Skip to content
Siemens SIMATIC ET 200SP DI 16x24VDC ST digital input module

Siemens ET 200SP DI 16x24VDC ST 6ES7131-6BH01-0BA0

6ES7131-6BH01-0BA0

Sixteen-channel Standard 24 V DC PNP input module with configurable filtering and module-level wire-break diagnostics. Uses type A0 BaseUnits and separate sensor-power distribution.

Availability
In Stock
Available quantity
12 units
Condition
New Original
SKU
6ES7131-6BH01-0BA0
Lifecycle
Active
$110.00
Request a quote
Ask a product question

12 months warranty

Warranty coverage and terms are confirmed with your order.

Fast shipping

We coordinate the fastest available shipping option for your destination.

Secure payment

Available payment methods are handled through secure payment channels.

Worldwide delivery

Carrier and delivery options are confirmed for your destination before dispatch.

Independent supplier: Xindustra is not an authorized distributor, reseller, or representative of Siemens. Brand names are used for identification and compatibility purposes only. Read disclaimer

Technical specifications

Signal characteristics, sensor wiring and configuration for the DI 16x24VDC ST.

Sixteen PNP input channels in a 15 mm module

This Standard module acquires sixteen 24 V DC PNP input signals in a 15 mm-wide electronic module. Its denser terminal assignment uses all sixteen I/O terminals for inputs and does not provide the eight-channel module’s sensor-supply terminals.

Signal characteristics

Digital inputs

16

Input logic

Sinking input for PNP signals (P-reading)

IEC 61131 input characteristic

Type 3

Nominal input voltage

24 V DC

Signal 0 voltage range

−30 to +5 V

Referenced to M

Signal 1 voltage range

+11 to +30 V

Referenced to M

Typical input current at signal 1

2.5 mA

Configurable input delay

0.05 / 0.1 / 0.4 / 0.8 / 1.6 / 3.2 / 12.8 / 20 ms

Additional line-length-dependent delay: 30–500 µs

2-wire sensor quiescent current, maximum

1.5 mA

Shielded cable length, maximum

1000 m

Unshielded cable length, maximum

600 m

Channel density changes the wiring plan

Choose the 16-channel module when input density is the priority. Plan sensor-power distribution separately: sixteen signal channels do not mean sixteen integrated sensor supplies.

BaseUnit requirements by sensor wiring

BaseUnit requirements by sensor wiring
Parameter / conditionBaseUnit arrangement
1-wireBU type A0
2-wireBU type A0 plus a potential distributor module
3-wireBU type A0 plus a potential distributor module
4-wireBU type A0 plus a potential distributor module

Provide sensor power separately

The module has no built-in 24 V encoder supply. One-wire signals use type A0 directly; the current data sheet specifies a potential distributor module for two-, three- and four-wire sensor arrangements.

Start or continue the potential group

A light-colored BaseUnit starts a new potential group; a dark-colored BaseUnit continues the voltage buses from the module on its left. Select the module’s potential-group parameter to match the physical BaseUnit arrangement. The electronic module and BaseUnit are separate order items.

Terminal assignment and signal path

One-wire sensor wiring

02/2019 · A5E03573442-AG, Figure 3-1. Original wiring and block diagram, including terminal numbers, voltage buses and the complete legend.

One-wire sensor wiring

Siemens DI 16x24VDC ST one-wire sensor wiring with terminal markings and circuit legend

02/2019 · A5E03573442-AG, Figure 3-1. Original wiring and block diagram, including terminal numbers, voltage buses and the complete legend.

Supply and isolation

Supply voltage L+

24 V DC

Permissible range: 19.2–28.8 V DC

Reverse polarity protection

Yes

Module current consumption, maximum

90 mA

Typical power loss

1.7 W

Built-in 24 V sensor supply

Not provided

Channel-to-channel isolation

No

Isolation from backplane bus

Yes

Fault detection and indication

Supply voltage monitoring

Supported

Wire-break diagnostics

Supported, module-wise

Sensor-supply short-circuit diagnostics

Not supported

Dedicated channel fault LEDs

No

Channel status LEDs

Green

Supply indication

Green PWR LED

Module indication

Green/red DIAG LED

Wire-break detection for mechanical contacts

Wire-break reporting is module-wise. When this function is enabled, connect a 25–45 kΩ resistor in parallel with each mechanical contact; this lets monitoring current flow when the contact is open. The resistor is unnecessary when wire-break detection is disabled.

Engineering system support

Engineering system support
Parameter / conditionSupported version / integration
STEP 7 TIA PortalV14; module manual lists HSP 0222
STEP 7 ClassicV5.5 SP3; module manual lists HSP 0229
PCS 7V8.1 SP1
PCS neoV1.0.0
PROFINETGSDML V2.3
PROFIBUSSeparate GSD files, revisions 3 and 5 or later

Address space and functions

Input address space

2 bytes plus 2 bytes for QI

Firmware update

Not supported

Isochronous operation

Not supported

PROFINET R1 interface modules

Suitable for operation

Identification and maintenance data

I&M0 to I&M3

Safety functions

Not supported

Configure the exact module identity

Configure this exact ET 200SP module rather than a visually similar input module. Use the listed engineering-system support for the selected configuration path.

Module dimensions and operating conditions

Dimensions W × H × D

15 × 73 × 58 mm

Electronic module; excludes BaseUnit and packaging

Approximate module weight

28 g

Horizontal operating temperature

−30 to +60 °C

Operation below 0 °C requires hardware status FS02 or later

Vertical operating temperature

−30 to +50 °C

Operation below 0 °C requires hardware status FS02 or later

Maximum installation altitude

5000 m

Above 2000 m, additional installation restrictions apply as described in the ET 200SP system manual

Color code

CC00

Mechanical coding

Type A

Packing unit

1 module

What this order number includes

6ES7131-6BH01-0BA0 identifies the DI 16x24VDC ST electronic module in a one-piece packing unit. Order the type A0 BaseUnit separately for the intended wiring arrangement. This is a standard digital I/O module, not a fail-safe I/O module, interface module or complete ET 200SP station.

Sourcing and order support

Order the exact product and condition your project requires, with assistance from quotation through delivery.

Exact product identification

Your quotation references the complete manufacturer part number to keep the requested product clear.

Condition options

Tell us whether you need new original, new surplus, used, refurbished or repaired equipment.

International delivery

Shipping options are prepared around your destination, quantity and requested delivery date.

Documentation support

Access available manufacturer product data, manuals and certificates associated with the order number.