Honeywell Sensepoint XCL Gas Detectors
Honeywell Sensepoint XCL single-sensor fixed gas detectors for commercial and light-industrial ordinary locations. Compare gas range, analog or Modbus interface, optional relay hardware and Bluetooth-enabled commissioning. Separate from hazardous-area XRL detectors.
View productsSensepoint XCL complete gas detectors
The first batch pairs oxygen, CO, low-range H2S, hydrogen and methane catalytic detectors with analog-only and analog-plus-relay hardware. All ten are charcoal Bluetooth models; Modbus and non-Bluetooth compliance models are separate configurations.
Showing 1–10 of 10

Sensors and detection
Honeywell SPLCC1BARCXNZZ XCL Carbon Monoxide Detector with Relays
SPLCC1BARCXNZZ
New Original
$724.00

Sensors and detection
Honeywell SPLCC1BAXCXNZZ XCL Carbon Monoxide Detector
SPLCC1BAXCXNZZ
New Original
$713.00

Sensors and detection
Honeywell SPLCF6BARCXNZZ XCL Methane Catalytic Detector with Relays
SPLCF6BARCXNZZ
New Original
$799.00

Sensors and detection
Honeywell SPLCF6BAXCXNZZ XCL Methane Catalytic Detector
SPLCF6BAXCXNZZ
New Original
$798.00

Sensors and detection
Honeywell SPLCG1BARCXNZZ XCL Hydrogen Detector with Relays
SPLCG1BARCXNZZ
New Original
$868.00

Sensors and detection
Honeywell SPLCG1BAXCXNZZ XCL Hydrogen Detector
SPLCG1BAXCXNZZ
New Original
$868.00

Sensors and detection
Honeywell SPLCH1BARCXNZZ XCL Hydrogen Sulfide Low Range Detector with Relays
SPLCH1BARCXNZZ
New Original
$909.00

Sensors and detection
Honeywell SPLCH1BAXCXNZZ XCL Hydrogen Sulfide Low Range Detector
SPLCH1BAXCXNZZ
New Original
$798.00

Sensors and detection
Honeywell SPLCO1BARCXNZZ XCL Oxygen Detector with Relays
SPLCO1BARCXNZZ
New Original
$799.00

Sensors and detection
Honeywell SPLCO1BAXCXNZZ XCL Oxygen Detector
SPLCO1BAXCXNZZ
New Original
$762.00
Match the gas and scale
XCL is a single-sensor detector: the same enclosure does not mean the same sensing element or range.
Oxygen concentration
Fixed 0–25% volume scale. The two thresholds distinguish rising high oxygen from falling low oxygen; their numbering differs from XCD.
CO, hydrogen sulfide and hydrogen
Electrochemical ppm measurement, with different selectable ranges, alarm points and stabilization times. H2S low and high range remain separate detector configurations.
Methane catalytic
Factory methane calibration on a %LEL scale. Target-gas selection and calibration use the XCL-specific star-rating method.
Choose the installed interface, not just the enclosure
This initial batch deliberately keeps color and Bluetooth capability consistent so gas and relay differences are easy to compare.
- 01
Analog only or analog plus two relays
BAX versions provide the source/sink 4–20 mA interface without relay hardware; BAR versions add two changeover relays.
- Default relay allocation is fault plus Gas Alarm 1, not two dedicated gas alarm relays.
- The analog output still needs the documented load even when relays are used.
- 02
Keep analog and Modbus specifications separate
The selected analog models accept 11–32 V DC or 20–27 V AC. Modbus is a different wired-interface variant, not an extra feature supplied by Bluetooth.
- Relay hardware adds a 0.6 W power allowance.
- Set the physical source/sink and inhibit selectors for the controller circuit.
- 03
Ordinary locations only
The compact polycarbonate enclosure is IP65/Type 4, not an explosion-proof XRL housing. Use a sheltered location protected from direct UV and rain.
- Body dimensions are 113 × 113 × 59 mm.
- Select glands for the actual opened inner or outer knockout.
- 04
Distinguish a bump test from calibration
Remote gassing supports a response test; formal calibration uses the SPXCLCAL cap. Bluetooth supports setup, concentration readings and maintenance.
- Keep the detector registration QR code/activation details available.
- Use the gas-specific flow and stabilization time.