Exact product identification
Your quotation references the complete manufacturer part number to keep the requested product clear.

5069-IA16
5069-IA16 Compact 5000 ac input module. 16 AC inputs in one shared-common group, 120/240 V nominal, with voltage-dependent input filters. Requires a separately ordered 5069-RTB18 terminal block.
Warranty coverage and terms are confirmed with your order.
We coordinate the fastest available shipping option for your destination.
Available payment methods are handled through secure payment channels.
Carrier and delivery options are confirmed for your destination before dispatch.
Independent supplier: Xindustra is not an authorized distributor, reseller, or representative of Allen-Bradley. Brand names are used for identification and compatibility purposes only. Read disclaimer
Signal ratings, field-power arrangement and terminal wiring for 5069-IA16.
5069-IA16 is an Allen-Bradley Compact 5000 standard digital I/O module. 16 AC inputs in one shared-common group, 120/240 V nominal, with voltage-dependent input filters. It expands a compatible Logix system; it is not a CPU, Ethernet adapter or safety I/O module.
5069-IA16
16
79–264 V AC, 47–63 Hz
79–264 V AC
40 V AC
5 mA at 120 V / 50 Hz; 6 mA at 120 V / 60 Hz; 9 mA at 240 V / 50 Hz; 11 mA at 240 V / 60 Hz
10 ms typical at 0–60 °C, plus selected filter time
IEC Type 1
For 120 V AC, the valid off-to-on filter is 1 ms; the on-to-off choices are 10 or 20 ms. At 240 V AC, off-to-on choices are 1, 2 or 5 ms and on-to-off choices are 5, 10 or 20 ms. The software can expose values that are invalid for a connected voltage, so the signal voltage determines which filter setting to use.
75 mA at 18–32 V DC
240 mA at 79–264 V AC
3.5 W
5069-RTB18-SPRING or 5069-RTB18-SCREW; ordered separately
0.4 N·m
0.34–1.5 mm² (22–16 AWG), copper, ≥105 °C
10 mm spring RTB; 12 mm screw RTB
This module needs an AC SA power segment. Separate AC and DC SA groups with a 5069-FPD field potential distributor; changing the field bus to AC does not change the 18–32 V DC MOD electronics supply. A Compact GuardLogix 5380 cannot provide AC SA power directly, so its local AC module group requires an intervening FPD.
Inputs 0–15 share a return through the internal circuitry to SA−. The last two RTB positions are unused. Feed this module from an AC SA power segment; the MOD electronics supply remains DC.
Rockwell Automation 5069-TD001P-EN-P, March 2026, p.7. Terminal assignment and field-power connections.
Compact 5000 I/O modules do not include the removable terminal block. Choose either the 18-position spring or screw RTB for the wiring method. Both use one wire per terminal; the screw torque applies to the screw RTB, not the spring mechanism.
Install these 5069 modules to the right of a compatible CompactLogix 5380, CompactLogix 5480 or Compact GuardLogix 5380 controller, or use a supported Compact 5000 EtherNet/IP adapter for a remote I/O station. Add the correct module profile and electronic keying in Studio 5000 Logix Designer. A remote station needs its adapter; the I/O module itself has no standalone Ethernet connection.
144.6 × 22 × 105.4 mm
1 standard Compact 5000 slot
175 g
0 to +60 °C
−40 to +85 °C
5–95%, noncondensing
Open style; enclosed installation required
EN50022, 35 × 7.5 mm, compatible zinc-plated steel
For local CompactLogix 5380 systems, mount the I/O assembly horizontally. System clearances depend on the controller and operating temperature: standard CompactLogix 5380 guidance is 50.8 mm at 50/55 °C and 101.6 mm at 60 °C. A standard-only adapter system uses 25.4 mm on all sides; adding safety modules changes the system clearance. Finish the last module with the system end cap.
Compact 5000 5069 modules are not 1769 Compact I/O or 1734 POINT I/O plug-in replacements. Match input/output role, signal type, terminal assignment, software profile and power segment. A matching channel count alone does not establish interchangeability.
Order the exact product and condition your project requires, with assistance from quotation through delivery.
Your quotation references the complete manufacturer part number to keep the requested product clear.