A fixture needs to confirm that a steel clamp has closed. A tank needs to report when liquid reaches a mark behind its plastic wall. Both tasks call for a switch without mechanical contact, but they ask the sensor to distinguish different things.
Start with what must change at the sensing face. An inductive sensor is usually the first choice when a nearby metal target moves into position. A capacitive sensor is a candidate when a non-metallic object or a change in material behind a non-metallic wall needs to be detected. Its suitability depends on how well the two installed states can be separated.
Use an inductive sensor to confirm a metal position
At GeTech's check fixture, an inductive sensor faces the metal toggle clamp. The control system requires the appropriate clamp positions before releasing the next inspection step. A second technology on the same fixture detects a different target. GeTech uses a small photoelectric sensor to check for O-rings at the ends of tubes. The clamp check and the O-ring check are separate jobs, even though they occur on the same station.2

An inductive sensor uses a coil to produce an electromagnetic field. A nearby metal target interacts with that field and changes the signal the electronics monitor. For a clamp or flag, check the actual target alloy, size and gap with the sensor in its final bracket. Standard models can have shorter range on non-ferrous metals than on the reference steel target. Use the chosen model's data if a replacement flag is aluminum or stainless steel, or if a small target barely overlaps the face.1
Decide what a capacitive sensor should see through
A capacitive sensor responds to changes in capacitance near its sensing face. That allows it to detect materials such as granules, plastic or liquid. For a point-level switch mounted outside a vessel, the wall is present both when the level is below the sensor and when the medium reaches it. The task is to detect the difference between those two conditions after mounting.3
At the Wasserburg plant, ifm documents a KNQ capacitive switch mounted on a sight glass or bypass with an adapter and cable ties. The switch checks for liquid at its installed height. The metal vessel is beside the measurement point. The sensor sees through the sight glass.4

A suitable polymer tank can also provide the sensing path. ifm's KQ10 installation example shows an exterior mount against a polymer tank. This model illustrates the mounting geometry for a capacitive level sensor. If the PLC only needs a low- or high-level signal, choose a point-level switch or a model with configurable switching points.5

Wall thickness and the medium matter together. A setup that distinguishes water from air can behave differently with oil, which generally produces less capacitive contrast. If the tank wall is metal, look for a suitable non-metallic sight glass or bypass, an approved insertion probe, or another level technology. A through-wall rating for a particular sensor and medium only applies under its stated conditions.3
Test the two states that must stay distinct
| Application | First choice to evaluate | What to reproduce before committing |
|---|---|---|
| Steel flag or clamp at end of travel | Inductive | Open and closed positions with the real flag, bracket, worst-case gap and any nearby metal. |
| Small plastic part in a fixture | Capacitive if the target and fixture are separable at close range. Consider photoelectric if there is a clear optical path. | Empty fixture, smallest part, off-center placement, and any nearby tooling that moves during the cycle. |
| Liquid or granules behind a non-metallic wall | Capacitive point-level switch | Actual wall and mounting layer, empty and filled states, expected buildup and the actual medium. |
| Liquid in a metal vessel | An appropriate probe or a sensor at a non-metallic bypass or sight glass | A sensing path to the medium, repeatable level at the switch position and access for cleaning or service. |
For a capacitive switch, fit the final bracket first. Teach or adjust the empty state according to the model instructions, then fill past the switch point and verify the output changes. Drain below the point and verify it clears. If a film remains after draining, repeat the test with that film present. Raise sensitivity only when the filled state is weak and the empty state still clears. A setup that works with a clean, dry wall needs to maintain that separation under the conditions the machine will see.3
Once the sensing principle and mounting work, check the output type, supply and pinout against the installed input using the proximity switch wiring guide.