Exact product identification
Your quotation references the complete manufacturer part number to keep the requested product clear.

5069-OA16
5069-OA16 Compact 5000 ac output module. 16 solid-state AC outputs, 0.5 A per channel with a 4 A total module limit, using AC SA field power. Requires a separately ordered 5069-RTB18 terminal block.
Warranty coverage and terms are confirmed with your order.
We coordinate the fastest available shipping option for your destination.
Available payment methods are handled through secure payment channels.
Carrier and delivery options are confirmed for your destination before dispatch.
Independent supplier: Xindustra is not an authorized distributor, reseller, or representative of Allen-Bradley. Brand names are used for identification and compatibility purposes only. Read disclaimer
Signal ratings, field-power arrangement and terminal wiring for 5069-OA16.
5069-OA16 is an Allen-Bradley Compact 5000 standard digital I/O module. 16 solid-state AC outputs, 0.5 A per channel with a 4 A total module limit, using AC SA field power. It expands a compatible Logix system; it is not a CPU, Ethernet adapter or safety I/O module.
5069-OA16
16
85–264 V AC, 47–63 Hz
120/240 V AC
0.5 A per channel; 4 A per module
1.5 V AC at 0.5 A
1 mA
Half a cycle, typical at 0–60 °C
5 A for 25 ms, repeatable every 2 s
Sixteen 0.5 A outputs do not provide an 8 A aggregate rating: the module maximum is 4 A. It supports field-power-loss detection but does not provide output short-circuit/overload protection, per-channel no-load diagnostics or scheduled outputs. Small AC loads can respond to the off-state leakage, so include the load’s off-state behavior in the circuit design.
Each output can be configured to turn off, turn on or hold its last state; off is the default. Fault-mode duration is also configurable. Set these behaviors deliberately for the connected actuator. These standard outputs do not replace a safety-rated output function.
100 mA at 18–32 V DC
4 A at 85–264 V AC
3.4 W
5069-RTB18-SPRING or 5069-RTB18-SCREW; ordered separately
0.4 N·m
0.34–1.5 mm² (22–16 AWG), copper, ≥105 °C
10 mm spring RTB; 12 mm screw RTB
This module needs an AC SA power segment. Separate AC and DC SA groups with a 5069-FPD field potential distributor; changing the field bus to AC does not change the 18–32 V DC MOD electronics supply. A Compact GuardLogix 5380 cannot provide AC SA power directly, so its local AC module group requires an intervening FPD.
Connect the AC supply to the device feeding this module’s SA segment. OUT0–OUT15 use the shared AC SA return; the final two RTB positions are unused. This is a solid-state AC output module, not a dry-contact relay output.
Rockwell Automation 5069-TD001P-EN-P, March 2026, p.12. Terminal assignment and field-power connections.
Compact 5000 I/O modules do not include the removable terminal block. Choose either the 18-position spring or screw RTB for the wiring method. Both use one wire per terminal; the screw torque applies to the screw RTB, not the spring mechanism.
Install these 5069 modules to the right of a compatible CompactLogix 5380, CompactLogix 5480 or Compact GuardLogix 5380 controller, or use a supported Compact 5000 EtherNet/IP adapter for a remote I/O station. Add the correct module profile and electronic keying in Studio 5000 Logix Designer. A remote station needs its adapter; the I/O module itself has no standalone Ethernet connection.
144.6 × 22 × 105.4 mm
1 standard Compact 5000 slot
175 g
0 to +60 °C
−40 to +85 °C
5–95%, noncondensing
Open style; enclosed installation required
EN50022, 35 × 7.5 mm, compatible zinc-plated steel
For local CompactLogix 5380 systems, mount the I/O assembly horizontally. System clearances depend on the controller and operating temperature: standard CompactLogix 5380 guidance is 50.8 mm at 50/55 °C and 101.6 mm at 60 °C. A standard-only adapter system uses 25.4 mm on all sides; adding safety modules changes the system clearance. Finish the last module with the system end cap.
Compact 5000 5069 modules are not 1769 Compact I/O or 1734 POINT I/O plug-in replacements. Match input/output role, signal type, terminal assignment, software profile and power segment. A matching channel count alone does not establish interchangeability.
Order the exact product and condition your project requires, with assistance from quotation through delivery.
Your quotation references the complete manufacturer part number to keep the requested product clear.
Tell us whether you need new original, new surplus, used, refurbished or repaired equipment.
Shipping options are prepared around your destination, quantity and requested delivery date.
Access available manufacturer product data, manuals and certificates associated with the order number.