Exact product identification
Your quotation references the complete manufacturer part number to keep the requested product clear.

6ES7132-6BH01-0BA0
Sixteen-channel Standard 24 V DC PNP output module rated 0.5 A per channel. Module-wise diagnostics, optional QI and temperature-dependent total current up to 8 A.
Warranty coverage and terms are confirmed with your order.
We coordinate the fastest available shipping option for your destination.
Available payment methods are handled through secure payment channels.
Carrier and delivery options are confirmed for your destination before dispatch.
Independent supplier: Xindustra is not an authorized distributor, reseller, or representative of Siemens. Brand names are used for identification and compatibility purposes only. Read disclaimer
Output ratings, load limits and configuration for the DQ 16x24VDC/0.5A ST.
This 15 mm-wide Standard module provides sixteen 0.5 A PNP outputs. The maximum 8 A module current is temperature-dependent; the sixteen-channel count does not guarantee every channel can carry 0.5 A at the highest operating temperature.
16
PNP, current-sourcing
24 V DC
0.5 A
8 A
Subject to mounting orientation and ambient-temperature derating
5 W
48 Ω to 12 kΩ
0.1 mA
Electronic
0.7–1.3; typical 1 A
50 / 100 µs typical with resistive load
The 0.5 A channel rating is the usable load-current limit. The electronic short-circuit response threshold is a protection characteristic, not permission to operate a channel above its rated current. Fault diagnostics provide an additional troubleshooting function; they do not increase the channel rating.
| Parameter / condition | Horizontal installation | Vertical installation |
|---|---|---|
| Up to +30 °C | 8 A | 8 A |
| Up to +40 °C | 8 A | 6 A |
| Up to +50 °C | 6 A | 4 A |
| Up to +60 °C | 4 A | Not within rated vertical operating range |
These are maximum module-total currents at the listed ambient-temperature limits, not a higher per-channel rating.
100 Hz
0.1 Hz
Higher rates depend on load current and the permitted switching-frequency curve in the module manual
10 Hz
Typically L+ − 50 V
Not permitted
Supported
Disable “Short circuit to L+” and “Wire break” diagnostics for the paired outputs to avoid false diagnostic messages
At +60 °C horizontal or +50 °C vertical installation, the module-total limit is 4 A. Distribute the actual load currents within that budget; do not parallel outputs to increase current. Inductive switching also depends on load current and the manual’s permitted-frequency curve.
24 V DC
Permissible range: 19.2–28.8 V DC
Yes
30 mA
Without load current
1 W
No
Yes
1000 m
600 m
| Parameter / condition | BaseUnit arrangement |
|---|---|
| 1-wire | BU type A0 |
| 2-wire | BU type A0 with AUX terminals, or a potential distributor module |
| 3-wire | BU type A0 with AUX terminals, or a potential distributor module |
A light-colored BaseUnit starts a new potential group; a dark-colored BaseUnit continues the voltage buses from the module on its left. Select the module’s potential-group parameter to match the physical BaseUnit arrangement. The electronic module and BaseUnit are separate order items.
All sixteen I/O terminals are output signals: terminal 1 is DQ0 through terminal 16 as DQ15. Return and additional conductor connections therefore need AUX terminals or a potential distributor module for the listed two- and three-wire arrangements.
Schematic circuit diagram
01/2025 · A5E03574420-AE, Figure 4-1. Original output circuit, terminal mapping, supply and backplane-bus connections.
Supported
Module-wise
Module-wise
No
Supported
Not supported
Not supported
Not supported
Not supported
2 bytes plus 2 bytes for QI
| Parameter / condition | Supported version / integration |
|---|---|
| STEP 7 TIA Portal | V14 with HSP0222; integrated from V15 |
| STEP 7 Classic | V5.5 SP3 with HSP0230 V7.0; integrated from V5.6 SP1 |
| PCS 7 | V8.1 SP1 |
| PROFINET | GSDML V2.3 |
| PROFIBUS | Separate GSD files, revisions 3 and 5 or later |
The module uses two bytes for sixteen output channels and a further two bytes when QI information is used. Fault reporting is module-wise, without individual red channel fault LEDs. TIA Portal V14 requires HSP0222; the module is integrated from V15.
15 × 73 × 58 mm
Electronic module; excludes BaseUnit and packaging
30 g
−30 to +60 °C
Operation below 0 °C requires hardware status FS03 or later
−30 to +50 °C
Operation below 0 °C requires hardware status FS03 or later
5000 m
Above 2000 m, additional installation restrictions apply as described in the ET 200SP system manual
CC00
Type A
1 module
6ES7132-6BH01-0BA0 identifies the DQ 16x24VDC/0.5A ST electronic module in a one-piece packing unit. Order the type A0 BaseUnit separately for the intended wiring arrangement. This is a standard digital I/O module, not a fail-safe I/O module, interface module or complete ET 200SP station.
Manufacturer data and installation resources for this exact module.
Order the exact product and condition your project requires, with assistance from quotation through delivery.
Your quotation references the complete manufacturer part number to keep the requested product clear.
Tell us whether you need new original, new surplus, used, refurbished or repaired equipment.
Shipping options are prepared around your destination, quantity and requested delivery date.
Access available manufacturer product data, manuals and certificates associated with the order number.