Skip to content

Mitsubishi Electric FREQROL FR-E800 Standard Inverters

Mitsubishi Electric FR-E800 standard-model inverters with RS-485, induction/PM motor control and selectable normal/light-duty ratings. Start with ten coated FR-E820-4-60 three-phase 200 V models, from 0.1 to 11 kW ND; Ethernet, safety-communication and sealed variants are separate configurations.

View products

FR-E800 standard inverters

This first range uses the FR-E820-4-60 specification: three-phase 200–240 V, AM monitoring, initial 50 Hz/source logic and circuit-board coating. Select by duty current, then braking and panel space.

Select the complete order number

The duty profile, input supply and full specification suffix affect the installation. A capacity label alone does not identify the configuration.

  1. 01

    Choose ND or LD by current and overload

    ND provides 150% for 60 seconds and 200% for 3 seconds. LD provides 120% for 60 seconds and 150% for 3 seconds. A larger LD motor-capacity figure does not retain the ND overload allowance.

    • Use motor rated current and load profile, not kW alone.
    • Account for carrier-frequency, temperature and altitude derating.
  2. 02

    -4-60 means AM, 50 Hz/source and coating

    The -4 specification selects the standard RS-485 model with AM voltage monitoring and initial 50 Hz/source logic. -60 adds circuit-board coating without plated conductors.

    • -60 is not a 60 Hz setting.
    • Ethernet and safety-communication models are outside this standard collection.
  3. 03

    Distinguish the transistor from the resistor

    0008 and 0015 do not support a directly connected brake resistor. Larger selected models have a built-in brake transistor, but still need a separately selected resistor and thermal protection for regenerative braking.

    • Use the correct braking arrangement for repeated deceleration.
    • Reserve space for wiring, cooling and any plug-in option.