Solid-State Relay Diagnostics: Load Failure, Overtemperature and Protection

Follow a heater circuit through SSR switching, current monitoring and fault alarms. Work through a two-heater detection threshold, AC timing and thermal loss, then distinguish diagnostics from independent load protection.

  • Xindustra Editorial Team
  • Published Nov 27, 2026
  • 11 min read
A real Carlo Gavazzi RAM1 solid-state relay showing its separate control and power connections

A heater controller can show its output as ON while the heater stays cold. It can also command OFF while a damaged solid-state relay continues supplying power. Both symptoms become easier to diagnose once the control signal, semiconductor switch and load-current measurement are treated as separate parts of the circuit.

An ordinary solid-state relay, or SSR, switches a load electronically. A monitored SSR adds observations of the load, supply or device temperature. Those observations can reveal a broken heater, a failed output or an overheating assembly, but the response depends on the fault and the particular relay. This article follows a resistive-heater circuit from the controller to the load, then shows how to interpret the signals and choose meaningful alarm settings.

A real Carlo Gavazzi RAM1 solid-state relay showing its separate control and power connections
Panel-mount RAM1 SSR, with separate control and load connections. Diagnostic features depend on the model; the monitored G3PF and RGC..M examples below have different packages. Photo: Jason Demicoli (Demjas), CC BY-SA 4.0; reused without annotations.

Photo credit: original photograph and author, licensed under CC BY-SA 4.0.

Follow the power path before interpreting the LEDs

In a typical AC-heater application, the controller supplies a relatively small signal to the SSR input. The SSR's output semiconductor controls a separate, higher-power circuit feeding the heater. Optical coupling can transfer the switching request across an isolation barrier; the controller's output does not provide the heater's operating power. OMRON's technical overview explains this distinction between the input, coupling and output sections.1

This immediately explains a common troubleshooting trap. An input LED can show that the SSR has received a command even when the heater supply is absent, a fuse is open, the heater is broken or the output semiconductor has failed. Conversely, removing the input signal cannot open a semiconductor that has physically failed short.

Single-phase heater power circuit with an SSR, current transformer, independent contactor and separate control and alarm paths
Functional single-phase heater circuit. Solid conductors carry load power; dashed blue paths represent control or diagnostic signals. CT measures the conductor feeding the heater. K1 provides a separate means of interrupting the power path. Protective earth is shown at the heater enclosure; component ratings, all-pole isolation, contactor actuation and the protective system must be designed for the actual installation. This is an original explanatory schematic, not a terminal wiring drawing.

The schematic gives three observations distinct jobs. The command says what the controller requested. The current transformer, or CT, indicates what current actually passed through the heater conductor. An alarm output reports the relay's interpretation of its measurements. Some equipment also provides an auxiliary output associated with switching status; its specified behavior must not be assumed to be an independent measurement of heater temperature or current.

A useful first question is therefore: which of these signals does the display actually represent? A heating-demand symbol on the controller and an alarm-free SSR are useful information, but neither proves that the process received the intended heat.

Why AC switching has its own timing

Many AC SSRs use a triac or a pair of thyristors. A zero-cross input function delays turn-on until the AC voltage is close to zero, reducing abrupt load-current transitions. The trigger circuit and zero-cross circuit perform switching functions; they are not heater-failure detectors.2

Once an AC thyristor output is conducting, removing its gate command does not interrupt it at an arbitrary point in the current waveform. Conduction ends as current falls below the device's holding requirement. For an ideal resistive heater, current and voltage are in phase, so their zero crossings coincide. With other load types that correspondence cannot be assumed. AC and DC output technologies should therefore be selected for the actual load.3

Illustrative 50 Hz voltage, input-command and heater-current timing for a zero-cross AC SSR
Calculated, ideal resistive-load example at 50 Hz. The ON command arrives at 4 ms and conduction begins at the next illustrated zero crossing, 10 ms. The OFF command arrives at 24 ms and current ends at 30 ms. The 6 ms intervals are consequences of these selected event times, not a published SSR specification or an alarm delay.

At 50 Hz, one complete cycle lasts 20 ms and a half-cycle lasts 10 ms. The example's short switching delays are normal consequences of its AC switching model. They must be distinguished from the much longer qualification time a diagnostic circuit may use before declaring a fault.

A suitable delay prevents normal switching transitions from being interpreted as failures. Changing a controller's time-proportioning period can also change whether an SSR has a long enough observation window. OMRON's G3PF documentation, for example, specifies conditions for heater-burnout detection under cycle control, including a minimum 200 ms control cycle and a minimum 50% output duty. It also identifies combinations where that detection function cannot be used.4

Detecting a broken heater needs a useful threshold

The simplest comparison is whether the expected load current appears during an ON command. That can reveal a completely open circuit. Partial load failure is more subtle: if several heaters share a circuit, one branch can break while current continues through the others.

Consider two identical resistive heaters in parallel on a 230 V supply. Each is assumed to draw 8 A at that voltage, corresponding to 1.84 kW and a resistance of 28.75 Ω. Together they draw 16 A. If one heater becomes open circuit, the other continues drawing 8 A. A detector set only to distinguish current from no current would miss the lost branch.

Calculated healthy and single-heater-failure current bands compared with a 12 A alarm setting
Illustrative two-heater calculation, with fixed resistance and a supply varying by ±5%. Healthy current spans 15.2–16.8 A; one open heater gives 7.6–8.4 A. The shaded 11.4–12.6 A interval is the G3PF datasheet's detection-current range for a nominal 12 A setting. The example leaves a gap on both sides; it is not a universal setting for heater banks.

The setting has to separate the lowest healthy current from the highest fault current. Under the example's fixed-resistance assumption, supply variation changes both bands proportionally. The healthy minimum is 16 × 0.95 = 15.2 A; the fault maximum is 8 × 1.05 = 8.4 A. A nominal 12 A setting falls between them even after allowing for the illustrated detection range.

OMRON's G3PF table gives that 12 A setting a detection range of 11.4–12.6 A. Its front switches use tens and ones digits. The range, rather than the nominal dial value alone, is the relevant comparison.4 In a real installation, heater resistance over temperature, supply tolerance, measurement uncertainty and branch imbalance may narrow or remove the gap. This calculation establishes a candidate threshold only for the stated assumptions.

A useful result of the calculation is also knowing when the proposed method will not work. If healthy and faulty current ranges overlap, no single threshold can reliably distinguish them. Separate branch monitoring or another observation is then needed. Increasing the alarm delay cannot repair an overlap in steady-state current.

The same reasoning becomes especially important with three-phase heater banks. The G3PF documentation discusses delta and star arrangements, including cases where the measured line current cannot identify the individual broken heater or where an unmonitored phase can hide the failure. The monitoring topology matters as much as the threshold.4

Read each alarm as a condition with a defined response

Monitoring options vary even within one product family. Carlo Gavazzi's RGC..M versions illustrate this: the documented monitoring scope is resistive loads, and the monitoring circuitry requires a separate supply. The manufacturer specifies distinct conditions for mains loss, load loss, output failure and overtemperature.5

RGC..M conditionDocumented qualificationImportant interpretation
Mains lossSupply absent for more than 1 sLoss of power and loss of the switching command are different observations.
Load lossOpen or absent load for more than 120 ms, with control ONThe alarm does not turn the output OFF while control remains present.
SSR output short circuitOutput remains ON for more than 250 ms without control voltageThe device attempts OFF, but a damaged output may not respond.
SSR output open circuitOutput pole does not switch ON within 250 msAn ON command alone cannot prove power reaches the load.
OvertemperatureInternal temperature monitoring tripsOutput is disabled; after cooling, restart is attempted if control remains ON.

Product example: RGC2/RGC3 DS ENG, 25 February 2026, pp. 24–28. These are documented conditions for that monitoring option, not general SSR timing values.5

For maintenance, the useful record is the combination of the alarm, command and actual load condition. An alarm may identify a condition without removing power. Clearing may occur automatically after the condition disappears. An automatic restart may be appropriate for the process—or may require additional control measures. Those outcomes should be established before using an alarm signal to drive a machine response.

Explain overheating through the heat path

An SSR's ON-state voltage drop means that a working relay can generate appreciable heat. OMRON gives a simple estimate: power loss is approximately the ON-state voltage drop multiplied by load current. Its G3NA-210B example uses 1.6 V and 8 A, producing 12.8 W.6

That is heat inside a switching assembly, not useful heat delivered to the process. It has to move from the semiconductor through its package and mounting interface into a heat sink or another specified cooling surface, then into the surrounding air.

Thermal path from an SSR semiconductor through its mounting interface and heat sink to cabinet air
Original thermal-path diagram. The 12.8 W value reproduces OMRON's stated G3NA-210B arithmetic example. The geometry is representative and is not the internal construction of the photographed RAM1. Thermal-interface and cooling requirements depend on the selected product.

A large heat sink cannot compensate for every defect upstream in that path. An unsuitable mounting surface or thermal interface can impede heat transfer before it reaches the fins. OMRON's application guidance describes the role of the heat-conductive interface between an SSR and its heat sink and requires the mounting arrangement to match the load.7

Cabinet air is the final part of the path. A blocked filter, failed fan or tightly packed enclosure can raise the local temperature while the heater current remains normal. The permitted load current must be read against the device's ambient-temperature and mounting conditions. OMRON's high-density-mounting guidance also notes that thermal stabilization takes time; a short cold-start observation does not establish the final operating condition.8

Overtemperature protection is therefore useful, but it does not replace thermal design. Optional shutdown variants can interrupt a healthy switching element when a temperature limit is reached. They cannot promise the same outcome after an output has already failed short. Loose power connections are another source of localized heating that deserves inspection under the appropriate isolation procedure.9

Separate three different meanings of protection

The term short-circuit protection can obscure three different tasks. A monitored SSR may detect its own output conducting unexpectedly. A fuse or coordinated protective device addresses excessive fault current. A separate contactor or breaker can remove load power when the electronic output cannot switch OFF. These functions should be named separately in the circuit documentation.

Carlo Gavazzi's RG product literature makes the distinction visible across variants: some include temperature protection, some add a semiconductor fuse, and others add current or system monitoring. A built-in diagnostic capability is not evidence that every variant contains the same fuse or shutdown hardware.10

The most consequential fault is an output failed short, because an OFF command can leave the heater energized. OMRON's SSR safety guidance explicitly calls for an additional contactor or breaker to remove load power on SSR failure. It also cautions that SSRs use semiconductors that may fail short.11 The independent interruption path shown earlier exists for this reason.

A normal heater current may remain below an overcurrent device's trip level even when the heater is being supplied at the wrong time. That is why an unwanted-ON condition and an excessive-current condition require separate reasoning. In the two-heater example, an SSR stuck ON could continue delivering the normal 16 A: the process can overheat without a load short circuit.

A short-circuit current rating must also be read with its coordination conditions. OMRON's G3PF specification states its rating with a specified fuse arrangement. It does not describe an SSR that independently opens that prospective fault current.12 Selection must consider the actual supply and protective combination.

Use the observations in a practical fault investigation

Before opening the panel or changing wiring, isolate the relevant supplies and verify the safe state using the site's established procedure. An input LED, an OFF command or the absence of an alarm is not an isolation test. Any energized measurement requires appropriate equipment and a qualified person.11

For a heater that stays cold, first establish whether the controller actually requests heat. Next distinguish the relay's input indication from a load-current observation. If the command is present but expected current is absent, investigate the power supply, protective devices, connections, heater continuity and switching path in a controlled order. OMRON's failure guidance identifies surges, excess inrush and installation conditions among the causes of damaged SSR elements.9

If current is reduced rather than absent, compare it with the expected branch currents and the alarm's threshold range. Check whether the observation was taken during a sufficiently long ON interval. A short observation during time-proportioning can look like loss of load even when the average process demand is behaving normally.

If substantial heater current continues after an OFF request and the documented switching interval has elapsed, treat the load as energized. Use the designed independent shutdown path and investigate the output rather than repeatedly sending OFF commands. Distinguish the observation from small specified leakage current: the G3PF specification, for example, lists nonzero OFF-state leakage.12

Finally, record the exact variant and settings alongside the observations: command state, measured current, alarm condition, local temperature and whether an independent interruption actually removed power. A replacement SSR should then be checked against the cause of failure. Replacing a heat-damaged unit without correcting its cooling path can leave the original problem in place.

References

  1. Overview of Solid-state Relays

    OMRON

  2. Explanation of Terms: trigger circuit and zero-cross circuit

    OMRON

  3. Technical Explanation for Solid-state Relays, CSM_SSR_TG_E_9_11

    OMRON

  4. G3PF Data Sheet, CSM_G3PF_DS_E_7_13, pp. 3–4

    OMRON

  5. RGC2/RGC3 DS ENG, 25 February 2026, pp. 24–28

    Carlo Gavazzi

  6. FAQ02235: calculating SSR heat generation

    OMRON

  7. Further Information: heat-radiation design and thermal interface

    OMRON

  8. FAQ03640: load current and ambient temperature under dense mounting

    OMRON

  9. FAQ02150: main causes and solutions of SSR failures

    OMRON

  10. RG Series brochure: protection and monitoring variants, p. 4

    Carlo Gavazzi

  11. Safety Precautions of Solid-state Relays

    OMRON

  12. G3PF Specifications: leakage and coordinated SCCR

    OMRON