Exact product identification
Your quotation references the complete manufacturer part number to keep the requested product clear.

6ES7131-6BH01-0BA0
Sixteen-channel Standard 24 V DC PNP input module with configurable filtering and module-level wire-break diagnostics. Uses type A0 BaseUnits and separate sensor-power distribution.
Warranty coverage and terms are confirmed with your order.
We coordinate the fastest available shipping option for your destination.
Available payment methods are handled through secure payment channels.
Carrier and delivery options are confirmed for your destination before dispatch.
Independent supplier: Xindustra is not an authorized distributor, reseller, or representative of Siemens. Brand names are used for identification and compatibility purposes only. Read disclaimer
Signal characteristics, sensor wiring and configuration for the DI 16x24VDC ST.
This Standard module acquires sixteen 24 V DC PNP input signals in a 15 mm-wide electronic module. Its denser terminal assignment uses all sixteen I/O terminals for inputs and does not provide the eight-channel module’s sensor-supply terminals.
16
Sinking input for PNP signals (P-reading)
Type 3
24 V DC
−30 to +5 V
Referenced to M
+11 to +30 V
Referenced to M
2.5 mA
0.05 / 0.1 / 0.4 / 0.8 / 1.6 / 3.2 / 12.8 / 20 ms
Additional line-length-dependent delay: 30–500 µs
1.5 mA
1000 m
600 m
Choose the 16-channel module when input density is the priority. Plan sensor-power distribution separately: sixteen signal channels do not mean sixteen integrated sensor supplies.
| Parameter / condition | BaseUnit arrangement |
|---|---|
| 1-wire | BU type A0 |
| 2-wire | BU type A0 plus a potential distributor module |
| 3-wire | BU type A0 plus a potential distributor module |
| 4-wire | BU type A0 plus a potential distributor module |
The module has no built-in 24 V encoder supply. One-wire signals use type A0 directly; the current data sheet specifies a potential distributor module for two-, three- and four-wire sensor arrangements.
A light-colored BaseUnit starts a new potential group; a dark-colored BaseUnit continues the voltage buses from the module on its left. Select the module’s potential-group parameter to match the physical BaseUnit arrangement. The electronic module and BaseUnit are separate order items.
One-wire sensor wiring
02/2019 · A5E03573442-AG, Figure 3-1. Original wiring and block diagram, including terminal numbers, voltage buses and the complete legend.
24 V DC
Permissible range: 19.2–28.8 V DC
Yes
90 mA
1.7 W
Not provided
No
Yes
Supported
Supported, module-wise
Not supported
No
Green
Green PWR LED
Green/red DIAG LED
Wire-break reporting is module-wise. When this function is enabled, connect a 25–45 kΩ resistor in parallel with each mechanical contact; this lets monitoring current flow when the contact is open. The resistor is unnecessary when wire-break detection is disabled.
| Parameter / condition | Supported version / integration |
|---|---|
| STEP 7 TIA Portal | V14; module manual lists HSP 0222 |
| STEP 7 Classic | V5.5 SP3; module manual lists HSP 0229 |
| PCS 7 | V8.1 SP1 |
| PCS neo | V1.0.0 |
| PROFINET | GSDML V2.3 |
| PROFIBUS | Separate GSD files, revisions 3 and 5 or later |
2 bytes plus 2 bytes for QI
Not supported
Not supported
Suitable for operation
I&M0 to I&M3
Not supported
Configure this exact ET 200SP module rather than a visually similar input module. Use the listed engineering-system support for the selected configuration path.
15 × 73 × 58 mm
Electronic module; excludes BaseUnit and packaging
28 g
−30 to +60 °C
Operation below 0 °C requires hardware status FS02 or later
−30 to +50 °C
Operation below 0 °C requires hardware status FS02 or later
5000 m
Above 2000 m, additional installation restrictions apply as described in the ET 200SP system manual
CC00
Type A
1 module
6ES7131-6BH01-0BA0 identifies the DI 16x24VDC ST electronic module in a one-piece packing unit. Order the type A0 BaseUnit separately for the intended wiring arrangement. This is a standard digital I/O module, not a fail-safe I/O module, interface module or complete ET 200SP station.
Manufacturer data and installation resources for this exact module.
Order the exact product and condition your project requires, with assistance from quotation through delivery.
Your quotation references the complete manufacturer part number to keep the requested product clear.
Tell us whether you need new original, new surplus, used, refurbished or repaired equipment.
Shipping options are prepared around your destination, quantity and requested delivery date.
Access available manufacturer product data, manuals and certificates associated with the order number.