Exact product identification
Your quotation references the complete manufacturer part number to keep the requested product clear.

SPXCDASMPX
Complete Sensepoint XCD propane detector with ndir infrared sensing, 0–100% LEL default range and epoxy-painted 316 stainless steel housing. ATEX/IECEx/AP, M20 entries, 4–20 mA source/sink and three relays; base version without Modbus.
Warranty coverage and terms are confirmed with your order.
We coordinate the fastest available shipping option for your destination.
Available payment methods are handled through secure payment channels.
Carrier and delivery options are confirmed for your destination before dispatch.
Independent supplier: Xindustra is not an authorized distributor, reseller, or representative of Honeywell. Brand names are used for identification and compatibility purposes only. Read disclaimer
Gas configuration, controller wiring and installation details for the complete SPXCDASMPX detector.
SPXCDASMPX combines a Sensepoint XCD display transmitter with a directly mounted ndir infrared sensor for propane. It has epoxy-painted 316 stainless steel housing, two M20 cable entries and the ATEX/IECEx/AP ordering configuration. It is a complete detector kit, not a replacement sensor cartridge or a remote RTD/RFD transmitter.
SPXCDASMPX
Propane (C3H8)
NDIR infrared
Epoxy-painted 316 stainless steel
2 × M20
ATEX / IECEx / AP
This A-version order code is separate from UL/NPT configurations.
3-wire 4–20 mA, selectable source or sink
Two alarm relays and one fault relay
Not included in this order code
Factory Modbus variants have an additional final M.
| Parameter / condition | Setting | Meaning |
|---|---|---|
| Measurement scale | 0–100% LEL | Percentage of the lower explosive limit |
| Selectable full scale | 20–100% LEL full scale, in 10% LEL steps | Scale adjustment does not change the sensor technology |
| Alarm 1 | 20% LEL, rising | First rising gas alarm |
| Alarm 2 | 40% LEL, rising | Second rising gas alarm |
Factory defaults are programmable settings, not universal site alarm recommendations. The detector’s configured full scale and receiving controller must use the same range.
This is the propane-characterized infrared version, not the methane IR version. The manual provides cross-reference factors for selected other hydrocarbons, but those factors apply to concentrations expressed as volume percent and do not make every gas an interchangeable factory calibration.
The propane IR manual table gives factors for ethylene, n-butane and n-pentane in volume-percent terms. Those factors do not apply directly to arbitrary %LEL readings. Calibration gas, target gas and their LEL definitions remain part of the measurement configuration.
16–32 V DC; 24 V DC nominal
At the detector terminals for this ATEX/IECEx/AP version.
5 W at 24 V DC
Use the current manual’s system rating, not a lower sensor-only figure.
Less than 800 mA
Power-supply dependent; allow start-up capacity when sizing the supply.
4–20 mA source or sink
250 Ω
3 × 5 A at 250 V AC
Each relay has selectable NO/NC contacts and programmable energization/latching behavior.
0.5–2.5 mm² (approximately 20–13 AWG)
1 = +24 V; 2 = 0 V
3 = 4–20 mA
7 = NC; 8 = COM; 9 = NO
10 = NC; 11 = COM; 12 = NO
13 = NC; 14 = COM; 15 = NO
The source/sink selector is on the rear of the display module. Use the arrangement that matches the receiving gas controller or PLC analog input. This is a powered three-wire transmitter, not a two-wire loop-powered sensor. The manual identifies terminals 4–6 for optional RS485 hardware; their presence in a shared terminal drawing does not include Modbus in this base MPN.
SPXCDHMANEN Issue 16, p.20, Diagram 7. Detector terminals are 1 power, 2 common and 3 signal. Controller numbering belongs to the illustrated controller, not the XCD terminal strip.
SPXCDHMANEN Issue 16, p.20, Diagram 8. Match the controller input topology and selector position; the source and sink circuits are alternatives.
Keep at least 16 V DC at this detector after the field-cable voltage drop. The factory 250 Ω load resistor is removed when the receiving controller already provides its own load resistor, as shown in the manual. Terminate the instrumentation screen at one end only; the equipment protective earth is a separate connection.
4–20 mA
With the default deadband setting.
0 to less than 1 mA
2 mA default
Toxic/flammable versions also permit a 4 mA inhibit setting.
22 mA
Configure the receiving controller to distinguish gas measurement from start-up, calibration inhibit, fault and over-range. Normal alarm relays default to non-latching, de-energized operation; the fault relay is normally energized. Front-panel configuration can change relay assignments, so an inhibit state is not a healthy zero-gas measurement.
164 W × 225 H × 99 D mm
Original outline includes the illustrated lower weather-protection assembly.
80 × 106 mm
Ø8.5 mm; four holes for M8 fasteners
3.7 kg
Current technical manual device weight; not packed shipping weight.
Integral wall/surface mounting plate; optional pipe kit
40–80 mm diameter/cross-section
−20 to +55 °C
Sensor performance range, separate from the wider enclosure certification temperatures.
80–120 kPa
20–90% RH, non-condensing
−25 to +65 °C
IP66
Protection depends on the specified assembly and accessories; this is not a guarantee of gas measurement during or after water exposure.
SPXCDHMANEN Issue 16, p.16, Diagram 4; dimensions in mm. This M20 version uses the A-approval entry arrangement. The outline shows the weather-protection assembly; oxygen performance conditions below distinguish its use.
Position the sensor where released gas can reach it, accounting for release points, ventilation, air movement and the gas behavior in the installation. Reserve access for gas application, magnetic-wand operation and sensor replacement. The optional pipe bracket is a separate accessory, not included merely by this detector order code.
The flammable performance conditions specify the SPXCDWP weather-protection cup. For the guarded IPX6 arrangement, mount the sensor with its sinter facing downward. Keep the guard and sensing inlet clear; environmental protection does not remove the need for gas response testing.
The enclosure certification permits wider ambient temperatures than the sensor performance table. Use the −20 to +55 °C sensor range for the stated measurement performance here. Extension conditions in the manual depend on sensor technology and changed accuracy; they do not establish full accuracy over the whole enclosure temperature range.
Important fit check
Disconnect the equipment or declassify the area before opening the enclosure or replacing the sensor. Use the protective-earth connection and the specified certified cable entries/plugs; keep the enclosure closed in operation.
50% LEL propane
0.4–0.6 L/min
Use the S3KCAL calibration cap and an appropriate regulator.
<30 s typical
Typical performance table values measured at 20–25 °C; accessory and ambient conditions affect response.
20–100% LEL full scale, in 10% LEL steps
SPXCDXSPXSS
A sensor-only service part, not the complete detector MPN.
Allow 30 minutes after applying power before initial calibration. A factory calibration enables pre-shipment testing but does not replace site commissioning. Apply the target gas, check the local indication and analog output, and exercise the alarm/fault behavior of the connected system. During calibration the current output is inhibited.
An infrared zero adjustment must be followed by span calibration. Do not carry out an IR zero alone. Use the gas for the actual sensor characterization: methane for RX, propane for PX. Exposure to a different hydrocarbon is not evidence that the original calibration remains linear for that gas.
A bump test checks that applied gas produces a response; it is not a zero/span calibration. Honeywell recommends testing and recalibration at six-month intervals or the established site interval. Shorten the interval when sensor contamination or exposure can affect sensitivity. Use the same sensor type for replacement, then recommission the detector.
The magnetic wand operates the display’s three magnetic switches for configuration, review and calibration. Green, flashing yellow and flashing red backlighting distinguish normal, fault and alarm states. These local indications supplement—not replace—the controller’s analog and relay supervision.
Order the exact product and condition your project requires, with assistance from quotation through delivery.
Your quotation references the complete manufacturer part number to keep the requested product clear.
Tell us whether you need new original, new surplus, used, refurbished or repaired equipment.
Shipping options are prepared around your destination, quantity and requested delivery date.
Access available manufacturer product data, manuals and certificates associated with the order number.