6ES7132-6BD21-0BA0
Four-channel Standard 24 V DC PNP output module rated 2 A per channel. Provides substitute values and module-wise fault diagnostics, with temperature-dependent total-current limits.
Warranty coverage and terms are confirmed with your order.
We coordinate the fastest available shipping option for your destination.
Available payment methods are handled through secure payment channels.
Carrier and delivery options are confirmed for your destination before dispatch.
Independent supplier: Xindustra is not an authorized distributor, reseller, or representative of Siemens. Brand names are used for identification and compatibility purposes only. Read disclaimer
Output ratings, load limits and configuration for the DQ 4x24VDC/2A ST.
A four-channel Standard PNP output module for 24 V DC loads up to 2 A per channel. It provides configurable substitute values and module-wise wire-break and short-circuit diagnostics. The current 6BD21 generation requires its own engineering support.
4
PNP, current-sourcing
24 V DC
2 A
8 A
Subject to mounting orientation and ambient-temperature derating
10 W
12 Ω to 3.4 kΩ
0.1 mA
Electronic
2.8–5.2 A
50 / 100 µs, typical, resistive load
The 2 A channel rating is the usable load-current limit. The electronic short-circuit response threshold is a protection characteristic, not permission to operate a channel above its rated current. Fault diagnostics provide an additional troubleshooting function; they do not increase the channel rating.
| Parameter / condition | Horizontal installation | Vertical installation |
|---|---|---|
| Up to +30 °C | 8 A | 8 A |
| Up to +40 °C | 8 A | 6 A |
| Up to +50 °C | 6 A | 4 A |
| Up to +60 °C | 4 A | Not within rated vertical operating range |
These are maximum module-total currents at the listed ambient-temperature limits, not a higher per-channel rating.
100 Hz
0.1 Hz
Higher rates depend on load current and the permitted switching-frequency curve in the module manual
10 Hz
Typically L+ − 50 V
Not permitted
Supported
Disable “Short circuit to L+” and “Wire break” diagnostics for the paired outputs to avoid false diagnostic messages
Calculate the sum of the four actual channel currents using the mounting-temperature matrix. At +60 °C horizontal installation, the module total is limited to 4 A, so four channels cannot all carry 2 A. Inductive loads also have a switching-frequency limit; the 100 Hz resistive-load rating does not apply to solenoids.
24 V DC
Permissible range: 19.2–28.8 V DC
Yes
20 mA
Without load current
1 W
No
Yes
1000 m
600 m
| Parameter / condition | BaseUnit arrangement |
|---|---|
| 1-wire | BU type A0 |
| 2-wire | BU type A0 |
| 3-wire | BU type A0 with AUX terminals, or a potential distributor module |
A light-colored BaseUnit starts a new potential group; a dark-colored BaseUnit continues the voltage buses from the module on its left. Select the module’s potential-group parameter to match the physical BaseUnit arrangement. The electronic module and BaseUnit are separate order items.
Each channel has two output terminal positions: DQ0 at 1/5, DQ1 at 2/6, DQ2 at 3/7 and DQ3 at 4/8. These are connections to four output channels, not eight independent outputs.
Schematic circuit diagram
04/2024 · A5E53132267-AA, Figure 4-1. Original output circuit, terminal mapping, supply and backplane-bus connections.
Supported
Module-wise
Module-wise
No
Supported
Not supported
Not supported
Supported
Not supported
1 byte plus 1 byte for QI
| Parameter / condition | Supported version / integration |
|---|---|
| STEP 7 TIA Portal | V19 with HSP0425; integrated from V20 |
| STEP 7 Classic | V5.5 SP3 with HSP0230 V11.0; integrated from V5.7 SP3 |
| PROFINET | GSDML V2.43 |
| PROFIBUS | Separate GSD files, revisions 3 and 5 or later |
TIA Portal V19 requires HSP0425; the module is integrated from V20. STEP 7 Classic support starts at V5.5 SP3 with HSP0230 V11.0. Do not treat the earlier 6BD20 configuration as this module’s catalog identity. Diagnostic messages are module-wise; there are no dedicated red channel fault LEDs.
15 × 73 × 58 mm
Electronic module; excludes BaseUnit and packaging
30 g
−30 to +60 °C
Full stated range for this current module generation
−30 to +50 °C
Full stated range for this current module generation
5000 m
Above 2000 m, additional installation restrictions apply as described in the ET 200SP system manual
CC02
Type A
1 module
6ES7132-6BD21-0BA0 identifies the DQ 4x24VDC/2A ST electronic module in a one-piece packing unit. Order the type A0 BaseUnit separately for the intended wiring arrangement. This current 6BD21 order number is not the older 6BD20 catalog number. It is not a fail-safe output module.
Manufacturer data and installation resources for this exact module.
Order the exact product and condition your project requires, with assistance from quotation through delivery.
Your quotation references the complete manufacturer part number to keep the requested product clear.
Tell us whether you need new original, new surplus, used, refurbished or repaired equipment.
Shipping options are prepared around your destination, quantity and requested delivery date.
Access available manufacturer product data, manuals and certificates associated with the order number.