Exact product identification
Your quotation references the complete manufacturer part number to keep the requested product clear.

EL3004
4-channel EtherCAT analog input terminal for ±10 V voltage signals. 12-bit conversion with single-ended inputs, spring-loaded field terminals and a 12 mm aligned width.
Warranty coverage and terms are confirmed with your order.
We coordinate the fastest available shipping option for your destination.
Available payment methods are handled through secure payment channels.
Carrier and delivery options are confirmed for your destination before dispatch.
Independent supplier: Xindustra is not an authorized distributor, reseller, or representative of Beckhoff. Brand names are used for identification and compatibility purposes only. Read disclaimer
Signal acquisition, terminal connections and installation data for EL3004.
EL3004 brings 4 ±10 V voltage inputs into an EtherCAT I/O station. Use it for sensors and devices with a bipolar voltage output; it is not a current-loop input.
EL3004
4
±10 V
Single-ended
12 bits; value presented in a 16-bit word
Multiplex
0.625 ms, default 50 Hz filter
1 kHz
>130 kΩ
<±0.3% of the full measuring range
<±0.5% of the full measuring range, within permitted operating range
The 12-bit converter determines quantization; the 16-bit process value is its data representation, not a 16-bit measurement specification. Use the full-scale measuring-error figures for accuracy calculations. The conversion-time rating is an acquisition characteristic, not an end-to-end PLC response-time guarantee.
Original Beckhoff EL30xx manual v6.1.0, p.25. Terminal markings and the matching signal connection are retained.
The inputs share an internal signal ground that is not connected to the power contacts. Connect the signal return to the marked 0 V/GND terminal, rather than assuming the power-contact 0 V provides the measurement reference.
Terminal electronics are supplied by the E-bus. The power contacts distribute field power along the terminal row; the analog signal must still be connected to its designated measurement terminals. A current-input terminal measures a loop signal and does not replace the transmitter or its loop supply.
E-bus
130 mA
500 V between E-bus and field voltage
2 bytes status + 2 bytes value
Approximately 15 × 100 × 70 mm
12 mm
35 mm DIN rail to EN 60715
Approximately 70 g
−25 to +60 °C
−40 to +85 °C
95%, non-condensing
IP20
Use an EtherCAT coupler or controller with an E-bus terminal row and include this exact terminal in the master configuration. Budget its typical 130 mA E-bus demand with the other terminals and power segments. It is an I/O terminal, not a standalone Ethernet sensor interface or PLC.
Preserve the ±10 V input range, single-ended measurement method and model-specific ground connection when selecting a replacement. Standard EL spring terminals and ES pluggable-wiring variants are distinct ordering references. The 500 V isolation rating applies between E-bus and field, not individually between every input channel.
Order the exact product and condition your project requires, with assistance from quotation through delivery.
Your quotation references the complete manufacturer part number to keep the requested product clear.
Tell us whether you need new original, new surplus, used, refurbished or repaired equipment.
Shipping options are prepared around your destination, quantity and requested delivery date.
Access available manufacturer product data, manuals and certificates associated with the order number.