Skip to content
Beckhoff EL3014 EtherCAT analog input terminal

Beckhoff EL3014 4-Channel 0–20 mA Analog Input Terminal

EL3014

4-channel EtherCAT analog input terminal for 0–20 mA current signals. 12-bit conversion with differential inputs, spring-loaded field terminals and a 12 mm aligned width.

Availability
In Stock
Condition
New Original
SKU
EL3014
Lifecycle
Active
$359.00
Request a quote
Ask a product question

12 months warranty

Warranty coverage and terms are confirmed with your order.

Fast shipping

We coordinate the fastest available shipping option for your destination.

Secure payment

Available payment methods are handled through secure payment channels.

Worldwide delivery

Carrier and delivery options are confirmed for your destination before dispatch.

Independent supplier: Xindustra is not an authorized distributor, reseller, or representative of Beckhoff. Brand names are used for identification and compatibility purposes only. Read disclaimer

Technical specifications

Signal acquisition, terminal connections and installation data for EL3014.

Acquire zero-based current signals

EL3014 brings 4 0–20 mA current inputs into an EtherCAT I/O station. Use it for devices with a 0–20 mA output. Select EL302x instead when the required nominal range starts at 4 mA.

Acquisition characteristics

Manufacturer part number

EL3014

Analog input channels

4

Nominal signal range

0–20 mA

Input reference

Differential

Resolution

12 bits; value presented in a 16-bit word

Sampling type

Multiplex

Typical conversion time

0.625 ms, default 50 Hz filter

Input filter cut-off frequency

1 kHz

Input resistance

85 Ω typical plus diode voltage

Maximum common-mode voltage

10 V

Measuring error at 0 to +55 °C

<±0.3% of the full measuring range

Measuring error outside 0 to +55 °C

<±0.5% of the full measuring range, within permitted operating range

Resolution and measurement accuracy are different

The 12-bit converter determines quantization; the 16-bit process value is its data representation, not a 16-bit measurement specification. Use the full-scale measuring-error figures for accuracy calculations. The conversion-time rating is an acquisition characteristic, not an end-to-end PLC response-time guarantee.

EL3014 terminal assignment and connection diagram

Original Beckhoff EL30xx manual v6.1.0, p.39. Terminal markings and the matching signal connection are retained.

EL3014 terminal assignment and connection diagram

EL3014 terminal assignment and connection diagram

Original Beckhoff EL30xx manual v6.1.0, p.39. Terminal markings and the matching signal connection are retained.

Ground reference for this exact model

The four differential current inputs share a reference ground connected to the 0 V power contact. Differential measurement does not provide four independently isolated channels. Keep the documented common-mode limit within the field wiring design.

Separate electronics power from the field signal

Terminal electronics are supplied by the E-bus. The power contacts distribute field power along the terminal row; the analog signal must still be connected to its designated measurement terminals. A current-input terminal measures a loop signal and does not replace the transmitter or its loop supply.

Use channel diagnostics during commissioning

Overcurrent is indicated in the process image and by a channel error LED. A 0 mA nominal lower endpoint is a valid part of the 0–20 mA range; it does not carry the same live-zero meaning as a 4–20 mA signal.

Terminal and station data

Electronics supply

E-bus

Typical E-bus current

130 mA

Electrical isolation

500 V between E-bus and field voltage

Default process image per channel

2 bytes status + 2 bytes value

Envelope width × height × depth

Approximately 15 × 100 × 70 mm

Aligned terminal width

12 mm

Mounting

35 mm DIN rail to EN 60715

Weight

Approximately 55 g

Operating ambient temperature

−25 to +60 °C

Storage temperature

−40 to +85 °C

Relative humidity

95%, non-condensing

Protection rating

IP20

Install as part of an EtherCAT terminal station

Use an EtherCAT coupler or controller with an E-bus terminal row and include this exact terminal in the master configuration. Budget its typical 130 mA E-bus demand with the other terminals and power segments. It is an I/O terminal, not a standalone Ethernet sensor interface or PLC.

Match the signal circuit before changing channel count

Preserve the 0–20 mA input range, differential measurement method and model-specific ground connection when selecting a replacement. Standard EL spring terminals and ES pluggable-wiring variants are distinct ordering references. The 500 V isolation rating applies between E-bus and field, not individually between every input channel.

Sourcing and order support

Order the exact product and condition your project requires, with assistance from quotation through delivery.

Exact product identification

Your quotation references the complete manufacturer part number to keep the requested product clear.

Condition options

Tell us whether you need new original, new surplus, used, refurbished or repaired equipment.

International delivery

Shipping options are prepared around your destination, quantity and requested delivery date.

Documentation support

Access available manufacturer product data, manuals and certificates associated with the order number.