ABB System pro M compact S200 thermal-magnetic miniature circuit breakers. Start with C-curve S201 single-pole and S203 three-pole models at 6, 10, 16, 20 and 32 A, with 6 kA Icn under IEC/EN 60898-1.

View products

S200 circuit breakers

Choose the pole configuration and current, then match the trip curve, applicable standard and fault level.

Match the protection to the circuit

A shared DIN-rail format does not make different current, curve or standard variants interchangeable.

  1. 01

    Current and trip characteristic

    The thermal release protects against overload and the electromagnetic release against short circuit. Choose rated current around the circuit conductors and load behavior, not simply the load’s average current.

    • This first selection is C curve only; the wider S200 family includes other characteristics.
    • An MCB is not an RCD or a dedicated adjustable motor-overload relay.
  2. 02

    Icn, Icu and regional application

    Standard S200 has 6 kA Icn under IEC/EN 60898-1. Its IEC/EN 60947-2 Icu rating is a different measure; do not label the whole family with a context-free 10 kA claim.

    • The selected models have 10 kA Icu at 230 V AC for 1P or 400 V AC for 3P.
    • UL 1077 supplementary-protector status is not UL 489 branch-circuit certification.
  3. 03

    Terminals, temperature and accessories

    Screw terminals accept rigid conductors up to 35 mm² or flexible conductors up to 25 mm². Allow for thermal grouping and enclosure temperature around the 30 °C IEC/EN 60898-1 reference.

    • Tightening torque 2.8 N·m; stripping length 12.5 mm.
    • Busbars and auxiliary/signaling contacts are selected separately.