Honeywell Searchline Excel Plus Open Path Gas Detectors

Honeywell Searchline Excel Plus complete open-path hydrocarbon gas detector systems for 2–120 m coverage. Compare the stainless-steel M25 and ¾-inch NPT kits, with transmitter, receiver, universal mounts and plastic sunshades.

View products

Searchline Excel Plus complete system kits

Two complete system codes cover the cable-entry choices. Both use a cooperative transmitter/receiver pair; separate replacements, Excel Edge and Classic systems are not mixed into this collection.

Design the optical channel as a system

An open-path detector needs a clear beam, stable mounting and power at both ends; the measurement comes from the receiver.

  1. 01

    Path length and LEL·m are different quantities

    The permitted transmitter/receiver spacing is 2–120 m. The normal gas full scale is 0–5 LEL·m, integrating gas along the beam.

    • A point gas concentration cannot be inferred without knowing the cloud geometry.
    • Excel Edge is the separate 60–330 m perimeter-monitoring product.
  2. 02

    Budget power for both ends

    Both instruments accept 18–32 V DC. Cold-start transmitter demand is 17 W; receiver heating can require 15 W.

    • Running power changes with ambient temperature.
    • Cable voltage drop must leave at least 18 V at each instrument.
  3. 03

    Choose the receiver output and loop wiring

    The receiver provides 4–20 mA/HART, Modbus and three relays. Source, sink and isolated loops have different jumper arrangements.

    • HART minimum loop load 250 Ω; total load less than 600 Ω.
    • Relay contacts are rated 32 V AC/DC, 2 A resistive—not mains switching contacts.
  4. 04

    Leave room for alignment and service

    Maintain clear beam radius of at least 10 cm and scope access radius of at least 50 cm at the cowling.

    • Keep supports stable within ±0.5° angular movement.
    • Alignment scope, filters, pole kits and gassing cell are separate accessories.