Exact product identification
Your quotation references the complete manufacturer part number to keep the requested product clear.

5069-OB16F
5069-OB16F Compact 5000 fast dc sourcing output module. 16 fast sourcing DC outputs at 0.5 A per channel, with scheduled-output capability and a 20 µs minimum pulse width. Requires a separately ordered 5069-RTB18 terminal block.
Warranty coverage and terms are confirmed with your order.
We coordinate the fastest available shipping option for your destination.
Available payment methods are handled through secure payment channels.
Carrier and delivery options are confirmed for your destination before dispatch.
Independent supplier: Xindustra is not an authorized distributor, reseller, or representative of Allen-Bradley. Brand names are used for identification and compatibility purposes only. Read disclaimer
Signal ratings, field-power arrangement and terminal wiring for 5069-OB16F.
5069-OB16F is an Allen-Bradley Compact 5000 standard digital I/O module. 16 fast sourcing DC outputs at 0.5 A per channel, with scheduled-output capability and a 20 µs minimum pulse width. It expands a compatible Logix system; it is not a CPU, Ethernet adapter or safety I/O module.
5069-OB16F
16
10–32 V DC
24 V DC
0.5 A resistive per channel; 8 A resistive per module
<0.2 V DC
<0.5 mA per point
1 mA
10 µs, ±1 µs at 25 °C and 0.5 A
20 µs at 25 °C and 0.5 A
±10 µs accuracy; 1 ns resolution
OB16F reduces the specified switching delay and pulse width compared with standard OB16, while retaining the same 0.5 A point and 8 A module current limits. Scheduled outputs provide ±10 µs accuracy with 1 ns resolution. No-load and output-fault diagnostics are supported; field-power-loss detection requires Series B hardware.
Use system CIP Sync time synchronization for timestamp and scheduled-output functions. These fast I/O modules are follower-only devices and need another device to provide the leader clock. The published microsecond timing accuracy and nanosecond timestamp resolution describe different properties; neither replaces the configured filter, network update or application timing budget.
Each output can be configured to turn off, turn on or hold its last state; off is the default. Fault-mode duration is also configurable. Set these behaviors deliberately for the connected actuator. These standard outputs do not replace a safety-rated output function.
75 mA at 18–32 V DC
No SA current draw; DC SA bus required
3.25 W
5069-RTB18-SPRING or 5069-RTB18-SCREW; ordered separately
0.4 N·m
0.34–1.5 mm² (22–16 AWG), copper, ≥105 °C
10 mm spring RTB; 12 mm screw RTB
The module electronics draw MOD power, while the outputs take field power from the LA terminals on the module RTB. This module does not draw SA current, but it must still be installed on a DC SA segment. LA power is not a reason to place a DC module on an AC SA bus.
The RTB has OUT0–OUT15 plus LA+ and LA−. Feed actuator power at LA, with load returns to LA−. A faster F module does not provide a larger output current or individually isolated channels.
Rockwell Automation 5069-TD001P-EN-P, March 2026, p.14. Terminal assignment and field-power connections.
Compact 5000 I/O modules do not include the removable terminal block. Choose either the 18-position spring or screw RTB for the wiring method. Both use one wire per terminal; the screw torque applies to the screw RTB, not the spring mechanism.
Install these 5069 modules to the right of a compatible CompactLogix 5380, CompactLogix 5480 or Compact GuardLogix 5380 controller, or use a supported Compact 5000 EtherNet/IP adapter for a remote I/O station. Add the correct module profile and electronic keying in Studio 5000 Logix Designer. A remote station needs its adapter; the I/O module itself has no standalone Ethernet connection.
144.6 × 22 × 105.4 mm
1 standard Compact 5000 slot
175 g
0 to +60 °C
−40 to +85 °C
5–95%, noncondensing
Open style; enclosed installation required
EN50022, 35 × 7.5 mm, compatible zinc-plated steel
For local CompactLogix 5380 systems, mount the I/O assembly horizontally. System clearances depend on the controller and operating temperature: standard CompactLogix 5380 guidance is 50.8 mm at 50/55 °C and 101.6 mm at 60 °C. A standard-only adapter system uses 25.4 mm on all sides; adding safety modules changes the system clearance. Finish the last module with the system end cap.
Compact 5000 5069 modules are not 1769 Compact I/O or 1734 POINT I/O plug-in replacements. Match input/output role, signal type, terminal assignment, software profile and power segment. A matching channel count alone does not establish interchangeability.
Order the exact product and condition your project requires, with assistance from quotation through delivery.
Your quotation references the complete manufacturer part number to keep the requested product clear.
Tell us whether you need new original, new surplus, used, refurbished or repaired equipment.
Shipping options are prepared around your destination, quantity and requested delivery date.
Access available manufacturer product data, manuals and certificates associated with the order number.