Honeywell SPXCDASMRX Sensepoint XCD Methane IR Gas Detector

SPXCDASMRX

Complete Sensepoint XCD methane detector with ndir infrared sensing, 0–100% LEL default range and epoxy-painted 316 stainless steel housing. ATEX/IECEx/AP, M20 entries, 4–20 mA source/sink and three relays; base version without Modbus.

Availability
In Stock
Available quantity
12 units
Condition
New Original
SKU
SPXCDASMRX
Lifecycle
Active
$2,363.00
Request a quote
Ask a product question

12 months warranty

Warranty coverage and terms are confirmed with your order.

Fast shipping

We coordinate the fastest available shipping option for your destination.

Secure payment

Available payment methods are handled through secure payment channels.

Worldwide delivery

Carrier and delivery options are confirmed for your destination before dispatch.

Independent supplier: Xindustra is not an authorized distributor, reseller, or representative of Honeywell. Brand names are used for identification and compatibility purposes only. Read disclaimer

Technical specifications

Gas configuration, controller wiring and installation details for the complete SPXCDASMRX detector.

Methane IR detection in a complete assembled unit

SPXCDASMRX combines a Sensepoint XCD display transmitter with a directly mounted ndir infrared sensor for methane. It has epoxy-painted 316 stainless steel housing, two M20 cable entries and the ATEX/IECEx/AP ordering configuration. It is a complete detector kit, not a replacement sensor cartridge or a remote RTD/RFD transmitter.

Exact product identity

Manufacturer part number

SPXCDASMRX

Detected gas

Methane (CH4)

Sensing technology

NDIR infrared

Housing

Epoxy-painted 316 stainless steel

Cable entry

2 × M20

Ordering approval family

ATEX / IECEx / AP

This A-version order code is separate from UL/NPT configurations.

Main output

3-wire 4–20 mA, selectable source or sink

Relay outputs

Two alarm relays and one fault relay

Modbus option

Not included in this order code

Factory Modbus variants have an additional final M.

Measurement scale and factory alarm settings

Measurement scale and factory alarm settings
Parameter / conditionSettingMeaning
Measurement scale0–100% LELPercentage of the lower explosive limit
Selectable full scale20–100% LEL full scale, in 10% LEL stepsScale adjustment does not change the sensor technology
Alarm 120% LEL, risingFirst rising gas alarm
Alarm 240% LEL, risingSecond rising gas alarm

Factory defaults are programmable settings, not universal site alarm recommendations. The detector’s configured full scale and receiving controller must use the same range.

What this sensing configuration does

The infrared element is characterized and linearized for methane. It avoids the catalytic-poison mechanism of a pellistor, but it is not a hydrogen detector or a universally linear hydrocarbon detector. Methane and propane IR cartridges are distinct selections.

Electrical integration

Input voltage

16–32 V DC; 24 V DC nominal

At the detector terminals for this ATEX/IECEx/AP version.

Maximum power

5 W at 24 V DC

Use the current manual’s system rating, not a lower sensor-only figure.

Typical start-up current

Less than 800 mA

Power-supply dependent; allow start-up capacity when sizing the supply.

Analog signal

4–20 mA source or sink

Maximum signal-load resistance

250 Ω

Relay contact rating

3 × 5 A at 250 V AC

Each relay has selectable NO/NC contacts and programmable energization/latching behavior.

Terminal capacity

0.5–2.5 mm² (approximately 20–13 AWG)

Power terminals

1 = +24 V; 2 = 0 V

Signal terminal

3 = 4–20 mA

Alarm 1 relay

7 = NC; 8 = COM; 9 = NO

Alarm 2 relay

10 = NC; 11 = COM; 12 = NO

Fault relay

13 = NC; 14 = COM; 15 = NO

Select the current-loop topology at the detector

The source/sink selector is on the rear of the display module. Use the arrangement that matches the receiving gas controller or PLC analog input. This is a powered three-wire transmitter, not a two-wire loop-powered sensor. The manual identifies terminals 4–6 for optional RS485 hardware; their presence in a shared terminal drawing does not include Modbus in this base MPN.

Original three-wire source circuit

SPXCDHMANEN Issue 16, p.20, Diagram 7. Detector terminals are 1 power, 2 common and 3 signal. Controller numbering belongs to the illustrated controller, not the XCD terminal strip.

Honeywell original Sensepoint XCD three-wire current-source wiring diagram showing controller, detector, load and screen

Honeywell original Sensepoint XCD three-wire current-source wiring diagram showing controller, detector, load and screen

SPXCDHMANEN Issue 16, p.20, Diagram 7. Detector terminals are 1 power, 2 common and 3 signal. Controller numbering belongs to the illustrated controller, not the XCD terminal strip.

Original three-wire sink circuit

SPXCDHMANEN Issue 16, p.20, Diagram 8. Match the controller input topology and selector position; the source and sink circuits are alternatives.

Honeywell original Sensepoint XCD three-wire current-sink wiring diagram showing current path, load, power and common

Honeywell original Sensepoint XCD three-wire current-sink wiring diagram showing current path, load, power and common

SPXCDHMANEN Issue 16, p.20, Diagram 8. Match the controller input topology and selector position; the source and sink circuits are alternatives.

Account for controller load and cable drop

Keep at least 16 V DC at this detector after the field-cable voltage drop. The factory 250 Ω load resistor is removed when the receiving controller already provides its own load resistor, as shown in the manual. Terminate the instrumentation screen at one end only; the equipment protective earth is a separate connection.

Analog status values

Normal measurement

4–20 mA

With the default deadband setting.

Fault

0 to less than 1 mA

Inhibit

2 mA default

Toxic/flammable versions also permit a 4 mA inhibit setting.

Maximum over-range

22 mA

Use fault and inhibit as separate controller states

Configure the receiving controller to distinguish gas measurement from start-up, calibration inhibit, fault and over-range. Normal alarm relays default to non-latching, de-energized operation; the fault relay is normally energized. Front-panel configuration can change relay assignments, so an inhibit state is not a healthy zero-gas measurement.

Housing and installation

Overall assembled outline

164 W × 225 H × 99 D mm

Original outline includes the illustrated lower weather-protection assembly.

Mounting centers

80 × 106 mm

Mounting holes

Ø8.5 mm; four holes for M8 fasteners

Approximate device weight

3.7 kg

Current technical manual device weight; not packed shipping weight.

Mounting

Integral wall/surface mounting plate; optional pipe kit

Optional pipe mounting

40–80 mm diameter/cross-section

Sensor full-accuracy operating temperature

−20 to +55 °C

Sensor performance range, separate from the wider enclosure certification temperatures.

Operating pressure

80–120 kPa

Continuous humidity

20–90% RH, non-condensing

Storage temperature

−25 to +65 °C

Ingress-protection family rating

IP66

Protection depends on the specified assembly and accessories; this is not a guarantee of gas measurement during or after water exposure.

Original outline and mounting dimensions

SPXCDHMANEN Issue 16, p.16, Diagram 4; dimensions in mm. This M20 version uses the A-approval entry arrangement. The outline shows the weather-protection assembly; oxygen performance conditions below distinguish its use.

Honeywell Sensepoint XCD original front and side dimension drawing with M20 entries, mounting-hole pitch and assembled outline

Honeywell Sensepoint XCD original front and side dimension drawing with M20 entries, mounting-hole pitch and assembled outline

SPXCDHMANEN Issue 16, p.16, Diagram 4; dimensions in mm. This M20 version uses the A-approval entry arrangement. The outline shows the weather-protection assembly; oxygen performance conditions below distinguish its use.

Keep the sensing point accessible and exposed to the hazard

Position the sensor where released gas can reach it, accounting for release points, ventilation, air movement and the gas behavior in the installation. Reserve access for gas application, magnetic-wand operation and sensor replacement. The optional pipe bracket is a separate accessory, not included merely by this detector order code.

Use the specified weather protection for flammable performance

The flammable performance conditions specify the SPXCDWP weather-protection cup. For the guarded IPX6 arrangement, mount the sensor with its sinter facing downward. Keep the guard and sensing inlet clear; environmental protection does not remove the need for gas response testing.

Enclosure certification is not full-range measurement accuracy

The enclosure certification permits wider ambient temperatures than the sensor performance table. Use the −20 to +55 °C sensor range for the stated measurement performance here. Extension conditions in the manual depend on sensor technology and changed accuracy; they do not establish full accuracy over the whole enclosure temperature range.

Do not open an energized detector in a hazardous atmosphere

Important fit check

Disconnect the equipment or declassify the area before opening the enclosure or replacing the sensor. Use the protective-earth connection and the specified certified cable entries/plugs; keep the enclosure closed in operation.

Sensor-specific commissioning

Default calibration point

50% LEL methane

Calibration-gas flow

0.4–0.6 L/min

Use the S3KCAL calibration cap and an appropriate regulator.

Typical T90 response

<30 s typical

Typical performance table values measured at 20–25 °C; accessory and ambient conditions affect response.

Full-scale configuration

20–100% LEL full scale, in 10% LEL steps

Matching replacement cartridge

SPXCDXSRXSS

A sensor-only service part, not the complete detector MPN.

Stabilize, calibrate and test the complete alarm path

Allow 30 minutes after applying power before initial calibration. A factory calibration enables pre-shipment testing but does not replace site commissioning. Apply the target gas, check the local indication and analog output, and exercise the alarm/fault behavior of the connected system. During calibration the current output is inhibited.

Always pair IR zero with span

An infrared zero adjustment must be followed by span calibration. Do not carry out an IR zero alone. Use the gas for the actual sensor characterization: methane for RX, propane for PX. Exposure to a different hydrocarbon is not evidence that the original calibration remains linear for that gas.

Separate a bump test from a full calibration

A bump test checks that applied gas produces a response; it is not a zero/span calibration. Honeywell recommends testing and recalibration at six-month intervals or the established site interval. Shorten the interval when sensor contamination or exposure can affect sensitivity. Use the same sensor type for replacement, then recommission the detector.

Configure without opening the enclosure

The magnetic wand operates the display’s three magnetic switches for configuration, review and calibration. Green, flashing yellow and flashing red backlighting distinguish normal, fault and alarm states. These local indications supplement—not replace—the controller’s analog and relay supervision.

Sourcing and order support

Order the exact product and condition your project requires, with assistance from quotation through delivery.

Exact product identification

Your quotation references the complete manufacturer part number to keep the requested product clear.

Condition options

Tell us whether you need new original, new surplus, used, refurbished or repaired equipment.

International delivery

Shipping options are prepared around your destination, quantity and requested delivery date.

Documentation support

Access available manufacturer product data, manuals and certificates associated with the order number.