Skip to content

2-Wire DC Proximity Sensors: Why the PLC Input Stays On

Compare OFF leakage, ON voltage and input current using an Omron E2E sensor and PLC input. Find why a two-wire sensor can keep a PLC input on.

  • Mason Alexander
  • Published Nov 23, 2026
Omron polarised E2E two-wire output circuit showing its load and proximity sensor in series

A steel flag moves away from a normally open proximity sensor. The sensor's output should turn off, but the PLC input stays on. Before changing the program or ordering another sensor, check how much current the input is still receiving. A two-wire electronic sensor can draw current through the input even in its OFF state.

Two limits tell you whether leakage can explain the symptom. Find the sensor's maximum OFF-state leakage current and the input module's permissible OFF-state current. If the sensor's maximum exceeds the input's limit, that pairing has no guaranteed OFF state. It can still happen to work on a particular machine. Swapping parts or adding a second sensor to the same input can expose a combination that was already outside the specified limits.

Follow the series circuit

In the Omron E2E diagram, the sensor and the load share a single path between the supply rails. When the load is a DC input, the current that powers the sensor in its OFF state also passes through the input circuit. In the ON state, the same series arrangement means that some supply voltage remains across the sensor. The PLC input gets what is left after the sensor and wiring drops.1

Omron polarised E2E two-wire output circuit showing its load and proximity sensor in series
Omron E2E catalog, p. 20. Follow the path from the supply through the load and sensor. This is the polarised two-wire variant. Use the exact model's diagram to locate the load relative to the input common.

A high-impedance meter can show voltage on an OFF input while only a small current is flowing. Measure at the input terminal relative to its actual common with the input still connected. An unloaded sensor lead gives a different circuit and cannot show whether that input will release.

Compare leakage and voltage drop separately

The two plots below use different axes because they describe different states. The left plot shows OFF leakage versus supply voltage. The right plot shows the voltage remaining across the ON sensor versus load current. The additional trace on the right is for the M1J-T variant. Even within the E2E family the suffix changes which trace applies.1

Paired Omron engineering curves for DC two-wire OFF-state leakage and ON-state residual voltage
Omron E2E catalog, p. 19. Use the curves to see how the two effects behave. For compatibility, use the specified maximum leakage and applicable residual-voltage limit.

A reading near the plotted curve for one unit is a useful diagnostic observation. Design the pairing from the published limits. Check the receiving module's actual OFF specification for its part number and revision. A typical ON current is a different rating and gives no OFF guarantee.

Work through an actual sensor and PLC input

Omron documents a 24 V nominal example with an E2E-X7D1-N and C200H-ID212 input unit. This is a useful reference for installed equipment because the catalog gives enough data to check all three conditions.1

Omron catalog parameters for the C200H-ID212 and E2E-X7D1-N with the two OFF-current limits highlighted
Omron E2E catalog, p. 26. The input side lists 1.3 mA for OFF. The sensor side lists 0.8 mA leakage. The part numbers at the bottom define the scope of these figures.
CheckCalculation for the documented pairWhat it establishes
OFF leakage1.3 mA input OFF limit − 0.8 mA sensor leakage = 0.5 mA margin.One sensor's specified leakage is within the input's OFF-current limit.
ON voltage20.4 V minimum supply − 3 V sensor drop = 17.4 V before wiring losses. The specified ON voltage is 14.4 V.3.0 V remains above the input's ON threshold in the catalog calculation.
ON current(20.4 V − 3 V − 4 V) ÷ 3 kΩ ≈ 4.5 mA.The calculated current clears the sensor's 3 mA minimum and lies below its 100 mA maximum. The extra 4 V term is the documented input's internal voltage drop.

In the same input model, Omron's calculation varies current with supply voltage. At 26.4 V, keeping the same two voltage-drop assumptions gives approximately 6.5 mA. For a different input module, obtain its own input characteristics before repeating that calculation. The catalog's 3 kΩ and 4 V describe this example.

Now consider two of the same sensors wired in parallel to one input. When both are OFF, the worst-case leakage budget becomes 0.8 + 0.8 = 1.6 mA. This exceeds the 1.3 mA limit by 0.3 mA. The arithmetic explains why an input that released reliably with one sensor may become unreliable after a second sensor is added. Confirm that the manufacturer permits the parallel wiring arrangement. If separate input channels are available, the PLC can combine the two signals in logic while each input sees only its own sensor.2

Check the point where the states disagree

  1. Read the sensor suffix and confirm NO or NC operation. On the E2E family, the red operation indication and green setting indication have different meanings. Use the timing chart for the actual suffix.1
  2. Compare the input channel indication and the raw PLC input with the target present and absent. If the raw input turns OFF while the program's condition stays ON, trace that condition in the program.
  3. If the raw input stays ON with the target absent, compare the loaded input voltage with the module's OFF region. Check for another device sharing the input, or an unintended connection to its supply, before attributing the voltage to sensor leakage.
  4. If the leakage budget fails, check the module's documented options. A compatible input, a suitable three-wire sensor, or an approved interface can resolve the mismatch. If the manufacturer specifies a shunt across the input, verify its OFF-voltage, ON-current and power limits for the actual circuit. An input filter can reject brief pulses. A sustained electrical ON state requires a circuit-level correction.

For the basic series connection, polarity, and other wire counts, see the proximity switch wiring guide.

References

  1. E2E Standard Proximity Sensor catalog, pp. 19, 20, 26

    Omron

  2. Connecting two or more proximity sensors in series or parallel

    Omron