SPXCDALMO1
Complete Sensepoint XCD oxygen detector with electrochemical sensing, 0–25.0% v/v default range and epoxy-painted aluminium alloy lm25 housing. ATEX/IECEx/AP, M20 entries, 4–20 mA source/sink and three relays; base version without Modbus.
Warranty coverage and terms are confirmed with your order.
We coordinate the fastest available shipping option for your destination.
Available payment methods are handled through secure payment channels.
Carrier and delivery options are confirmed for your destination before dispatch.
Independent supplier: Xindustra is not an authorized distributor, reseller, or representative of Honeywell. Brand names are used for identification and compatibility purposes only. Read disclaimer
Gas configuration, controller wiring and installation details for the complete SPXCDALMO1 detector.
SPXCDALMO1 combines a Sensepoint XCD display transmitter with a directly mounted electrochemical sensor for oxygen. It has epoxy-painted aluminium alloy lm25 housing, two M20 cable entries and the ATEX/IECEx/AP ordering configuration. It is a complete detector kit, not a replacement sensor cartridge or a remote RTD/RFD transmitter.
SPXCDALMO1
Oxygen (O2)
Electrochemical
Epoxy-painted aluminium alloy LM25
2 × M20
ATEX / IECEx / AP
This A-version order code is separate from UL/NPT configurations.
3-wire 4–20 mA, selectable source or sink
Two alarm relays and one fault relay
Not included in this order code
Factory Modbus variants have an additional final M.
| Parameter / condition | Setting | Meaning |
|---|---|---|
| Measurement scale | 0–25.0% v/v | Oxygen volume concentration |
| Selectable full scale | Fixed 25.0% v/v full scale | Fixed oxygen scale |
| Alarm 1 | 19.5% v/v, falling | Oxygen deficiency |
| Alarm 2 | 23.5% v/v, rising | Oxygen enrichment |
Factory defaults are programmable settings, not universal site alarm recommendations. The detector’s configured full scale and receiving controller must use the same range.
Measures oxygen deficiency and enrichment on a fixed 0–25.0% volume scale. Low-oxygen and high-oxygen alarms use opposite directions. This sensor is not specified for inertisation measurements, and the 25% display range does not authorize operating the equipment in an oxygen-enriched hazardous atmosphere.
16–32 V DC; 24 V DC nominal
At the detector terminals for this ATEX/IECEx/AP version.
5 W at 24 V DC
Use the current manual’s system rating, not a lower sensor-only figure.
Less than 800 mA
Power-supply dependent; allow start-up capacity when sizing the supply.
4–20 mA source or sink
250 Ω
3 × 5 A at 250 V AC
Each relay has selectable NO/NC contacts and programmable energization/latching behavior.
0.5–2.5 mm² (approximately 20–13 AWG)
1 = +24 V; 2 = 0 V
3 = 4–20 mA
7 = NC; 8 = COM; 9 = NO
10 = NC; 11 = COM; 12 = NO
13 = NC; 14 = COM; 15 = NO
The source/sink selector is on the rear of the display module. Use the arrangement that matches the receiving gas controller or PLC analog input. This is a powered three-wire transmitter, not a two-wire loop-powered sensor. The manual identifies terminals 4–6 for optional RS485 hardware; their presence in a shared terminal drawing does not include Modbus in this base MPN.
SPXCDHMANEN Issue 16, p.20, Diagram 7. Detector terminals are 1 power, 2 common and 3 signal. Controller numbering belongs to the illustrated controller, not the XCD terminal strip.
SPXCDHMANEN Issue 16, p.20, Diagram 8. Match the controller input topology and selector position; the source and sink circuits are alternatives.
Keep at least 16 V DC at this detector after the field-cable voltage drop. The factory 250 Ω load resistor is removed when the receiving controller already provides its own load resistor, as shown in the manual. Terminate the instrumentation screen at one end only; the equipment protective earth is a separate connection.
4–20 mA
With the default deadband setting.
0 to less than 1 mA
2 mA default
Oxygen also permits a 17.4 mA inhibit setting.
22 mA
Configure the receiving controller to distinguish gas measurement from start-up, calibration inhibit, fault and over-range. Normal alarm relays default to non-latching, de-energized operation; the fault relay is normally energized. Front-panel configuration can change relay assignments, so an inhibit state is not a healthy zero-gas measurement.
164 W × 225 H × 99 D mm
Original outline includes the illustrated lower weather-protection assembly.
80 × 106 mm
Ø8.5 mm; four holes for M8 fasteners
1.7 kg
Current technical manual device weight; not packed shipping weight.
Integral wall/surface mounting plate; optional pipe kit
40–80 mm diameter/cross-section
−20 to +55 °C
Sensor performance range, separate from the wider enclosure certification temperatures.
80–120 kPa
20–90% RH, non-condensing
−25 to +65 °C
IP66
Protection depends on the specified assembly and accessories; this is not a guarantee of gas measurement during or after water exposure.
SPXCDHMANEN Issue 16, p.16, Diagram 4; dimensions in mm. This M20 version uses the A-approval entry arrangement. The outline shows the weather-protection assembly; oxygen performance conditions below distinguish its use.
Position the sensor where released gas can reach it, accounting for release points, ventilation, air movement and the gas behavior in the installation. Reserve access for gas application, magnetic-wand operation and sensor replacement. The optional pipe bracket is a separate accessory, not included merely by this detector order code.
The manual’s EN 50104 oxygen performance conditions specify operation without the SPXCDWP weather-protection cup. Its separate IPX6 assembly condition uses the guard and a downward-facing sinter. These are different configurations: do not combine the oxygen performance condition and guarded ingress-protection condition into one unqualified installation claim. Oxygen measurement is for deficiency/enrichment, not inertisation. The manual also restricts equipment operation in atmospheres above 21% oxygen for electrical safety.
The enclosure certification permits wider ambient temperatures than the sensor performance table. Use the −20 to +55 °C sensor range for the stated measurement performance here. Extension conditions in the manual depend on sensor technology and changed accuracy; they do not establish full accuracy over the whole enclosure temperature range.
Important fit check
Disconnect the equipment or declassify the area before opening the enclosure or replacing the sensor. Use the protective-earth connection and the specified certified cable entries/plugs; keep the enclosure closed in operation.
20.9% v/v oxygen
0.5–1.0 L/min
Use the S3KCAL calibration cap and an appropriate regulator.
<30 s typical; ≤38 s under EN 50104 test conditions
Typical performance table values measured at 20–25 °C; accessory and ambient conditions affect response.
Fixed 25.0% v/v full scale
SPXCDXSO1SS
A sensor-only service part, not the complete detector MPN.
Allow 30 minutes after applying power before initial calibration. A factory calibration enables pre-shipment testing but does not replace site commissioning. Apply the target gas, check the local indication and analog output, and exercise the alarm/fault behavior of the connected system. During calibration the current output is inhibited.
The oxygen sensor does not use the general zeroing procedure. Span with a known 20.9% v/v oxygen source; suitable clean background air can be used as described in the manual. The low alarm falls at 19.5% v/v by default, while the upper alarm rises at 23.5% v/v.
A bump test checks that applied gas produces a response; it is not a zero/span calibration. Honeywell recommends testing and recalibration at six-month intervals or the established site interval. Shorten the interval when sensor contamination or exposure can affect sensitivity. Use the same sensor type for replacement, then recommission the detector.
The magnetic wand operates the display’s three magnetic switches for configuration, review and calibration. Green, flashing yellow and flashing red backlighting distinguish normal, fault and alarm states. These local indications supplement—not replace—the controller’s analog and relay supervision.
Order the exact product and condition your project requires, with assistance from quotation through delivery.
Your quotation references the complete manufacturer part number to keep the requested product clear.
Tell us whether you need new original, new surplus, used, refurbished or repaired equipment.
Shipping options are prepared around your destination, quantity and requested delivery date.
Access available manufacturer product data, manuals and certificates associated with the order number.