How to Detect Clear Bottles on a Conveyor

Choose and test a clear-bottle sensor for a conveyor. Compare a Banner QS18E and a Q4X, teach the empty line and check PET bottles at the actual spacing and speed.

  • Mason Alexander
  • Published Nov 24, 2026
  • 6 min read
Banner application rendering of a Q4XTBCOD300-Q8 directed at clear bottles on a metal conveyor.

A clear PET bottle can be directly in front of a sensor while the receiver still sees enough light to report a clear path. The same bottle may switch the output at its shoulder, then drop out briefly through its sidewall. A reliable installation has to distinguish the weakest bottle signal from normal movement in the empty-line signal. If the station counts bottles, it also has to see a clear interval between them. 12

Start by choosing what the sensor sees with the conveyor empty. A clear-object retroreflective sensor watches the return from a matched reflector. A Q4X clear-object laser sensor watches a taught reference surface and looks for changes in distance and returned intensity. Both can work for bottle presence. The better fit depends on the mount, the available reference and the actual bottles. 13

Banner application rendering of a Q4XTBCOD300-Q8 directed at clear bottles on a metal conveyor.
Banner’s beverage-line rendering shows a Q4X clear-object sensor mounted beside the bottle path. The beam crosses a repeatable height on the bottle wall.

Banner illustrates the single-sided Q4X arrangement on a clear-bottle line. Its QS18E demonstration shows the fixed reflector that the other arrangement needs. 67

Choose a reflector or a taught reference surface

Station conditionStarting pointWhat to prove before release
A fixed reflector can fit across the lineBanner QS18E clear-object retroreflectiveThe weakest bottle changes the reflector return enough to switch, and a wet or dirty reflector does not cause a false bottle
A suitable matte surface is available, with no practical reflector mountBanner Q4X clear-object detection modelThe empty reference stays stable and every bottle produces a detectable change at the chosen height
Bottles can travel touching and the PLC needs an individual countProve an optical gap or change the station geometry or spacingEach pair generates two separate events and the input resets between them

A standard retroreflective sensor for opaque cartons may leave too much signal at the receiver when a clear bottle passes. Raising sensitivity alone can make the empty and occupied signals harder to separate. For the full comparison with ordinary through-beam and diffuse sensing, see the conveyor photoelectric sensor selection guide. 12

Set up a QS18E with a matched reflector

On the Banner QS18EP6XLPC, light goes from the sensor to the reflector and back through the same path. A bottle in that path can attenuate or redirect enough light to change the return. The reference is the reflector with the path clear. Select the reflector from the sensor's own table. Banner lists up to 1.3 m with the BRT-40X19A, 2.0 m with the BRT-51X51BM and 3.0 m with the BRT-92X92C. Those are specified pairing limits. Check the intended bottle at the installed spacing. 1

Yellow Banner QS18 sensor on a demo bracket, with its red spot centered on a small reflector.
Banner’s QS18 demonstration setup. Center the spot on the matched reflector with the path empty before teaching a reference.

Align the spot on the reflector with no bottle present, then use Light Set to teach that empty return. The quick-start guide identifies a successful Light Set by three green flashes followed by five rapid flashes of both indicators. If the return is insufficient, the same teach action can select Dark Set instead. Check the acceptance pattern before running the bottle trial. Light Set establishes the threshold. Dark Operate is a separate output choice that can make loss of return turn the output on. For the distinction between received light and the PLC bit, see Light-ON and Dark-ON explained. 12

Banner gives 16% as the default Light Set offset and 8% for weak contrast in stable conditions. A smaller offset makes a smaller loss of return detectable. It also leaves less separation from normal signal variation when the path is empty. If a dry empty bottle only switches at the more sensitive setting, test line vibration, a damp reflector and the actual cleaning cycle before accepting that configuration. Improve alignment or move the beam to a more repeatable height when the two states overlap. 12

Set up a Q4X with a stable empty reference

The Banner Q4XTBCOD300-Q8 can operate without a retroreflector. During teach, it records the distance and intensity of a fixed reference with the line empty. A clear bottle can change one or both measurements or introduce another reflection. The display shows how closely a reading matches the taught condition. Banner lists 75% as a starting match threshold for PET bottles and trays. The percentage expresses match to the taught reference. It does not represent the bottle's light transmission. 34

Banner Q4X mounting diagram with the bottle close to the sensor, a reference surface farther back, and the beam tilted down at least ten degrees in the illustrated view.
Banner’s Q4X mounting example separates the bottle from the reference surface. The illustrated beam is tilted away from perpendicular to the reference.

For this threaded-barrel model, Banner recommends a reference from 50 mm to the maximum sensing distance. The Q4XTBCOD300-Q8 has a 300 mm maximum. Use a fixed matte surface, keep the bottle closer to the sensor than the reference, and follow the manual's mounting-angle guidance. Move the sensor or reference if the bottle can only pass close to the reference surface. A small difference in geometry can make it harder for the sensor to distinguish the bottle from the empty condition. 34

The washdown example from Banner is a presence application. A stationary or accumulating bottle can keep the signal active long enough to meet a delay. The same delay can be counterproductive for a counter, where an extended active signal may erase the clear interval between bottles. Set delay from the behavior the PLC needs and check the actual output at the closest bottle spacing. 35

Trial the bottles the way they run

Teach the line empty first. Mark the beam height so you can repeat it after moving a bracket. Start with a relatively uniform section of the bottle wall where the beam crosses it at a repeatable position. If seams, the shoulder or an edge of the label cross the spot in production, deliberately include them in the trial. A good hand pass with one bottle orientation only establishes one of the sensor's working conditions.

Trial conditionChange one input at a timeWhat passes
Empty, dry and after normal cleaningWatch the installed reflector or reference with the belt stopped and runningThe output remains consistently in the empty state
Clear empty and filled samplesRun each material and fill level the station actually handlesEach sample produces a reliable occupied state at the chosen beam height
Label variants and rotationUse the allowed unlabeled and labeled samples and turn the seam or label edge through the beamNo extra transitions or blind positions
Worst lateral travel, fastest speed and tightest spacingRun at the real limits and include touching bottles if they occurPresence stays valid. A counter sees one event per bottle and resets before the next event

For a simple timing check, a 6 mm effective clear gap at 1.2 m/s lasts 5 ms. That is an illustrative estimate before sensor response, output delay, input filtering and PLC sampling. If an output's OFF delay is longer than the observed reset window, it can bridge the gap. With zero clear interval, a single presence output that stays continuously active supplies no new edge for the next bottle. Change the beam position, add spacing or use a different counting method instead of trying to recover edges with a threshold adjustment.

If a stationary bottle switches the sensor but counts drop at line speed, use the conveyor troubleshooting steps to compare the measured gaps with the PLC filter. If the raw bit fails even with a bottle held in place, check the PLC input wiring. Record the mount dimensions, reflector or reference, teach and output settings, and which samples and speeds passed. That gives the next shift a repeatable setup after a format change or sensor replacement.

References

  1. QS18E Clear Object Detection Quick Start Guide

    Banner Engineering · 195502 Rev. C

  2. QS18E Clear Object Detection Product Manual

    Banner Engineering · 194469 · July 2026

  3. Q4X Stainless Steel Discrete Laser Sensor Product Manual

    Banner Engineering · 181483 · September 2025

  4. Q4XTBCOD300-Q8 Clear Object Sensor specifications

    Banner Engineering · 95292

  5. Detecting Transparent Bottles in a Washdown Environment

    Banner Engineering

  6. QS18 Expert Clear Object Detection Demo Kit

    Banner Engineering

  7. Detecting Clear Glass and Plastic PET Bottles in Washdown Environments

    Banner Engineering