5069-IB16 Compact 5000 dc sinking input module. 16 sinking DC inputs for sourcing field devices, with one shared common and standard-speed input processing. Requires a separately ordered 5069-RTB18 terminal block.

Availability
In Stock
Available quantity
12 units
Condition
New Original
SKU
5069-IB16
Lifecycle
Active
$379.59
Request a quote
Ask a product question

12 months warranty

Warranty coverage and terms are confirmed with your order.

Fast shipping

We coordinate the fastest available shipping option for your destination.

Secure payment

Available payment methods are handled through secure payment channels.

Worldwide delivery

Carrier and delivery options are confirmed for your destination before dispatch.

Independent supplier: Xindustra is not an authorized distributor, reseller, or representative of Allen-Bradley. Brand names are used for identification and compatibility purposes only. Read disclaimer

Technical specifications

Signal ratings, field-power arrangement and terminal wiring for 5069-IB16.

DC Sinking Input Module

5069-IB16 is an Allen-Bradley Compact 5000 standard digital I/O module. 16 sinking DC inputs for sourcing field devices, with one shared common and standard-speed input processing. It expands a compatible Logix system; it is not a CPU, Ethernet adapter or safety I/O module.

Electrical characteristics

Catalog number

5069-IB16

Channels

16

Signal / load range

10–32 V DC

On-state voltage

10–32 V DC; 24 V DC nominal

On-state current

6 mA nominal at 24 V DC

Off-state voltage / current, maximum

5 V DC / 1.5 mA

Input delay, screw to backplane

≤100 µs, ±10 µs at 25 °C

Minimum input pulse width

60 µs

Simple/frequency counter range

0–500 Hz

Standard input response with adjustable filtering

The input filter uses a 50 µs hardware delay plus a selectable 0–50 ms filter for each transition direction. This is the standard-speed IB16, not the faster IB16F: a shorter sensor pulse or higher pulse rate can require the F model even when the 16-channel count and nominal voltage match.

Power and terminal requirements

MOD electronics supply

75 mA at 18–32 V DC

SA field-side demand / placement

200 mA at 10–32 V DC

Maximum power dissipation

3.9 W

Field terminal block

5069-RTB18-SPRING or 5069-RTB18-SCREW; ordered separately

Screw RTB tightening torque

0.4 N·m

Conductor size

0.34–1.5 mm² (22–16 AWG), copper, ≥105 °C

Wire stripping

10 mm spring RTB; 12 mm screw RTB

Keep MOD, SA and load power distinct

Use a DC SA power segment and a separately budgeted MOD electronics supply. SA powers the input-side field circuit; MOD powers the module electronics. If the system also contains AC SA modules, a 5069-FPD separates those AC and DC field-power groups.

Channel wiring

Inputs 0–15 receive sourcing field signals. Their return is through the module to SA−, so the channel inputs share the DC SA common rather than having individually isolated returns. The final two RTB terminals are unused.

Original manufacturer wiring diagram

Rockwell Automation 5069-TD001P-EN-P, March 2026, p.8. Terminal assignment and field-power connections.

5069-IB16 manufacturer terminal wiring, field supply connections and wiring notes

5069-IB16 manufacturer terminal wiring, field supply connections and wiring notes

Rockwell Automation 5069-TD001P-EN-P, March 2026, p.8. Terminal assignment and field-power connections.

The terminal block is a separate order item

Compact 5000 I/O modules do not include the removable terminal block. Choose either the 18-position spring or screw RTB for the wiring method. Both use one wire per terminal; the screw torque applies to the screw RTB, not the spring mechanism.

Local or adapter-based I/O

Install these 5069 modules to the right of a compatible CompactLogix 5380, CompactLogix 5480 or Compact GuardLogix 5380 controller, or use a supported Compact 5000 EtherNet/IP adapter for a remote I/O station. Add the correct module profile and electronic keying in Studio 5000 Logix Designer. A remote station needs its adapter; the I/O module itself has no standalone Ethernet connection.

Module envelope and environment

Dimensions, H × W × D

144.6 × 22 × 105.4 mm

Slot width

1 standard Compact 5000 slot

Approximate weight

175 g

Operating surrounding air

0 to +60 °C

Nonoperating temperature

−40 to +85 °C

Relative humidity

5–95%, noncondensing

Enclosure type

Open style; enclosed installation required

DIN rail

EN50022, 35 × 7.5 mm, compatible zinc-plated steel

Allow system clearance, not only module width

For local CompactLogix 5380 systems, mount the I/O assembly horizontally. System clearances depend on the controller and operating temperature: standard CompactLogix 5380 guidance is 50.8 mm at 50/55 °C and 101.6 mm at 60 °C. A standard-only adapter system uses 25.4 mm on all sides; adding safety modules changes the system clearance. Finish the last module with the system end cap.

A 5069 catalog number defines the platform

Compact 5000 5069 modules are not 1769 Compact I/O or 1734 POINT I/O plug-in replacements. Match input/output role, signal type, terminal assignment, software profile and power segment. A matching channel count alone does not establish interchangeability.

Sourcing and order support

Order the exact product and condition your project requires, with assistance from quotation through delivery.

Exact product identification

Your quotation references the complete manufacturer part number to keep the requested product clear.

Condition options

Tell us whether you need new original, new surplus, used, refurbished or repaired equipment.

International delivery

Shipping options are prepared around your destination, quantity and requested delivery date.

Documentation support

Access available manufacturer product data, manuals and certificates associated with the order number.