagnostics and calibration functions over the 4–20 mA loop. Maintain at least 230 Ω loop resistance without exceeding the applicable upper limit. Very low fault current can interrupt HART communication; the manual describes an adjustable fault-current mode for service access.

Default analog signal states

Default analog signal states
Parameter / conditionDefault currentController interpretation
FaultLess than 1 mADetector fault, not a valid zero-gas reading
Inhibit2 mAMaintenance or inhibited measurement
Warning3 mAService warning; gas monitoring continues and a detected gas reading takes priority
Measurement4–20 mA0–100% of the configured gas full scale
Over-range21 mAGas above the configured scale

Factory defaults; several status currents are configurable. Program the receiving controller for the installed settings rather than treating every below-4 mA signal as the same state.

Use a gas controller for indication and alarm actions

The detector head has no integral numeric display or relay contacts. A suitable receiving controller supplies the concentration indication and site alarm actions. An XNX transmitter, OELD display, junction box or other interface is separate equipment, not included merely because it is shown elsewhere in the Optima Plus ecosystem.

Use the response data for the chosen gas

Ethylene-version calibrations have their own response characteristics. A methane response figure from the family specification is not the response time for every ethylene-version gas calibration.

Act on optical contamination warnings

The optical self-check and warning channel support maintenance before contamination becomes a full fault. A warning is not a substitute for a gas response check, and it must be distinguished from inhibit and fault at the receiving controller.

Detector body and operating conditions

Detector dimensions

165 mm long × 73 mm diameter

Detector body dimensions, not the complete junction-box, shade and tubing installation envelope.

Approximate detector weight

1.6 kg

Mounting orientation

Horizontal

Mounting spigot

M25

Ingress protection

IP66 / IP67

Ambient operating temperature

−40 to +65 °C

Maximum temperature change rate

Less than 3 °C per minute

Relative humidity

0–99% RH, non-condensing

Pressure

80–120 kPa

Uncompensated pressure range.

Original M25 mounting arrangement

Honeywell MAN0905 Issue 7, p.19. The M25 version uses a nylon sealing washer and lock nut; compress the washer to maintain ingress protection.

Honeywell Optima Plus horizontal mounting illustration with junction box, sealing washer and lock nut

Honeywell Optima Plus horizontal mounting illustration with junction box, sealing washer and lock nut

Honeywell MAN0905 Issue 7, p.19. The M25 version uses a nylon sealing washer and lock nut; compress the washer to maintain ingress protection.

Keep the optical cell horizontal and the weather openings down

Mount the detector horizontally in a suitable certified enclosure or mounting arrangement with its M25 spigot. Fit the standard weather protection with its semicircular openings facing downward. Secure the M25 spigot with the specified sealing washer and lock nut. Keep access for cleaning and gas checks.

Fit the supplied shade without blocking gas access

The deluge/sunshade fits over the standard weather protection with its longer overhang toward the front. Keep its clamp clear of the gas vent slot. Allow space for the junction box, outgoing cables and any test tubing in addition to the bare detector dimensions.

Avoid rapid temperature swings and condensate

Keep steam, hot condensate and direct contamination away from the optical path. The detector is rated for a wide ambient range, but a temperature change faster than 3 °C/min is a separate limit and can cause faults or damage. Place the sensing point according to gas-release and ventilation behavior, not simply where the cable is easiest to route.

Stabilize before a gas check

The detector is factory calibrated. Allow one hour powered stabilization before gas testing or calibration work. Establish the site test/inhibit procedure, confirm the detector/controller scale agreement and verify the intended warning, fault and alarm paths before returning the channel to service.

Original remote gassing cell

Honeywell MAN0905 Issue 7, p.24. This factory-fitted RGC is for a functional response check, not a continuous process sampling housing.

Honeywell Optima Plus remote gassing cell showing its high-concentration test-gas nozzles

Honeywell Optima Plus remote gassing cell showing its high-concentration test-gas nozzles

Honeywell MAN0905 Issue 7, p.24. This factory-fitted RGC is for a functional response check, not a continuous process sampling housing.

Remote gassing cell response check

Test method

Functional response / bump test

Manual test gas

50% v/v methane

High-concentration gas applied to the RGC, not a declaration of the detector measurement scale.

Maximum RGC gas flow

0.3 L/min

Typical application duration

30–60 seconds

Long tubing increases delivery time.

Inlet protection

Inline particulate filter

Outlet arrangement

One-way valve; safe exhaust routed away from the detector

RGC response is not a span-calibration reading

The RGC provides a practical response check at a difficult-to-access detector. Response depends on the configured calibration; do not expect a universal numerical reading from the test gas. The fitted cell does not include a sampling pump or turn this diffusion detector into a high-concentration sampling model. Vent the high-concentration test gas safely, away from the sensing path and people.

Inspect and test; do not add unnecessary routine span adjustment

Honeywell states that Optima Plus does not require routine calibration. Schedule inspections and gas response checks for the actual installation conditions, and investigate failed checks or contamination warnings. Where adjustment is needed, follow the gas-specific zero/span procedure rather than imposing a generic six-month recalibration rule from another detector family.

Clean optics without damaging them

Remove contamination with the documented mild detergent and a soft cloth or cotton bud. Do not use solvents or abrasives. Restore the dust barrier, weather protection and shade in their correct positions after service, then complete the required response check before removing inhibit.

Sourcing and order support

Order the exact product and condition your project requires, with assistance from quotation through delivery.

Exact product identification

Your quotation references the complete manufacturer part number to keep the requested product clear.

Condition options

Tell us whether you need new original, new surplus, used, refurbished or repaired equipment.

International delivery

Shipping options are prepared around your destination, quantity and requested delivery date.

Documentation support

Access available manufacturer product data, manuals and certificates associated with the order number.