Skip to content
ABB S200 3-pole miniature circuit breaker with black toggle and red brand stripe

ABB S203-C6 S200 3-Pole 6 A C-Curve Miniature Circuit Breaker

S203-C6

S200 3-pole C-curve MCB, 6 A, 6 kA Icn under IEC/EN 60898-1 at 400 V AC. Thermal-magnetic overcurrent protection, screw terminals and 52.5 mm-wide DIN-rail housing. ABB order code 2CDS253001R0064.

Availability
In Stock
Available quantity
12 units
Condition
New Original
SKU
S203-C6
Lifecycle
Active
$14.22
Request a quote
Ask a product question

12 months warranty

Warranty coverage and terms are confirmed with your order.

Fast shipping

We coordinate the fastest available shipping option for your destination.

Secure payment

Available payment methods are handled through secure payment channels.

Worldwide delivery

Carrier and delivery options are confirmed for your destination before dispatch.

Independent supplier: Xindustra is not an authorized distributor, reseller, or representative of ABB. Brand names are used for identification and compatibility purposes only. Read disclaimer

Technical specifications

Protection ratings, terminal connections and installation data for S203-C6.

6 A C-curve overcurrent protection

S203-C6 is a 3-pole, 6 A ABB S200 miniature circuit breaker. Its delayed thermal release protects against overload and its electromagnetic release responds to short circuits. It has three protected poles in a 52.5 mm-wide housing for three-phase circuit arrangements. This is an MCB, not a residual-current device.

Electrical selection

Type designation

S203-C6

ABB order code

2CDS253001R0064

Product family

System pro M compact S200

Rated current

6 A

Tripping characteristic

C

Protected poles

3

Pole configuration

3P

Rated AC voltage, IEC/EN 60898-1

400 V AC

Rated frequency

50 / 60 Hz

Rated insulation voltage

440 V

Reference ambient, IEC/EN 60898-1

30 °C

Short-circuit ratings by standard

Icn, IEC/EN 60898-1

6 kA

At 400 V AC.

Icu, IEC/EN 60947-2

10 kA

At 400 V AC.

Ics, IEC/EN 60947-2

7.5 kA

At 400 V AC.

Keep the breaking-capacity standard attached to the number

The 6 kA Icn and 10 kA Icu values describe different standard-based ratings; they do not make this a higher-capacity S200M breaker. Under UL 1077, standard S200 devices are supplementary protectors, not UL 489 branch-circuit breakers.

Select the circuit, not only the current number

Use the 6 A rating together with conductor capacity, load starting behavior and the prospective short-circuit current at the installation point. The C characteristic defines the trip response; the breaker is not a dedicated adjustable motor-overload relay. Residual-current protection requires a separate suitable device.

Three protected poles, no fourth neutral pole

S203-C6 is 3P, not 3P+N or 4P. It provides three protected current paths; a fourth neutral pole is not part of this product.

Screw-terminal data

Terminal design

Failsafe bi-directional cylinder-lift screw terminals

Rigid conductor

0.75–35 mm²

Flexible conductor

0.75–25 mm²

Flexible with ferrule

0.75–25 mm²

Stripping length

12.5 mm

Tightening torque

2.8 N·m

Recommended screwdriver

Pozidriv 2

Supply connection direction

Either side, as stated by ABB

Busbar and indication are separate selection decisions

The System pro M compact terminal design supports conductor and busbar connections. Select a busbar with the matching pitch, pole arrangement and current rating. Auxiliary/signaling contacts are separately selected accessories; the standard breaker itself provides red ON / green OFF mechanical contact-position indication, not a remote electrical output.

Mechanical and environmental data

Dimensions (W × H × D)

52.5 mm × 88 mm × 69 mm

DIN modules

3

Net product weight

0.336 kg

Power loss at rated conditions

6 W

Total device value, not an extra value per pole.

Mounting

DIN rail, IEC 60715

Mounting position

Any

Operating ambient

−25 to +55 °C

Storage ambient

−40 to +70 °C

Protection degree

IP20; IP40 in an enclosure with cover

S200 DIN-rail mounting and release

Original ABB S200 installation illustration, from instruction 2CDS207104P0002. Shows the standard S200 rail latch; busbar-assisted and S300 procedures are separate.

S200 DIN-rail mounting and release

Original ABB S200 DIN-rail mounting, tilt-on attachment and screwdriver latch-release sequence

Original ABB S200 installation illustration, from instruction 2CDS207104P0002. Shows the standard S200 rail latch; busbar-assisted and S300 procedures are separate.

Ambient range is not a full-current guarantee at every temperature

The thermal release responds to surrounding temperature and neighboring devices. The IEC/EN 60898-1 reference temperature is 30 °C; use the manufacturer’s temperature/grouping factors for a tightly populated or hotter cabinet. IP40 applies with the enclosure cover, not to a loose breaker on an open rail.

Preserve the complete order code

Order S203-C6 as 2CDS253001R0064. A similar S200M, S200P, S200C or neutral-switching suffix changes the device specification. This 3P C6 configuration must not be substituted solely because another breaker fits the same DIN rail.

Sourcing and order support

Order the exact product and condition your project requires, with assistance from quotation through delivery.

Exact product identification

Your quotation references the complete manufacturer part number to keep the requested product clear.

Condition options

Tell us whether you need new original, new surplus, used, refurbished or repaired equipment.

International delivery

Shipping options are prepared around your destination, quantity and requested delivery date.

Documentation support

Access available manufacturer product data, manuals and certificates associated with the order number.